ABB ODPSE230C Installation and Operating Instructions

Type
Installation and Operating Instructions
ODPS
A07078
34ODPS A/ 1SCC390112M0201
Dual Power Source, ODPSE230C
Installation and operating instructions
Introduction
ODPSE230C is used to provide power supply for motorized switches and breakers by using two lines, Line I and Line II.
Features
• Protects the motor operator against over and undervoltage
• No need for external supply voltage
• Isolation provided between line I and II
Status indication
AgreenLEDlightforLineIandLineIIindicatesthatvoltageisbetweenspeciedrange.IncaseofanomalyLEDsare
switchedOFF.Speciedvoltagerangeis80%-120%xratedACvoltage.
LINE I LINE II Output LEDs
OK NOT OK LINE I LINE I
NOT OK OK LINE II LINE II
NOT OK NOT OK None None
OK OK LINE I LINE I + II
Picture 1 Front panel Table 1 Status indication of ODPS
Installation
Picture 2 Drilling hole distances/Screw mounting
1
2
ODPS
3
35Êmm
ENÊ50022
ODPS
A07080
ODPS
Remove
A07081
Picture3DIN-railmountingofODPS
LN1
LN2
ODPS
Technical data
Voltage and current limits
Rated AC voltage 220…240V+/-20%,50/60Hz+/-10%
Output current Max 4 A
Operating time 2 s
Main circuit connections
X11:1 Line I Phase
X11:2 Line I Neutral
X13:1 Line II Phase
X13:2 Line II Neutral
X12:1 Motor operator Phase
X12:2 Motor operator Neutral
Connection cables
Supply side cables of the main circuit 0,2...2,5mm
2
Load side cables of the main circuit 0,2...2,5mm
2
External transformer
When ODPS230 is used in network where N is not connected an external transformer must be used to drop voltage
level. Transformer has to be Main to Phase transformer and isolative. Effective value depends on the size of the mo-
tor operator. See Connection diagram.
Dielectric properties
Overvoltage category III
IEC60947-1Ratedimpulsewithstandvoltage(Uimp),basic
insulation
4,0 kV
IEC60947-1Dielectrictest 1,89kV,50Hz,5s
IEC60092-504Insulationresistancemeasurement > 100 M,500VDC
Mechanical characteristics
Material of Enclosure Self-extinguishingthermoplastic,UL94V-0
Degree of protection IP 20
Dimensions
Height 90 mm
Width 32 mm
Depth 130 mm
Environmental conditions
Ambient air temperature -25…+60°C
Altitude of the site of installation < 2000 m
IEC60068-2-30Humidity,relative <93%,T=-25...+60°C
IEC60947-1Pollutiondegree 3
Mechanical tests
IEC60068-2-6Vibrationtest
5Hzto13,2Hz:+/-1mm
13,2Hzto100Hz:+/-0,7g
Qdoesnotexceed5
Duration90minat30Hzorateachresonancefre-
quency
IEC60068-2-27Shocktest
Acceleration 100 m/s
2
peak(10g
n
)and150m/s
2
peak
(15g
n
).Pulseduration:11ms
Transport and storage
Ambient air temperature
-40…+70°C
EMC characteristics
IEC61000-4-2Electrostaticdischargeimmunitytest
8kV(Level3)Airdischarge
4kV(Level2)Contactdischarge
IEC61000-4-3Radiated,radio-frequency,electromagnetic
eldimmunitytest
Level 3
IEC61000-4-4Electricalfasttransient/burstimmunitytest
Level 3
IEC61000-4-5Surgeimmunitytest
2kV Phase to Neutral
IEC61000-4-6Immunitytoconducteddisturbances,induced
byradio-frequencyelds
Level 3
IEC61000-4-8Powerfrequencymagneticeldimmuntiytest
Level 4
CISPR 11 Electromagnetic disturbance characteristics
(Emission)
Group 1 Class B
Table 2 Technical data
Picture 4 Connectors
Dimensions Connection diagram
Picture5Dimensionsofthedevice Picture6Connectiondiagram
ABB Oy
Low Voltage Switches
P.OBox622
FI-65101VAASA,Finland
Telephone+358102211 Thetechnicaldataanddimensionsarevalid
Telefax+358102245708  atthetimeofprinting.Wereservetherightto
www.abb.com subsequent alterations.