Moxa ioLogik E1510-T Specification

Category
Network extenders
Type
Specification
ioLogik E1500 Series Users Manual
Second Edition, August 2012
www.moxa.com/product
© 2012 Moxa Inc. All rights reserved.
ioLogik E1500 Series Users Manual
The software described in this manual is furnished under a license agreement and may be used only in accordance with
the terms of that agreement.
Copyright Notice
© 2012 Moxa Inc. All rights reserved.
Trademarks
The MOXA logo is a registered trademark of Moxa Inc.
All other trademarks or registered marks in this manual belong to their respective manufacturers.
Disclaimer
Information in this document is subject to change without notice and does not represent a commitment on the part of
Moxa.
Moxa provides this document as is, without warranty of any kind, either expressed or implied, including, but not limited
to, its particular purpose. Moxa reserves the right to make improvements and/or changes to this manual, or to the
products and/or the programs described in this manual, at any time.
Information provided in this manual is intended to be accurate and reliable. However, Moxa assumes no responsibility for
its use, or for any infringements on the rights of third parties that may result from its use.
This product might include unintentional technical or typographical errors. Changes are periodically made to the
information herein to correct such errors, and these changes are incorporated into new editions of the publication.
Technical Support Contact Information
www.moxa.com/support
Moxa
Americas
Toll
-free: 1-888-669-2872
Tel:
+1-714-528-6777
Fax:
+1-714-528-6778
Moxa China (Shanghai office)
Toll
-free: 800-820-5036
Tel:
+86-21-5258-9955
Fax:
+86-21-5258-5505
Moxa Europe
Tel:
+49-89-3 70 03 99-0
Fax:
+49-89-3 70 03 99-99
Moxa A
sia-Pacific
Tel:
+886-2-8919-1230
Fax:
+886-2-8919-1231
Moxa India
Tel:
+91-80-4172-9088
Fax:
+91-80-4132-1045
Table of Contents
1. Introduction to the ioLogik E1500 ..................................................................................................... 1-1
Quick Start Guide ............................................................................................................................... 1-2
Product Features ................................................................................................................................ 1-3
Inside the Box .................................................................................................................................... 1-3
Ordering Information .......................................................................................................................... 1-3
Specifications ..................................................................................................................................... 1-3
Common Specifications ................................................................................................................ 1-3
ioLogik E1510-T .......................................................................................................................... 1-4
ioLogik E1512-T .......................................................................................................................... 1-4
Physical Dimensions ............................................................................................................................ 1-5
Hardware Reference ............................................................................................................................ 1-6
Panel Guide ................................................................................................................................ 1-6
LED Indicators ............................................................................................................................ 1-6
I/O Circuit Diagram ............................................................................................................................. 1-7
Isolation DI (DI channels) ............................................................................................................ 1-7
DI Circuit (DIO channels) ............................................................................................................. 1-7
DO Circuit (DIO channels) ............................................................................................................ 1-7
2. Initial Setup ...................................................................................................................................... 2-1
Hardware Installation .......................................................................................................................... 2-2
Connecting the Power .................................................................................................................. 2-2
Grounding the ioLogik E1500 ........................................................................................................ 2-2
Connecting to the Network ........................................................................................................... 2-2
I/O Wiring Diagrams .................................................................................................................... 2-3
Software Installation ........................................................................................................................... 2-5
Load Factory Defaults .......................................................................................................................... 2-5
3. Using the Web Console ...................................................................................................................... 3-1
Introduction to the Web Console ........................................................................................................... 3-2
Overview ........................................................................................................................................... 3-3
Network Settings ................................................................................................................................ 3-3
General Settings ......................................................................................................................... 3-3
Ethernet Configuration ................................................................................................................. 3-4
User-defined Modbus Addressing .......................................................................................................... 3-4
Default Address........................................................................................................................... 3-5
Active OPC Server Settings .................................................................................................................. 3-5
Tag Generation ................................................................................................................................... 3-5
I/O Settings ....................................................................................................................................... 3-7
DI Channels ................................................................................................................................ 3-7
DO Channels ............................................................................................................................... 3-9
System Management ......................................................................................................................... 3-11
IP Accessibility .......................................................................................................................... 3-11
Network Connection................................................................................................................... 3-12
Firmware Update ....................................................................................................................... 3-12
Import System Configuration Settings ......................................................................................... 3-12
Export System Configuration Settings .......................................................................................... 3-13
Change Password ...................................................................................................................... 3-13
Load Factory Defaults ........................................................................................................................ 3-13
Save/Restart .................................................................................................................................... 3-14
4. Using ioSearch .................................................................................................................................. 4-1
Introduction to ioSearch ...................................................................................................................... 4-2
ioSearch Main Screen .......................................................................................................................... 4-2
Main Screen Overview .................................................................................................................. 4-2
Main Items ........................................................................................................................................ 4-3
System ...................................................................................................................................... 4-3
Sort ........................................................................................................................................... 4-4
Quick Links ................................................................................................................................. 4-4
Main Function ..................................................................................................................................... 4-4
Locate ........................................................................................................................................ 4-5
Firmware Upgrade ....................................................................................................................... 4-5
Unlock ....................................................................................................................................... 4-5
Import ....................................................................................................................................... 4-6
Export ........................................................................................................................................ 4-6
Change IP Address ...................................................................................................................... 4-7
Batch TCP/IP Configuration of Multiple Devices ............................................................................... 4-7
Restart System ........................................................................................................................... 4-8
Reset to Default .......................................................................................................................... 4-8
Mass Deployment (Import) ........................................................................................................... 4-9
Mass Deployment (export) ........................................................................................................... 4-9
5. Active OPC Server Utility ................................................................................................................... 5-1
Active OPC Server............................................................................................................................... 5-2
OLE for Process Control ................................................................................................................ 5-2
Active OPC ServerFrom Pull to Push ............................................................................................ 5-3
Features of Active OPC Server .............................................................................................................. 5-5
One Simple Click Creates Active Tags ............................................................................................ 5-5
Faster, More Accurate Data Collection than Traditional “Pull Technology” ............................................ 5-5
Active OPC Server Overview ................................................................................................................. 5-6
Installing Active OPC Server ......................................................................................................... 5-6
Main Screen Overview .................................................................................................................. 5-6
Menu Bar ................................................................................................................................... 5-6
A. Modbus/TCP Default Address Mappings ............................................................................................ A-1
E1510 User Defined Modbus ................................................................................................................. A-2
E1512 User-Defined Modbus ................................................................................................................ A-6
B. Network Port Numbers ...................................................................................................................... B-1
C. Factory Defaults ................................................................................................................................ C-1
D. Pinouts .............................................................................................................................................. D-1
E. FCC Interference Statement .............................................................................................................. E-1
F. European Community (CE) ................................................................................................................ F-1
1
1. Introduction to the ioLogik E1500
The ioLogik E1500 Ethernet I/O product is housed in a rugged aluminum case, and is compliant with the EN
50121-3-2, EN 50121-4 and essential sections of EN 50155 standards, all of which define standards for
electronic equipment used in rolling stock applications. I/O channels on the ioLogik E1500 are individually
isolated from one another to protect against power surges and to ensure that data communications remain
highly stable. This is an important factor to consider when choosing an Ethernet I/O solution, since safety is
always a top priority for railway applications.
The following topics are covered in this chapter:
Quick Start Guide
Product Features
Inside the Box
Ordering Information
Specifications
Common Specifications
ioLogik E1510-T
ioLogik E1512-T
Physical Dimensions
Hardware Reference
Panel Guide
LED Indicators
I/O Circuit Diagram
Isolation DI (DI channels)
DI Circuit (DIO channels)
DO Circuit (DIO channels)
ioLogik E1500 Series Introduction to the ioLogik E1500
1-2
Quick Start Guide
Overview
1. Product Features
2. Product Model Information
Getting Started
1. Hardware Installation
2. I/O Wiring Diagram
3. ioSearch Installation
Basic Configuration
1. Introduction to the Web Console
2. Network Settings for the Web Console
3. User-defined Modbus Addressing
4. Active OPC Server Settings
5. I/O Settings
6. Firmware Update
Software Configuration
1. ioSearch Setup
2. Active OPC Setup
ioLogik E1500 Series Introduction to the ioLogik E1500
1-3
Product Features
Compliant with EN 50121-3-2, EN 50121-4 and essential sections of EN 50155
Wide operating temperature: -40 to 85°C (-40 to 185°F)
Channel-to-Channel isolation (DI only)
Robust and compact design for harsh environments
Active communication with patented Active OPC Server
User-defined Modbus/TCP addressing
MXIO programming library for Windows and WinCE VB/VC.NET and Linux C APIs
Web configuration with Import/Export function
Inside the Box
The ioLogik E1500 is shipped with the following items:
ioLogik E1500 remote Ethernet I/O server
Documentation and software CD
Quick installation guide
NOTE: Notify your sales representative if any of the above items are missing or damaged.
Ordering Information
Model Description
ioLogik E1510-M12-T Ethernet remote I/O, M12 connector, 12 DIs, -40 to 85°C operating
temperature
ioLogik E1512-M12-T Ethernet remote I/O, M12 connector, 4 DIs, 4 DIOs, -40 to 85°C operating
temperature
ioLogik E1510-M12-CT-T Ethernet remote I/O, M12 connector, 12 DIs, coating, -40 to 85°C operating
temperature
ioLogik E1512-M12-CT-T Ethernet remote I/O, M12 connector, 4 DIs, 4 DIOs, coating, -40 to 85°C
operating temperature
Specifications
Common Specifications
LAN
Ethernet:
1 10/100 Mbps switch port, M12
Protection:
1.5 KV magnetic isolation
Protocols:
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Power Requirements
Power Input:
24 VDC nominal, 12 to 48 VDC
Note: Compliant with EN 50155 at 24 VDC
Physical Characteristics
Wiring:
I/O cable max. 14 AWG
Dimensions:
144 x 124 x 30 mm (5.67 x 4.88 x 1.18 in)
Weight:
825 g
Mounting:
DIN rail (standard), wall (with optional kit)
Environmental Limits
ioLogik E1500 Series Introduction to the ioLogik E1500
1-4
Operating Temperature:
-40 to 85°C (-40 to 185°F)
Storage Temperature:
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity:
5 to 95% (non-condensing)
Altitude:
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Conformal Coating:
Applies only to -CT models
Standards and Certifications
Safety:
UL 508
EMI:
EN 61000-3-2, EN 61000-3-3, EN 61000-6-4, FCC Part 15 Subpart B Class A
EMS:
EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000
-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11,
EN 61000
-6-2
Shock:
IEC 60068-2-27
Freefall:
IEC 60068-2-32
Vib
ration: IEC 60068-2-6
Rail Traffic:
EN 50155, EN 50121-3-2, EN 50121-4
Green Product: RoHS, CRoHS, WEEE
Note: Please check Moxa’s website for the most up
-to-date certification status.
Warranty
Warranty Period:
5 years
Details:
See www.moxa.com/warranty
ioLogik E1510-T
Inputs and Outputs
Digital Inputs:
12 channels (channel-to-channel isolation)
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Counter Frequency:
250 Hz, power off storage
Digital Filtering Time Interval:
Software selectable (minimum: 1 millisecond)
Power Requirements
Power Consumption:
163 mA @ 24 VDC
ioLogik E1512-T
Inputs and Outputs
Digital Inputs:
4 channels (channel-to-channel isolation)
Configurable DIOs:
4 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
ioLogik E1500 Series Introduction to the ioLogik E1500
1-5
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Common Type:
2 points per COM (Configurable DIOs)
Counter Frequency:
250 Hz, power off storage
Digital Filtering Time Interval:
Software selectable (minimum: 1 millisecond)
Power Requirements
Power Consumption:
149 mA @ 24 VDC
Physical Dimensions
Unit = mm
ioLogik E1500 Series Introduction to the ioLogik E1500
1-6
Hardware Reference
Panel Guide
NOTE
The reset button restarts the server and resets all settings to factory defaults. Remove the two screws and the
aluminum plate on top of the aluminum housing, and then press and hold the reset button for 8 seconds. The
factory defaults will be loaded once the Ready LED turns green again. You may then release the reset button.
LED Indicators
Type Color Description
PWR
Green
Off System power is OFF
RDY Green System is ready
Green Blinking Located
Red System Booting-up Error
Green/Red Blinking Safe Mode
Red Blinking Firmware upgrade (LED flashes for 3 seconds and then stays Red
restart)
Off System is not ready
LAN Green 100 Mbps
Amber 10 Mbps
Blinking Data Transmitting
Off Ethernet Off
EXP Green Expansion Mode Ready
Red Configuration Failure
Off
DI Green Channel ON
Off Channel OFF
DIO Green Channel ON
Off Channel OFF
ioLogik E1500 Series Introduction to the ioLogik E1500
1-7
I/O Circuit Diagram
Isolation DI (DI channels)
DI Circuit (DIO channels)
DO Circuit (DIO channels)
2
2. Initial Setup
This chapter describes how to install the ioLogik E1500.
The following topics are covered in this chapter:
Hardware Installation
Connecting the Power
Grounding the ioLogik E1500
Connecting to the Network
I/O Wiring Diagrams
Software Installation
Load Factory Defaults
ioLogik E1500 Series Initial Setup
2-2
Hardware Installation
Connecting the Power
Connect the 12 to 48 VDC power line to the terminal block on the top panel of the ioLogik E1500. If power is
properly supplied, the Power LED will glow a solid amber color.
ATTENTION
Disconnect the power cord before installing or wiring your ioLogik E1500.
Do not exceed the maximum current for the wiring
Determine the maximum possible current for each power wire and common wire. Observe all electrical
codes dictating the maximum current allowable for each wire size. If the current exceeds the maximum
rating, the wiring could overheat, causing serious damage to your equipment. For safety reasons, we
recommend an average cable size of 22 AWG. However, depending on the current load,
you may want to
adjust your cable size (the maximum wire size for power connectors is 2 mm).
Grounding the ioLogik E1500
The ioLogik E1500 is equipped with a grounding point on the terminal block located on the top panel. Connect
the ground pin ( ) if earth ground is available.
Connecting to the Network
The ioLogik E1500 uses an M12-to-RJ45 Cat 5e UTP Ethernet cable for connecting to either the host PC or
another ioLogik device. The M12 connector ensures a tight, robust connection, and guarantees reliable
operations even for applications that are subject to high vibration and shock.
For initial setup of the ioLogik E1500, it is recommended that the ioLogik E1500 be configured using a direct
connection to a host computer rather than remotely over the network.
Configure the host PC’s IP address to 192.168.127.xxx (where xxx ranges from 001 to 253). When using
Windows, you will need to do the configuration from the Control Panel.
ioLogik E1500 Default IP Address Default Netmask Default Gateway
192.168.127.254 255.255.255.0 None
Use the web console or ioSearch configuration utility to connect to the ioLogik E1500. Once the ioLogik E1500
has been detected, modify the settings as needed for your network environment, and then restart the server.
Refer to Chapters 3 and 4 or further details.
ioLogik E1500 Series Initial Setup
2-3
I/O Wiring Diagrams
DI dry contact mode
DI wet contact mode (Ch-Ch isolation)
NOTE
P
ure DI is differential structure.
ioLogik E1500 Series Initial Setup
2-4
DI wet contact PNP/NPN mode (No CH-CH isolation)
DIO_DI wet contact mode (no CH-CH isolation)
NOTE
DIO is signal end structure
.
ioLogik E1500 Series Initial Setup
2-5
DIO_DO sink mode
Software Installation
ioSearch is a search utility that helps the user locate ioLogik E1500 devices on the local network. Find the
ioSearch utility in the Documentation and Software CD under Software ioSearch, or download the latest
version from Moxa’s website.
1. Installing from the CD: Insert the Documentation and Software CD into the host computer. In the root
directory of the CD, locate and run SETUP.EXE. The installation program will guide you through the
installation process and install the ioSearch utility. You can also install the MXIO DLL library separately.
2. Open ioSearch: After installation is finished, run ioSearch from Start Program Files MOXA IO
Server Utility ioSearch.
3. Search the network for the server: From the menu bar, select System Auto Scan Active Ethernet I/O
Server. A dialog window will pop up. Click Start Search to begin searching for the ioLogik E1500.
If multiple ioLogik E1500 units are installed on the same network, remember that each unit has the same
default IP address. You will need to assign a different IP address to each unit to avoid IP conflicts.
Load Factory Defaults
There are three ways to restore the ioLogik E1500 to the factory default.
1. Hold the RESET button for 5 seconds.
2. Right click the specified ioLogik in the ioSearch utility and select Reset to Default.
3. Select Load Factory Default from the web console.
3
3. Using the Web Console
The ioLogik E1500’s main configuration and management utility is the built-in web console, which can be used
to configure a wide range of options.
The following topics are covered in this chapter:
Introduction to the Web Console
Overview
Network Settings
General Settings
Ethernet Configuration
User-defined Modbus Addressing
Default Address
Active OPC Server Settings
Tag Generation
I/O Settings
DI Channels
DO Channels
System Management
IP Accessibility
Network Connection
Firmware Update
Import System Configuration Settings
Export System Configuration Settings
Change Password
Load Factory Defaults
Save/Restart
ioLogik E1500 Series Using the Web Console
3-2
Introduction to the Web Console
The ioLogik E1500 web console is a browser-based configuration utility. When the ioLogik E1500 is connected
to your network, you may enter the server’s IP address in your web browser to access the web console.
The left navigation panel has an expandable menu tree for navigating to the various settings and categories.
When you click on a menu item in the navigation panel, the main window will display the corresponding options
for that item. Configuration changes can then be made in the main window. For example, if you click on
Network Settings in the navigation panel, the main window will show a page of basic settings that you can
configure.
You must click on the Submit button after making configuration changes. The Submit button will be located
at the bottom of every page that has configurable settings. If you navigate to another page without clicking the
Submit button, your changes will not be retained.
Submitted changes will not take effect until they are saved and the ioLogik E1500 is restarted! You
may save and restart the server in one step by clicking on the Save/Restart button after you submit a change.
If you need to make several changes before restarting, you may save your changes without restarting by
selecting Save/Restart in the navigation panel. If you restart the ioLogik E1500 without saving your
configuration, the ioLogik E1500 will discard all submitted changes.
ioLogik E1500 Series Using the Web Console
3-3
Overview
The Overview page contains basic information about the ioLogik E1500, including the model name, serial
number, firmware version, MAC address, and current IP address. Most importantly, you can see the current I/O
status by hitting the F5 key on the computer keyboard to refresh the page.
Network Settings
General Settings
On the General Settings page, you can assign a server name and location to assist you in differentiating
between different ioLogik E1500 units. You may also configure the Server Socket Idle Connection Timeout
Interval or enable the Communication Watchdog function.
The Server Socket Idle Timeout is designed to avoid TCP connection failure. If the network host is unable to
respond due to hardware failure or a network problem, the ioLogik will continue to wait for a response from the
host. This will cause the TCP port to be occupied indefinitely by the host. On the other hand if Modbus/TCP
Server Socket Idle Timeout interval is enabled, When the ioLogik's connection to the server exceeds a specified
time period the device will automatically release its modbus/TCP connection to the server, to free up the port
for the next connection.
ioLogik E1500 Series Using the Web Console
3-4
The Communication Watchdog activates Safe Mode after a specified amount of time has passed following a loss
of network connectivity. Safe Mode is designed especially for products that have output channels to output a
suitable value or status when the ioLogik E1500 cannot be controlled by a remote PC (due to network failure,
for example). By default, the Watchdog is disabled. Users can configure how each output channel responds on
the I/O Settings page.
To enable the Watchdog, check Enable connection watchdog, set the timeout value, and then restart the
server. With Watchdog enabled, the ioLogik E1500 will enter Safe Mode after there is a disruption in
communication that exceeds the specified time limit.
For easier location of devices when troubleshooting, enable the remote control of LEDs on the E1500 series
devices by selecting Enable I/O Locate to allow remote toggling of the Ready LED from off to flashing.
Ethernet Configuration
On the Ethernet Configuration page, you can set up a static or dynamic IP address for the ioLogik E1500, and
configure the subnet mask and gateway address.
User-defined Modbus Addressing
The input and output addresses can be configured in a different format on a specific settings page. Check the
Enable User-defined Modbus Addressing box, select the Modbus function, and then configure the start
address of each item.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61