IMI PNEUMATEX Simply Vento V 2.1 S Installation guide

Type
Installation guide

IMI PNEUMATEX Simply Vento V 2.1 S is a compact, space-saving differential pressure controller specifically designed to maintain precise pressure conditions in heating, solar and cooling systems. It features a durable EPP insulation, a range of accessories for flexible installation, a modern intuitive color display, and an integrated data logger for detailed system analysis. Its robust design and simple operation make it an excellent choice for various applications, including maintaining differential pressure, system filling, venting, and make-up water management.

IMI PNEUMATEX Simply Vento V 2.1 S is a compact, space-saving differential pressure controller specifically designed to maintain precise pressure conditions in heating, solar and cooling systems. It features a durable EPP insulation, a range of accessories for flexible installation, a modern intuitive color display, and an integrated data logger for detailed system analysis. Its robust design and simple operation make it an excellent choice for various applications, including maintaining differential pressure, system filling, venting, and make-up water management.

SAFETY – INSPECTION – DISASSEMBLING – DISPOSAL prescriptions
Compresso
Transfero
Vento
Pleno
Rell
SAFETY – INSPECTION
•••••Personnel
Installing and operating personnel must possess the appropriate knowledge and training.
•••••Follow the instructions
Installation, operation, maintenance and disassembly must be carried out as stated and showed in the dierent instruction
manuals making integral part of the delivery and in accordance with best practice. In addition to the IMI Hydronic Engineering
instructions, additional instructions from other companies may be included for the components used (e.g. backow preventers)
.
You must follow these instructions in the same way as the IMI Hydronic Engineering instructions.
If anything is unclear, please contact IMI Hydronic Engineering customer service.
•••••Tests for commissioning and periodic inspections
Test required for commissioning and periodic inspections must be performed according to the regulations in the country
where the device is installed and operated. There are no unied international regulations for the acceptance test prior to
commissioning and periodic inspections. It is usually the vessels that determine how the installation is classied.
These are CE type-tested in accordance with guideline PED/2014/68/EU for pressurised equipments. For periodic
inspections, openings are provided for ange-type or endoscope inspections.
In Switzerland, Compresso does not require autorisation from the SVTI if the installation is protected in such a way that
psCH is not exceeded. Vessels with psv x V up to 3000 bar*litres do not require inspection by the SVTI.
Following combinations with TecBox are recommended:
Primary vessel (2) TecBox safety valve (SV)
C 10 C15
1000 litres 3 bar on request
800 litres 3.75 bar on request
700 litres 4.2 bar on request
600 litres 5 bar on request
500 litres 6 bar 6 bar
300 litres 10 bar
For Transfero as many extension vessels as required can be connected to the primary vessel. The CE-approved 2 bar
safety valve protects the vessels from inadmissible pressures. In Switzerland, SVTI inspection is not required for these
types of vessels.
Backow preventer BA: Perform inspection and maintenance in accordance with EN 1717 and the rules in the operator’s
country. Functional testing, with documentation, must normally be carried out annually. Dirt trap (SF): Inspect and clean if
necessary after a drop in the water make-up capacity or before functional testing of the backow preventer BA. We recommend
including the Pleno P / P R / P CR / BA4R in the maintenance cycle of the connected pressure-maintaining or degassing station.
Follow the maintenance instructions for Rell softening modules. The Pleno P / P R / P CR / BA4R can work as an accessory in
systems requiring technical inspections (Compresso | Transfero) and can be included as part of the inspection.
•••••Place of installation
The access to the place of installation must be restricted to trained and specialised personnel. The oor statics must be able
to support the maximum operating and installation conditions. Connections for electricity, communication, main water and
waste water must correspond to the requirements of the device. The room must be thouroughly ventilated. Do not store
ammable, explosive materials near the pressure vessel. Pressurized containers (eg Compresso expansion vessels) must
be protected against external re, at least according to national regulations.
•••••Water quality
IMI Hydronic Engineering devices are designed to maintain pressure, to degass or to make-up and/or treat water in closed
heating, solar and cooling systems with water that contains no aggressive or toxic agents.The entire system must be
dimensioned and operated in such a way as to minimise the amount of oxygen admitted through the make-up water or
through permeable components. Water treatment systems are to be dimensioned, installed and operated according to the
current state of the art.
•••• Electrical connection
The electrical and the communication wiring and connections should be carried out by a qualied electrician, in accordance
with current local regulations. The devices and the potential free outputs must be disconnected from the electrical supply
before working on electrical components.
Protection on the supply to be done by the contractor:
Compresso C2.1, C10.1; C10.2; C15; CX: 10 A
Compresso C15.2: 16 A
Transfero range 4, 6, 8, 10, 14 = 1 x 230 V: T.1: 10 A
T.2: 16 A
Transfero 19, 25 = 3 x 400 V: 10 A
Vento range 2, 4, 6, 8, 10, 14 = 1 x 230V: 10 A
Vento range 19, 25 = 3 x 400 V: 10 A
Pleno PI9.1; PI6.1; PIX: 10 A
Pleno PI9.2; PI6.2: 16 A
Pleno P BA4R: not applicable
Residual current device (RCD) following local regulation.
If installed in residential building we recommend a commercially available line lter to the junction box.
WXMOIN00001
07.2019
en
de
fr
nl
12060000406
09.2021
Simply Vento V 2.1 S
Vento Compact V 2.1 FE
INSTALL
www.imi-hydronic.com
2
1
2
3
12
3
Sout
Sin
2
1
3
4
5
3
≥400
+5°C - +40°C
1x230V
≥400
4
Accessory kit
(~1200)
460
ø
12
60
60
A
ø
8,5
ø
18
460
1
2
415
88
70
(~1435)
(~1108)
804
ø
12
5
ø
12
min. 85
120
60
376
2 1
453
270
95
70
500
520
A
A (1:1)
(~1108)
(~1435)
31
2
4
5
+
Option 30103230021
6
Sout
Sin
3
1
2
Sout
Sin
7
Optional
V2.1 S V2.1 FE
dpu min bar 0,5 0,5
dpu max bar 2,5 2,5
Sin Sout Swm
Ts min °C 0 0 0
Ts max °C 90 90 65
Pleno / Pleno Refill
Swm
WM
Sin1 Sout
Vento V2.1 FE
TecBox
V1
PT
ECO
PT
W
FL
SWME
SoutSin
Sout
Sin
AA B
Pleno Refill
Modul A Refill-IN Modul B Refill-OUT
Pleno P BA4 R =
Modul A + Modul B
Sin1 Sout
Vento V2.1 S
PT
W
FL
TecBox
Sout
Sin
Swm
Sout
Sin
Vento V2.1 S Vento V2.1 FE
8
 tr≤90°C
Vento V2.1 FE
+
Pleno P BA4R
 tr≤90°C
Vento V2.1 S
DNe
V2.1 S V2.1 FE
L max 10 m DNe 25 25
L max 20 m DNe 25 25
L max 30 m DNe 32 32
tR
Q
psvs
Hst
P
ZUT
tmax
DSV...DGH
> 500 mm
Statico SD/SU
min SD 80
DLV
Zeparo Cyclone
DNe
Sin1Sout
pw 2 - 10 bar
tw 5 - 65 °C
SinSout
Swm
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
t
R
Q
psvs
Hs
t
P
ZUT
t
max
DSV...DGH
> 500 mm
Statico SD/SU
min SD 80
DLV
Zeparo Cyclone
Sin1Sout
SinSout
DNe
VN ≥ 80 (SD 80, SU 140, SU 200, …)
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
DNe
9
230V/50 Hz
10A / 3 x 1,0 mm²
5
1 2
LPE
N
LPE
N
34
6
1!
BrainCube
Connect!
#1-5
www.imi-hydronic.com
V.1 = 10A
10
Vento V2.1 S / V2.1 FE
230V/50 Hz
11
Vento V2.1 S / V2.1 FE
24V
12
P
umpe 1 Sicherung F20
0
1
0 AT / T
y
p: 5
20
q
NPN
S
HIEL
D
S
HIEL
D
R
S 485
US
B
RS
458
L
AN
/
E
t
he
rn
e
t
A B
S
A‘ B‘
S
IN OU
T
Jumper (RS485)
o
ff
=
Off
en
/
stationne‘
/
ope
n
on =
G
esteckt
/
branche‘
/
connect
G
ND
IN
G
ND
IN
G
ND
+
I
N
A B
S
A‘ B‘
S
ID6 ID5 IDA3
q
NP
N
S
HIEL
D
S
HIEL
D
RS
485
ID6 ID5 IDA3
US
B
RS458
LAN
/
E
t
he
rn
e
t
A B
S
A‘ B‘
S
IN OU
T
Jumper (RS485)
off = Offen / stationne‘ / o
p
en
on = Gesteckt / branche‘ / connect
GND
IN
GND
IN
G
ND
+
IN
A B
S
A‘ B‘
S
M
1
~
LINE P/C1 V
1
V
3
V
4
WM V2 P
/C
2OD1OD2
O
D3 OD
4
L
N
PE
L
N
PE
L
N
PE
13 14 13 14 13 14
Klemmen Aus
f
ührung
C
V
ersion des bornes
C
T
e
rmin
a
l
e
x
ecu
ti
o
n
C
230
V 5
0
Hz
F2
0
1
S
icherung
/
f
usible
/
f
use
1
0 A
/
250V
/
5x20
Vento
Vento
Compresso
Compresso
Compresso
Connect
Vento
13
www.imi-hydronic.com
We reserve the right to introduce technical alterations without prior notice.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13

IMI PNEUMATEX Simply Vento V 2.1 S Installation guide

Type
Installation guide

IMI PNEUMATEX Simply Vento V 2.1 S is a compact, space-saving differential pressure controller specifically designed to maintain precise pressure conditions in heating, solar and cooling systems. It features a durable EPP insulation, a range of accessories for flexible installation, a modern intuitive color display, and an integrated data logger for detailed system analysis. Its robust design and simple operation make it an excellent choice for various applications, including maintaining differential pressure, system filling, venting, and make-up water management.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI