ICM Controls ICM316C Installation guide

Type
Installation guide
ICM
316
DEFROST TIMER
LII276-1
www.icmcontrols.com
800-365-5525
ICM CONTROLS
7313 William Barry Blvd.
North Syracuse, NY 13212
Input
Voltage: 18-30 VAC
Frequency: 50-60 Hz
Power Consumption: 1 watt maximum
Output
O, X2:
– Type: Relay
– Form: DPST, normally open
– Rating: 1 amp @ 30 VAC
ODF:
– Type: Relay
– Form: SPDT, normally open
– Rating: 2 HP @ 230 VAC
Time Delays
Defrost: Fixed at 10 minutes (+/- 5%)
Interval Between Defrost:
– Pin selectable (50/70/90 minutes)
Test Time: Short across test terminals
reduces test time by 256x
Mechanical
Dimensions: 3” x 6”
Mounting:
Surface mount using (5) #6 or #8
screws, or plastic stand offs
WIRING DIAGRAM
SPECIFICATIONS
Lowcosttimeandtemperaturedefrostcontrol
Indoor
T’Stat
24
VAC
Outdoor
Fan
Compressor
RVS
HPS LPS
Aux
COM NC
Outdoor
T’Stat
Evaporator
Defrost Relay EDR
O
X2
Y
B
B
R
R
T
D
O