HZXB-160KV

Huazheng HZXB-160KV User manual

  • Hello! I am an AI chatbot trained to assist you with the Huazheng HZXB-160KV User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
HZXB-160KV/160KVA
HV series resonance test device
Huazheng Electric Manufacturing(Baoding) Co.,Ltd
USER MANUAL
For Thanks:
Dear customers, Thank you for using the Wuhan Friends Electric Co., Ltd. series
resonant test device, we will uphold innovation, unity, efficiency, the integrity of purpose
and dedication for you!
Company Profile
Our company is a set of development, development, production, operation of
electrical testing equipment in one of the professional electrical company. Our main
business is produce Series resonant test deviceAdjust the inductance series resonant
test deviceNo partial discharge induction voltage test equipmentFully automatic
intelligent CVT resonant boosterElectronic multi-frequency and air-core reactor and other
test equipment. Company location in Guan Nan Yuan 4 Road No.2 East Lake New
Technology Development Zone Wuhan. We have 15 years high voltage power test
equipment series resonant test device of professional experience in production, Site
power engineering commissioning test services and testing equipment rental services and
other sets of business. High pressure test equipment production workshop covers an area
more than 2500 m2. Vacuum drying oven, vacuum pouring cans, vacuum incubators, high
/ low pressure winding machine, such as a large number of professional manufacturing
machinery and equipment. And also have a professional technology Research and
development teamClean and hygienic winding group, Large scale assembly groupStrict
and meticulous quality inspection groupDedicated dedication of the after-sales service
and other professional team.These excellent team is the company's production of product
quality and quantity, rapid response to delivery, after-sale Thanksgiving service a strong
guarantee.
The company's contribution to the power industry.
Since 2008We keep not less than 25% growth rate for the each year, Among them
Series resonant test deviceAdjust the inductance series resonant test deviceNo PD test
equipmentFully automatic intelligent CVT resonant boosterElectronic multi-frequency
and air-core reactor and other test equipmentProduce 400set./year, Market share of
more than 3,000 sets. Is the largest domestic production capacity and sales of
pressure-resistant power equipment manufacturers, Products sold to the twenty-six
provinces, municipalities, autonomous regions and municipalities, exports to Southeast
Asia, the Middle East, Africa and other countries and regions, has served more than 5,000
user units, and domestic and foreign customers recognized and acclaimed
Dear customer
Thank you for purchasing the company's Frequency conversion series resonant test
device. Before you use this product for the first time, please read this instruction manual in
detail.It will probably help you skillfully use this instrument.
Our aim is to continue to improve and perfect the company's products. So you may
have a little difference with the use of the product if there is any change
Warning
Due to the input and output terminals, test column, etc. are likely to take the
voltageWhen you plug in the test line, power outlet, will produce electric
spark. Carefully electric shock, avoid electric shock hazard, pay attention to
personal safety
Careful guarantee
The company's products, in three months from the date of delivery, such as product
defects, we can change for you.Defects such as products within a year, the
implementation of free maintenance. One year or more defects,the implementation of paid
lifelong maintenance.
Safety requirements
Please read the following safety precautions to avoid personal injury
Only qualified technical personnel to perform maintenance
—To prevent fire or personal injury
Use appropriate power linesCan only use the product specific, and in line with the
product specifications of the power supply line
Correctly connect and disconnectWhen the test lead and the live wire are connected,
please do not connect or disconnect the test lead.
Product groundingIn addition to the products through the power line grounding
conductor earthing, shell grounding column must be grounded. In order to prevent electric
shock, grounding conductors must be connected to the ground. In connection with the
input or output terminals of this product, the product is properly grounded.
Note the ratings of all terminalsIn order to prevent fire or electric shock hazard, please
note all the ratings of this product and mark. Before connecting to this product, please
read the instruction manual for further information about the value of the rated value.
Do not operate in the absence of instrument coverIf the cover plate or the panel has
been removed, do not operate this product.
Do not operate when there is a faultIf you find that the product is damaged, please
check the company's maintenance personnel, do not continue to operate.
Do not operate in wet conditions
Content
One Product overview.................................................................................1
Two HZXB-160KV/160KVA HV series resonance test device..................2
Three HZXB-160KV/160KVAEquipment application.....................................................5
Four VF power supply detailed introduction................................................6
Five Common trouble shooting.................................................................17
Six Related data......................................................................................19
1
OneProduct overview
This device principal for 220KV/25000KVA Main transformer neutral point AC
voltage withstand test. The reactor is designed to meet the requirements of low voltage
AC voltage test, such as high voltage and low voltage, and it can meet the requirement of
low voltage AC voltage test with 10kV cable.
The device is composed of a frequency conversion control power supply, an excitation
transformer, a reactor, a capacitor voltage divider, and a compensating capacitor.
1.1 Application of series resonance in power system
1.1.1The required power capacity is greatly reduced. Series resonant power supply is
the use of the resonant reactor and the capacitor voltage to generate high voltage
and high current. In the whole system, the power supply is only required to provide
active power consumption of the system, therefore, the power required to test the
power is only 1/Q.
1.1.2The weight and volume of the device is greatly reduced. The series resonant power
supply, not only saves large power heavy pressure adjusting device and ordinary
power frequency test transformer and resonant excitation power supply only needs to
test the capacity of 1/Q, which makes the system weight and volume greatly reduced,
generally for ordinary test device 1/10.
1.1.3Improve the output voltage waveform. Resonant power supply is a resonant filter
circuit, can improve the output voltage waveform distortion, get a good sinusoidal
waveform, effectively preventing the harmonic peak of the test sample of the false
breakdown.
1.1.4Prevention of large short-circuit current burn. In series resonant state, when the
insulation of the test sample is breakdown, the circuit is immediately removed, and
the loop current is rapidly decreased to the normal test current 1/Q. And parallel
resonance or test transformer mode to do the test, the breakdown of the current rise
in a few times, the difference between the short circuit current and the breakdown
current of several hundred times. Therefore, the series resonance can effectively find
the insulation weakness, and there is no big fault point of the fault of the short circuit.
2
1.1.5Will not appear any recovery over voltage. When the product is broken down, the
high
voltage is lost immediately, the arc is extinguished immediately, and the recovery
voltage is very long, and it is easy to break off the power supply.
1.2 The main functions and technical characteristics of the
FM resonance device of our company
The device has the protection function such as over voltage, over current, zero
position start, and the system is out of order. The protection value can be adjusted
according to user's need, and the flashover voltage of the test sample can be recorded.
1.2.1The whole unit weight is light, easy to use in the field..
1.2.2The device has three working modes, which is convenient for the user to choose
according to the situation of the scene, and to improve the test speed.
Work mode is: automatic mode, manual mode, automatic tuning manual boost mode.
1.2.3Can store and remote print data, the data is stored in the digital, convenient to help
users identify and find.
1.2.4Device automatically sweep frequency when the starting point can be set in the
specified range, sweep direction can be up and down, while the LCD screen display
scan curve, easy to understand whether users can find the resonance point.
1.2.5Using the DSP platform technology, it can be convenient for the user to increase or
decrease the function and upgrade, but also makes the man-machine exchange
interface more humane.
Two HZXB-160KV/160KVA HV series resonance test device
2.1 HZXB-the manufacturer code
160-the maximum rated capacity of the equipment to be able to output, the unit is
kVA
/160-the voltage level of the device to be able to output, the unit is kV
2.2 HZXB-160KV/160KVA HV series resonance test device
Technical Parameters
3
2.2.1.额定电压:
160kV—Suffice AC withstand voltage test of 220KV/25000KVA Main transformer
neutral point AC voltage withstand test; working frequency: 45-65Hz, the test
voltage is not more than 160kV, the test time 1min
2.2.2Output voltage waveform distortion rate<1.0
2.2.3Allow continuous working time: 60 minutes under the rated conditions
2.2.4Device itself quality factorQ>30
2.2.5GIS, switch, etc. the full load factorQ>20Load related
2.2.6Input power: three-phase 380V or single phase 220V
2.2.7Frequency regulation range30Hz300Hz
2.2.8System measuring accuracy1.5
2.2.9The device has the protection function of over voltage, over current and zero
position.
2.3 Equipment to follow the standard
Electrical equipment installation engineering electrical equipment handover test
standardGB50150-2006
High voltage resonant test deviceDL/T 849.6—2004
reactorGB10229.88
Electrical equipment preventive testing procedures
DL/T596-1996
Coupling capacitor and capacitor voltage divider
IEC358(1990)
2.4 Equipment configuration and technical parameters
2.4.1.VF power supply 1set):
Rated Capacity10kW
Input voltage: 380V or single phase 220V±5% 50Hz
Output voltage: 0 ~ 400V adjustable
Output voltage frequency: 30 ~ 300Hz
0.1Hz step can be adjusted
4
Frequency stability is less than or equal to 0.02%
output current025A
2.4.2Reactor4set
rated operational voltage40kV
rated operational current1A
Rated inductance110H
Continuous working time5min
Temperature rise65k
Working frequency30~300Hz
2.4.3Excitation transformer1set
Rated Capacity10kVA
Input voltage400V
Output voltage10kV
output current1A
2.4.4Capacitor voltage divider1set ):
Capacitance1000pF
Rated voltage160kV
Working frequency30300Hz
uncertainty1.5%
2.4.5Compensating capacitor1set
Capacitance5000pF
Rated voltage160kV
Working frequency30300Hz
2.4.6Test line and accessories 1 bag
5
ThreeHZXB-160KV/160KVA HV series resonance test
device
3.1 Maintransformer
3.2 Wiring diagram
Test product test configuration table
configuration
REACTOR
EXCITATION
6
FourVF power supply detailed introduction
4.1 Basic equipment
4.1.1.power
Connect the three 380V of the to the "input" of the FM power supply..
4.1.2.Operation panel description:
Pic 1
Power switch: be responsible for power supply of inverter power supply.
High voltage indicator: variable frequency power supply starting
instruction.
reset: load mismatch, frequency source of overheating and other
Test product
40kVA/40kV 4 SET
VOLTAGE
220KV/25000kVA Main transformer neutral
point
Use 4 electric reactors in series and
Compensating capacitor
10kV
7
protection actions after fault reset..
Signal - divider divider for access: low voltage arm, maximum voltage
100V, the input impedance of 10M.
Grounding: for system safety grounding.
Mouse interface: access to the U disk query information or access to the
mouse to replace the touch operation.
Liquid crystal display: the display of the system parameters, the wave, the
menu and so on..
L input: access to power three-phase or single-phase 220V 380V + 5% +
5% ~ 45 65Hz, when the power supply is 380V, A, B, C three, can be rated
load test; when the power supply is 220V, A, C phase, 1/2 can only load
test
Output: variable frequency power supply output to the excitation
transformer input.
4.1.3.connect power
Variable frequency power supply in the electric control box after "power switch", lit
LCD display.
Note: the fan at the two sides of the instrument is operating in the operation,
which means that the internal power components of the instrument are normal.
Otherwise, there is no reduction in the internal heat of the instrument or the last
test. At this point should be cut off the power, the instrument will be placed in a
ventilated place for 1 hours or so, until the internal temperature is appropriate to
lower the starting power.
When fans often do not start, the proposal immediately contact the manufacturer.
Please do not disassemble the instrument when the equipment is not recoverable..
4.2 Touch screen
Frequency conversion power supply control screen for the full touch screen, you only
need to operate on the screen, click on the location, that can be operated.
4.2.1. After starting, the display interface is shown in Figure 2.
8
Pic 2
4.2.2.Test parameters configuration: all kinds of test before each test.
Parameters! After clicking on the parameter configuration, the display interface is shown
in Figure 3..
Pic 3
● The starting frequency of the automatic tuning is the highest frequency of 20Hz,
the upper limit frequency is 200Hz.
● The termination frequency: select the automatic tuning of the end frequency,
lower frequency up to 100Hz, the upper limit frequency of the lowest is 300Hz.
9
1 set "the starting frequency" is not higher than the "stop frequency".
2 when the first test is recommended to use 300Hz ~ 30Hz scan.
3 when the frequency range is known, it can be selected to reduce the test
time in the appropriate frequency section.
L: set the initial voltage tunable input voltage at the beginning of this
value.
1 for the low Q value of the test products such as generator, motor, aerial bus,
at the beginning of this value is set to 50 ~ 70V;
2 for the Q value of the higher test products such as power cables,
transformers, GIS, etc., at the beginning of this value is set to 30 ~ 50V.
The first phase of the test voltage: the first phase of the test voltage setting
value.
Test time - the first stage: the first stage pressure time setting of the test
voltage.
Second - stage test voltage: second stage set the test value of voltage.
The second stage: pressure test time - time setting second phase voltage
test.
Third - stage test voltage: third stage set the test value of voltage.
Third stage test time: set the third stage test voltage of the voltage.
Our voltage tracking system has the function of automatic calibration of large
voltage fluctuations, but the fluctuation range of the grid voltage is small, and the
fluctuation of the voltage is also in the range of the instrument. Therefore, we
strongly recommend that you set up the test voltage at the test voltage.
If there is no phase pressure test, it is only required to set up a stage test
voltage and the corresponding test time, and other test voltage and test time is set to
0.
For the partial pressure ratio L: divider ratio is 2000:1, the divider ratio is set
to 2000; (General Factory has been set up)
The overvoltage protection: limit setting test voltage value, the voltage
exceeds automatic termination test, the test voltage is 10% higher than the
10
general.
The overcurrent protection: the highest value is set low output current.
Without knowing the actual test current, it is generally set to the rated current
of the device.
L: set the breakdown voltage of flashover protection error value, and when the
liquid crystal display must be restarted after flashover
ENT: confirm key.
1 ~ 0: digital key: select the desired set value.
ESC: return key.
Automatic test: when the "parameter configuration" is set up, click the "auto
test", enter the "automatic test" interface, display interface as shown in Figure 4
Pic 4
Click "start test", the system will automatically find the resonance point, the
right corner of the tip is tuned, if there is abnormal situation, please click on the
"down"; blue on behalf of the voltage curve, the display interface as shown in
Figure 5
11
Pic 5
To find the resonance point, the system automatically boost, the right corner of
the tip, "is being boosted, such as abnormal conditions, please click" stop "; the
display interface as shown in Figure 6.
Pic 6
When the U resonant voltage rise to the test of the pressure value, the system
automatically when the pressure, the right corner of the tip is time, if there is
abnormal situation, please click on the "buck stop"; the display interface as shown
in Figure 7
12
Pic 7
When the time to set up the pressure time, the system automatically pressure,
the right corner of the tip is the pressure, if there is abnormal situation, please click
on the "down"; the display interface, as shown in Figure 8.
Pic 8
13
When the U resonance voltage is 0, the right bottom corner is indicated by the
"test", and the display interface is shown in Figure 9..
Pic 9
Manual test: when the "test parameters" is set up, click the "manual test"
and enter the "manual test" interface, the display interface is shown in
Figure 10..
Pic 10
14
Click start test, if you want to find the resonance point, click the "tune", the
system automatically find the resonance point, the blue line represents the
voltage curve, showing the interface as shown in Figure 11.
Pic 11
If you do not want to automatically find the resonance point, first click on the
"50V", the "U" rose to a, and then click on the "frequency" to find the resonance
point, to find the resonance point, click on the "rising voltage", showing the
interface as shown in Figure 12.
Pic 12
15
When the U resonance voltage rises to the setting time of the pressure value,
click on the "breakdown time", the system starts to time. Display interface as
shown in Figure 13.
Pic 13
When the "pressure time", click "stop", the system automatically, the display
interface as shown in Figure 14.
Pic 14
When the U resonant voltage buck 0, the test is completed, such as the test
record, please click on the buck before saving the data, the buck click "file
management"; the display interface as shown in Figure 15.
/