APPLICATION NOTE
# 0009
August 08, 2008
Part No. 4809-0009 Rev 8-08 Software Bulletin V0.11 EV-S-3 & S-3 Expansion
Evolution S-3 & S-3 Expansion
Secondary Sensing System
Software Bulletin
Revision V0.11
Hired Hand Manufacturing, Inc.
1733 County Road 68
PO Box 99
Bremen, Alabama 35033
Part No. 4809-0009 Rev 8-08 Software Bulletin V0.11 Table of Contents
Table of Contents
Section Title Page
Evolution S-3 and S-3 Expansion Software Enhancements ...................................................................................3
V0.11 Software Revision........................................................................................................................................3
1. History Mode.................................................................................................................................................3
2. Synchronize Systems.....................................................................................................................................4
3. Software Bugs Repaired................................................................................................................................4
4. P3 - Back-Up Timer Percentage....................................................................................................................5
Part No. 4809-0009 Rev 8-08 Evolution S-3 & S-3 Expansion Page 3 of 6
Software Bulletin V0.11
Evolution S-3 and S-3 Expansion Software Enhancements
V0.11 Software Revision
1. History Mode
A new feature was added to allow automatic resetting of the on-board history. In this
revision, the history will also reset any time the Synchronize button is pressed.
The History Mode displays the High and Low Temperatures for each specific zone, any
Back-Up stages which have turned ON, as well as any alarm conditions which have
occurred since the last reset.
The History Reset function is displayed after pressing the Mode Button once after the
Low Temp is displayed. The Zone 1 display will indicate “HIS” and the Zone 2 display
will indicate “no” initially. Press the “+” button for selecting YES, then press the Mode
button to confirm the History Reset to reset all control history. A new feature added in
version V0.10 and later software allows automatic resetting of the on-board history
anytime the Synchronize button is pressed.
Status for Specific Zones
(High or Low Temperature Mode)
Temperatures for
Specific Zones
High Temp Low Temp Reset
Press
Display History Selection Sequence
Press
Part No. 4809-0009 Rev 8-08 Evolution S-3 & S-3 Expansion Page 4 of 6
Software Bulletin V0.11
2. Synchronize Systems
The Synchronize Systems feature is used with the EV-3000 or EV-3001 controller to
update the S3 target temperatures to the match the controller target temperatures and also
automatically reset the on-board history. The on-board history automatic reset is a new
feature added in version V0.10 and later software. If the S3 and the EV-3000 or EV-3001
temperature targets do not reflect the same information, the Synchronize Systems LED
will flash. Press the Select button to automatically Synchronize the target temperatures
and reset the on-board history. When the Synchronize Systems Select button is pressed,
the target temperatures of the S3 will be changed to match the Evolution 3000/3001
controller target temperatures. It will also be displayed in the Back-Up display for
verification.
3. Software Bugs Repaired
Several noise related issues have been reported especially in the S3/EV-16 Combo. Since
the combo is exposed to more switching noise it makes sense to assume that it would
display more noise related issues. Some of the reported problems have been settings such
as high and/or low limits changing automatically, unusual history recordings such as
abnormally high temperature history, and the displays blanking for long periods of time.
Issues were discovered in the routines that handle the interface. More specifically, it had
to do with the way that it handles the temperature sensor and back-up display buttons. It
was discovered that this setting was not checked to determine if it was above its
maximum. If for some reason, it was allowed to be greater than the maximum, it will
cause the issues described above. This was corrected in this revision.
In addition to this, changes were made to insure that the displays were always displaying
data by reloading the settings every two seconds. This way if noise does affect the
operation, the controller will correct itself within two seconds. Also, if the controller
ever locks up, the Watchdog timer will completely reset the display functions insuring
that it does not continue to be locked up.
Synchronize Systems
Select Buttons
Synchronize
Systems
LED Displays
Part No. 4809-0009 Rev 8-08 Evolution S-3 & S-3 Expansion Page 5 of 6
Software Bulletin V0.11
4. P3 - Back-Up Timer Percentage
This determines the percentage that COOL 1 will be run in an Emergency condition for
minimum ventilation. (10% to 100%). The timer is a five minute timer.
A new timer percentage curve feature (added in version V0.09 and later software)
automatically changes the timer percentage based on the Target Temperature.
The data and table below shows an example:
The table and graph above is representative of the curve. The curve actually has multiple
points as the Target Temperature changes in between these points. The Emergency
Back-Up Timer Percentage is not user selectable although you can view the current timer
percentage by going to Program Mode and displaying P3. As you can see by the table,
once the Target Temperature gets to 70 F (21.1 C) or less, the timer fan will run 100% of
the time. In other words, Cool 1 will always run in the event that the main controller is
lost or has a problem operating its timer fans. Timer percentages in between 70 – 100%
are not implemented because frequent on-off transitions are very hard on single phase AC
motors.
Part No. 4809-0009 Rev 8-08 Evolution S-3 & S-3 Expansion Page 6 of 6
Software Bulletin V0.11