Fujitsu AOTG18LACC Installation guide

Category
Split-system air conditioners
Type
Installation guide
SPLIT AIR CONDITIONER
INSTALLATION MANUAL
(PART No. 9332809046-02)
R410A
REFRIGERANT
This Air Conditioner contains and operates
with refrigerant R410A.
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED
BY QUALIFIED PERSONNEL.
Refer to Commonwealth, State, Territory and local legislation,
regulations, codes, installation & operation manuals, before
the installation, maintenance and/or service of this product.
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and installation
and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional
piping and are nuts with the R410A piping and are nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional re-
frigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when storing the
piping, securely seal the opening by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and always charge
from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the
diameter of each port has been changed.
It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
Charge hose
To increase pressure resistance, the hose material and base size were changed.
Vacuum pump
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Gas leakage detector
Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or
discolored portion (especially on the interior surface). Otherwise, the expansion value or
capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is
necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table.
Never use copper pipes thinner than that in the table even when it is available on the market.
Thicknesses of Annealed Copper Pipes
Thickness (mm)
Nominal
diameter (in.)
Outer diameter
(mm)
R410A [ref.] R22
1/4 6.35 0.80 0.80
1/2 12.70 0.80 0.80
WARNING
Do not use the existing (for R22) piping and are nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc. (Use the special R410A materials.)
When installing and relocating the air conditioner, do not mix gases other than the speci ed refrigerant (R410A) to enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
For authorized service personnel only.
WARNING
For the room air conditioner to operate satisfactory, install it as outlined in this installation manual.
Connect the indoor unit and outdoor unit with the air conditioner piping and cables available standards parts. This installation manual describes the correct
connections using the standard accessories and the parts speci ed in this installation manual.
Have installation work done by authorized service personnel only.
Do not use this equipment with air or any other unspeci ed refrigerant in the refrigerant lines. Excess pressure can cause a rupture.
Do not use an extension cable.
Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved.
The maximum length of the piping is 30 m. The minimum length of the piping is 5 m. The maximum height difference of the piping is 20 m.
If the units are further apart than these, correct operation can not be guaranteed.
Tapping screw
Hooks
Connector cover
Tapping screw
OUTDOOR UNIT INSTALLATION
OPERATING
RANGE
WARNING
Install the unit where it will not be tilted by more than 5°.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
Outdoor temperature
Cooling Mode
Dry Mode
About -10 to 46°C
Heating Mode About -15 to 24°C
POWER
WARNING
The rated voltage of this product is 240 V AC 50 Hz. Use a circuit breaker and receptacle matched to the capacity of the air
conditioner.
Do not extend the power cable.
Before turning on the power, check if the voltage is within the
220 V -10 % to 240 V +10 % range.
Perform wiring work in accordance with standards so that the air conditioner
can be operated safely and positively.
Always use a special branch circuit and install a special receptacle to
supply power to the room air conditioner.
Install a leakage circuit breaker in accordance with the related laws and
regulations and electric company standards.
CAUTION
The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances. When the current contracted ca-
pacity is insuf cient, change the contracted capacity.
When the voltage is low and the air conditioner is dif cult to start, contact the power company the voltage raised.
ELECTRICAL REQUIREMENT
Install all electrical works in accordance to the
national standard.
Install the disconnect device with a contact
gap of at least 3 mm in all poles nearby the
units. (Both indoor unit and outdoor unit)
Install the circuit breaker nearby the units.
Electric wire size and breaker capacity:
Cable Conductor size [mm
2
] Type Remarks
Power supply cable 4.0
Type 60245
IEC 57
2Cable+Earth(Ground),1φ240V
Connection cable 1.5 3Cable+Earth(Ground),1φ240V
Installation instruction on the back.
Decide the mounting position with the customer as follows:
(1) If possible, do not install the unit where it will be exposed to direct sunlight. (If necessary, install a blind that
does not interfere with the air ow.)
(2) Do not install the unit where a strong wind blows or where it is very dusty.
(3) Do not install the unit where people pass.
(4) Take your neighbors into consideration so that they are not disturbed by air blowing into their windows or by
noise.
(5) Provide the space shown in the gure so that the air ow is not blocked. Also for ef cient operation, leave
open three of the four directions front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the outdoor units and install positively so that the units will
not topple or fall.
CAUTION
Do not install the outdoor unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or
the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam. It will deteriorate plastic
parts, causing the parts to fail or the unit to leak water.
Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas,
acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
Area containing equipment that generates electromagnetic interference. It will cause the control system to
malfunction, preventing the unit from operating normally.
Area that can cause combustible gas to leak, contains suspended carbon bers or ammable dust, or volatile
in ammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a re.
Area that has heat sources, vapors, or the risk of the leakage of ammable gas in the vicinity.
Area where small animals may live. It may cause failure, smoke or re if small animals enter and touch
internal electrical parts.
Area where animals may urinate on the unit or ammonia may be generated.
When the outdoor temperature is 0°C or less, do not use the accessory drain pipe . If the drain pipe are
used, the drain water in the pipe may freeze in extremely cold weather.
Do not place any other electrical products or household belongings under indoor unit or outdoor unit. Dripping
condensation from the unit might get them wet, and may cause damage or malfunction of your property.
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach
the unit.
Do not touch the aluminum ns of heat exchanger built-in the indoor or outdoor unit to avoid personal injury
when you install or maintain the unit.
In the area with heavy snowfall, if the intake and outlet of outdoor units blocked with snow, it might become
dif cult to get warm and it is likely to cause of the breakdown.
Please construct a canopy and a ped-estal or place the unit on a high stand (local con gured).
SELECTING THE MOUNTING POSITION
54 cm
32 cm
INSTALLATION
DIAGRAM
INDOOR UNIT
[OUTDOOR UNIT]
10 cm
or over
60 cm or over
10 cm or over
20 cm
or over
25 cm
or over
5 cm or over
OUTDOOR UNIT ACCESSORIES
Drain pipe
1
Drain cap
3
Set the unit on a strong stand such as thing made of concrete blocks to
minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Connector cover removal
Remove the tapping screws.
Installing the connector cover
(1) After inserting the four hooks, then slide the cover.
(2) Tighten the tapping screws.
Outdoor
unit
bottom
Drain
pipe
Drain cap
Drain cap
Breaker
capacity
25(A)
NL321
12 3
Outdoor unit terminal block
Indoor unit terminal block
Connection cable
Earth
screw
Earth
screw
Power supply cable
(1) Remove the outdoor unit connector cover.
(2) Bend the end of the cable as shown in the gure.
(3) Connect the end of the connection cable fully into the
terminal block.
(4) Fasten the sheath with a cable clamp.
(5) Install the connector cover.
Connection cable wiring
Run the connection cable to the rear of the outdoor unit
within the
A
range of the arrows shown in the gure.
(The connector cover becomes dif cult to install.)
30mm
12mm
5mm
5mm
12mm
20mm
20mm
12mm
5mm
5mm
12mm
20mm
Connection cable Power supply cable
OUTDOOR UNIT WIRING
Connection cable
Cable clamp
Cable clamp
Earth
screw
Insulation
tube
Connection cable
Hole
8 cm
10 cm
CAUTION
Match the terminal block numbers and connection cable colors with those
of the indoor unit.
Erroneous wiring may cause burning of the electric parts.
Always fasten the outside covering of the connection cable with the cable
clamp. (If the insulator is chafed, electric leakage may occur.)
Securely earth the power cable.
Connect the connection cables rmly to the terminal block. Imperfect installa-
tion may cause a re.
Do not use the earth screw for an external connector. Only use for intercon-
nection between two units.
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or forced cooling
operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling operation.)
(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve (large) and opening the low-
pressure valve slightly.
(2) Close the valve stem of 2 way valve (small) completely.
(3) Start the cooling operation or following forced cooling operation.
When using the remote controller
Press the TEST RUN button after starting the cooling operation by the remote controller.
The operation indicator lamp and timer indicator lamp will begin to ash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote controller is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)
(4) Close the valve stem of 3 way valve (large) when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm
2
).
(5) Stop the operation.
Press the START/STOP button of the remote controller to stop the operation.
Press the MANUAL AUTO button when stopping the operation from indoor unit side.
(It is not necessary to press on keeping for more than 10 seconds.)
WARNING
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation 2 way or 3 way valve open. This may cause abnormal pressure in the refrigera-
tion cycle that leads to rupture and even injury.
PUMP DOWN
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation
set or procured at the site) to the wall pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the are surface and tightening the nut
hand tight, tighten the nut to the speci ed tightening torque with a torque
wrench. (Table 1)
FLARING
(1) Cut the connection pipe to the necessary
length with a pipe cutter.
(2) Hold the pipe downward so that cuttings
will not enter the pipe and remove the
burrs.
(3) Insert the are nut onto the pipe and are
the pipe with a aring tool.
Insert the are nut (always use the are nut attached to the indoor and out-
door units respectively) onto the pipe and perform the are processing with
a are tool.
Use the special R410A are tool, or the conventional (for R22) are tool.
When using the conventional are tool, always use an allowance adjustment gauge and
secure the A dimension shown in table 2 .
BENDING PIPES
(1) When bending the pipe, be careful not to crush it.
(2) To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or over.
(3) If the copper pipe is bend the pipe or pulled to often, it will become stiff.
Do not bend the pipes more than three times at one place.
CONNECTING THE PIPING
Tighten with two wrenches.
Torque
wrench
Wrench ( xed)
Flare nut
Indoor unit pipe
Connection pipe
To prevent gas leakage, coat the are
surface with refrigerator oil.
Table 1 : Flare nut size and tightening torque
Flare nut
Diameter (mm) Torque (N
.
m)
6.35 mm dia. 17 16 18
12.70 mm dia. 26 49 61
Table 2 : Pipe outside diameter
Pipe outside
diameter
A (mm)
Flare tool for
R410A, clutch type
Conventional (R22) are tool
Clutch type Wing nut type
ø 6.35 mm (1/4”) 0 to 0.5 1.0 to 1.5 1.5 to 2.0
ø 12.70 mm (1/2”) 0 to 0.5 1.0 to 1.5 1.5 to 2.0
WARNING
During installation, make sure that the refrigerant pipe is attached rmly
before you run the compressor. Do not operate the compressor under the
condition of refrigerant piping not attached properly with 2-way or 3-way
valve open. This may cause abnormal pressure in the refrigeration cycle
that leads to rupture and even injury.
Check if [L] is ared uniformly and is
not cracked or scratched.
Die
A
Pipe
AIR PURGE
Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the outdoor unit at the
factory.
Close the high pressure side valve of the gauge manifold fully and do not
operate it during the following work.
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed fully.
3. Connect the gauge manifold charge hose to the charging port of the 3-way
valve (side with the projection for pushing in the valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the are nut of the 3-way valve and check if air enters, then
retighten the are nut.
(When the are nut is loosened the operating sound of the vacuum pump
changes and the reading of the compound pressure gauge goes from minus
to zero.)
7. Pump down the system for at least 15 minutes, then check if the compound
pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of the gauge
manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the compound
pressure gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and
disconnect the charge hose from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the charge hose is dis-
connected, it may be dif cult to disconnect the charge hose.)
10. Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon
wrench. (After the valve stem begins to turn, turn it with a torque of less than 2.9
N • m (30 kgf • cm) until it stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and the charging
port cap.
Additional charge
Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit
at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.
Pipe length 15 m 20 m 25m 30 m Rate
Additional refrigerant None +100g +200g +300 g 20 g/m
3-way valve
2-way valve
Flare nut
Valve stem
Blank cap
Charge hose
Charging port
Vacuum pump
Charge
hose
High
pressure
side valve
(closed)
Pressure gauge
Gauge manifold
Compound pressure gauge
-0.1 MPa
(-76 cmHg
-1 bar)
Low pressure
side valve
Charging port cap
CAUTION
Refrigerant must not be discharged into atmosphere.
After connecting the piping, check the joints for gas leakage with gas
leak detector.
Tightening torque
Blank cap(2-way valve) 20 to 25 N•m (200 to 250 kgf•cm)
Blank cap(3-way valve) 28 to 32 N•m (280 to 320 kgf•cm)
Charging port cap 12.5 to 16 N•m (125 to 160 kgf•cm)
CAUTION
When adding refrigerant, add the refrigerant from the charging port at
the completion of work.
The maximum length of the piping is 30 m. If the units are
further apart than this, correct operation can not be guaranteed.
Between 15 m and 30 m, when using a connection pipe other than that in
the table, charge additional refrigerant with 20 g/1 m as the criteria.
Perform test operation and check items below.
For the test operation method, refer to the operating manual.
The outdoor unit, may not operate, depending on the room temperature. In this case, press the TEST RUN button on the remote controller while the air
conditioner is running, (Point the transmitter section of the remote controller toward the air conditioner and press the TEST RUN button with the tip of a ball-
point pen, etc.)
To end test operation, press the remote controller START/STOP button.
(When the air conditioner is run by pressing the TEST RUN button, the OPERATION indicator lamp and TIMER indica-
tor lamp of the indoor unit will simultaneously ash slowly.)
OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
TEST RUN
Transmitter section
Test run button
A
CAUTION
Fasten a are nut with a torque wrench as instructed in this manual. If
fastened too tight, the are nut may be broken after a long period of time
and cause a leakage of refrigerant..
NL321
How to xed connection cable at
the cable clamp
After passing the connection cable through
the insulation tube, fasten it with the cable
clamp.
Insulation tube
Insulation tube
Cable clamp
Use VW-1, 1.0 mm thick, PVC tube as the
insulation tube.
  • Page 1 1
  • Page 2 2

Fujitsu AOTG18LACC Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI