Siemens RVP200 Installation Instructions Manual

Type
Installation Instructions Manual

This manual is also suitable for

Siemens RVP200 is an easy-to-use heating controller that can be used for various heating applications, such as floor or ceiling heating systems, as well as for domestic hot water preparation. It features a clear and user-friendly interface with a backlit display, making it easy to read and adjust settings even in low-light conditions. With its compact design, the controller can be mounted on a DIN rail, control panel, or directly on a wall, providing flexible installation options.

Siemens RVP200 is an easy-to-use heating controller that can be used for various heating applications, such as floor or ceiling heating systems, as well as for domestic hot water preparation. It features a clear and user-friendly interface with a backlit display, making it easy to read and adjust settings even in low-light conditions. With its compact design, the controller can be mounted on a DIN rail, control panel, or directly on a wall, providing flexible installation options.

8/12 16.04.1999 4 319 2697 0 c Siemens Building Technologies / Landis & Staefa Division
Schémas de raccordement
Pour alimentation basse tension
AC 230 V
B9
B3
B3
1
D1 D2
2462A01
2
S1
2462A02
2462A03
3
B3
F3
T
c Mesure de la température ECS par sonde (uniquement RVP210)
d Contact externe pour commutation du régime
e Mesure de la température ECS par thermostat (uniquement RVP210)
Pour alimentation secteur
2464A04
AC 230 V
1
Q1
M3
Q3/Y3
F1/F4 F2 F3
2
F1/F4
F1 F2
E1
2462A05
3
F1/F4
2462A06
Y3
Q3/Y3
4
F3
2462A07
c Raccordement servomoteur trois points, pompe de circuit de chauffage et (uniquement RVP210) pompe de charge ECS
d Raccordement brûleur (régulation de température de chaudière)
e Raccordement servomoteur électrothermique (régulation de température de départ)
f Raccordement servomoteur pour vanne de dérivation d'eau sanitaire (uniquement RVP210)
A6 Appareil d'ambiance QAW50 ou QAW70
B1 Sonde de température de départ ou de chaudière
B3 Sonde de température ECS (uniquement RVP210)
B9 Sonde extérieure QAC22 ou QAC32
E1 Brûleur
F1 Thermostat de chaudière
F2 Limiteur de température de sécurité
F3 Thermostat d'eau sanitaire (uniquement RVP210)
M1 Pompe de circuit de chauffage
M3 Pompe de charge ECS (uniquement RVP210)
N1 Régulateur RVP2...
S1 Contact externe
Y1 Servomoteur trois points
Y2 Servomoteur électrothermique
Y3 Servomoteur pour vanne de dérivation (uniquement RVP210)
en English
Do not throw these instructions away but keep
them with the controller!
Only the RVP210 provides d.h.w. heating.
Installation
Place of installation
In a dry place, e.g. the boiler room.
Mounting choices:
-
In the control panel, on the inner wall or on a DIN
mounting rail
-
On a panel
-
In the control panel front
-
In the sloping front of a control desk
Permissible ambient temperature: 0…50 °C
Electrical installation
-
Local regulations on electrical installations must
be complied with
-
Cable tension relief must be assured
-
The cables from the controller to the actuator and
the pump carry mains voltage
-
The cables to the detectors should not be run
parallel to mains carrying cable (insulation class II
to EN 60730!)
Specifications of cable
Maximum permissible cable lengths to the detectors
and the room unit:
Copper cable 0.6 mm dia.: 30 m
Copper cable 0.5 mm
2
: 50 m
Copper cable 1.0 mm
2
: 80 m
Copper cable 1.5 mm
2
: 120 m
Siemens Building Technologies / Landis & Staefa Division 4 319 2697 0 c 16.04.1999 9/12
Installing and wiring the base
Wall mounting
1. Separate base from the controller.
2. Hold base against the wall. Marking "TOP" must
be at the top!
3. Mark fixing holes on the wall.
4. Drill holes.
5. If required, knock out holes on the base for fitting
cable entry glands.
6. Secure base.
7. Wire up base.
Rail mounting
1. Fit rail.
2. Separate base from the controller.
3. If required, knock out holes on the base for fitting
cable entry glands.
4. Fit base to the rail. Marking "TOP" must be at
the top!
5. If required, secure the base (depending on type
of rail used).
6. Wire up base.
Flush panel mounting
Maximum thickness: 3 mm
Panel cutout required:
138 x 92 mm (+1 mm / –0 mm)
1. Separate base from the controller.
2. If required, knock out holes on the base for fitting
cable entry glands.
3. Insert base in the panel cutout from behind until
stop is reached. Marking "TOP" must be at the
top!
4. Push lateral tongues behind the front panel (see
illustration).
5. Wire up base. Make sure the cable lengths will
be adequate so that the control panel door can
be opened.
2462Z06
Wrong Correct
Place tongues correctly on the left and on the right. They must
not be inside the cutout!
Fitting the controller to the base
1. Make sure that position and orientation of the
turning levers are correct, using the fixing screws
(illustration below shows the lateral wall of the
controller casing).
2522Z13
2. Insert controller in the base until stop is reached.
Marking "TOP" must be at the top!
3. Tighten fixing screws gradually.
Fitting the time switch
If a time switch is to be fitted (weekly or digital time
switch), the respective opening in the cover must be
cut out with a knife.
Readjusting the clock after a power failure
When power returns after a power failure, the clock
will be readjusted. Automatic readjustment can be
aborted by briefly setting the operating mode se-
lector to manual operation
and then back to the
required operating mode, allowing manual adjust-
ment of the clock.
Commissioning
Plant-specific settings
Setting elements: please refer to illustration on page
10.
The coding switches and setting potentiometers for
the plant-specific settings are accessible after re-
moval of the time switch.
-
Removing the time switch: pull dial away from the
controller.
-
Fitting the time switch: insert time switch and push
it down (audible click).
Checking the motorized valve
Check the seat or slipper valve: see if
-
it is correctly installed (observe direction of flow
indicated on the valve body)
-
the slipper moves in the correct angular range
(note position indicator)
-
the manual level is disengaged
Exercise caution with underfloor and ceil-
ing heating systems!
The limit thermostat must be correctly set. During
the functional check, the flow temperature may not
exceed the maximum permissible level (usually
55 °C). If it does, proceed immediately as follows:
-
Either close the seat or slipper valve manually, or
-
Switch off the pump, or
-
Close the pump isolating valve
10/12 16.04.1999 4 319 2697 0 c Siemens Building Technologies / Landis & Staefa Division
Setting elements
Override
2462Z03
1
2
3
4
5
6
7
8
910
11
12
1 Opening for time switch
2 LED for "Override"
3 Operating mode selector
4 Setting knob for heating curve
5 Setting knob for setback
6 Setting knob for d.h.w. temperature (only RVP210)
7 Setting knob for normal room temperature
8 Coding switches
9 Setting potentiometer for authority of room tem-
perature and quick setback active / inactive
10 Setting potentiometer for max. limitation of flow or
boiler temperature
11 Setting potentiometer for ECO heating limit
12 Setting potentiometer for switching differential
Coding switches
Function Switch position on the left Symbol Symbol Switch position on the right
Type of regulating unit Control of a motorized valve Control of a atmospheric or
forced draught burner
Type of control Three-position (modulating)
3Pt. 2Pt.
Two-position (on/off)
Frost protection Yes, frost protection No, no frost protection
D.h.w. priority (only
RVP210)
With priority (absolute)
Underfloor heating systems
and boiler operations: al-
ways set to abs.!
abs. par.
No priority (parallel)
RVP210 with boiler temperature control
Regulating unit for d.h.w.
heating
Changeover valve
3Pt. 2Pt.
Charging pump
Setting potentiometers
Settings must be determined during the planning phase.
If missing, the following guide values can be used.
Potentio-
meter
Function Setting range Guide value Notes
Switching differential
with two-position con-
trol
1...20 K Burner control: 6 K
Authority of room
temperature on flow
temperature control
0...100 % authority
OFF = quick setback
is inactive
50 % (quick setback is
active)
Plants with no room
unit: setting is inactive
Plants with no outside
detector:
Setting 0...100 % =
quick setback is active
Setting OFF = quick
setback is inactive
Heating limit for ECO
automatic energy
saver
–10…+8°C (referred
to the room tempera-
ture set value)
–3 K (gives a heating
limit of 17 °C at a room
temperature set value
of 20 °C)
OFF = function disabled
Max. limitation of flow
or boiler temperature
10...100 °C Guide value for under-
floor and ceiling heat-
ing systems:
55 °C max..
OFF = function disabled
Siemens Building Technologies / Landis & Staefa Division 4 319 2697 0 c 16.04.1999 11/12
Commissioning the controller
1. Check wiring according to the plant connection
diagram.
2. Switch on power supply.
3. Check LED for "Override":
-
If it flashes, the detector wiring may be faulty
-
If it is lit, the controller is overridden by a re-
mote operation facility (room unit or changeo-
ver switch). Set room unit to operating mode
or open the external switch)
4. Set operating mode selector to
.
5. Set heating curve potentiometer
to 4 and
setting knob
to +8:
-
Flow temperature must rise: burner on, valve
open, heating circuit pump on (electro-thermal
actuators respond with a certain delay!)
-
If not: check wiring of the detectors
(flow/boiler, outside detector), actuator/burner
and heating circuit pump
6. Set operating mode selector to
.
7. Set heating curve to 0.25 and setting knob
to
–8.
-
Burner must switch off (observe minimum run-
ning time of 4 minutes), valve must travel to-
ward "colder", and heating circuit pump must
remain activated
-
If not: check wiring of the detectors
(flow/boiler, outside detector), actuator/burner
and heating circuit pump
Commissioning the remote operation
facility
1. Set the controller's operating mode selector to
one of the two
positions.
2. If a room unit is present: select operating mode
or on the room unit.
-
Check the "Override" LED on the controller:
must be lit
-
If not: check wiring of the room unit
3. If a changeover switch is present: close it (gives
operating mode
on the controller).
-
Check the "Override" LED on the controller:
must be lit.
-
If not: check wiring of the changeover switch
Commissioning of d.h.w. heating
(only RVP210)
1. The d.h.w. temperature must be around 30 °C
(check by touching or use a measuring instru-
ment).
2. Set the controller's operating mode selector
to
.
3. Set setting knob
to 60.
-
D.h.w. temperature must rise: charging pump
on or changeover valve open
-
If not: check wiring of the d.h.w. temperature
detector and the heating circuit pump, or the
changeover valve
4. Set setting knob
to 10 (observe overrun time)
-
Charging pump or changeover valve must
switch off
-
If not: check wiring of d.h.w. temperature de-
tector
5. Reset setting knob
to 55 (factory-setting).
Settings on the controller
20 10
0
-10 -20 -30
90
80
70
60
50
40
30
4
3,5 3 2,75 2,5 2,25
2
1,75
1,5
1,25
1
0,75
0,5
0,25
100
2462D01
T
V
T
A
110
20
T
A
Outside temperature [°C]
T
V
Flow temperature [°C]
1. Set heating curve as specified in the planning
documentation or in compliance with local prac-
tices.
2. Reset setting knob
to 0 (factory-setting, cor-
responds to 20 °C room temperature).
3. Leave setting knob
to –6 (factory-setting).
4. Set operating mode selector to one of the two
positions.
5. Set time switch as indicated in the operating
instructions.
Seal the transparent cover, if required.
12/12 16.04.1999 4 319 2697 0 c Siemens Building Technologies / Landis & Staefa Division
Connection diagrams
For low voltage
AC 230 V
B9
B3
B3
1
D1 D2
2462A01
2
S1
2462A02
2462A03
3
B3
F3
T
c D.h.w. temperature measurement with a detector (only RVP210)
d External switch for changeover of operating mode
e D.h.w. temperature measurement with a thermostat (only RVP210)
For mains voltage
2464A04
AC 230 V
1
Q1
M3
Q3/Y3
F1/F4 F2 F3
2
F1/F4
F1 F2
E1
2462A05
3
F1/F4
2462A06
Y3
Q3/Y3
4
F3
2462A07
c Connection of three-position actuator, heating circuit pump and (only RVP210) d.h.w. charging pump
d Connection of burner (boiler temperature control)
e Connection of two-position actuator (flow temperature control)
f Connection of actuator for d.h.w. changeover valve (only RVP210)
A6 Room unit QAW50 or QAW70
B1 Flow or boiler temperature detector
B3 D.h.w. temperature detector (only RVP210)
B9 Outside detector QAC22 or QAC32
E1 Burner
F1
Thermal reset limit thermostat
F2
Manual reset safety limit thermostat
F3 D.h.w. thermostat (only RVP210)
M1 Heating circuit pump
M3 D.h.w. charging pump (only RVP210)
N1 Controller RVP2…
S1 External switch
Y1 Three-position actuator
Y2 Two-position actuator
Y3 Actuator of changeover valve (only RVP210)
Maßbild
Dimensions
Dimensions
19
26 26 26 26
15
96
144
114,7
19,7
60,4
14
56
112
4,5
138
+1
0
92
+0,8
0
2462M01
144
1997 Siemens Building Technologies Ltd.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Siemens RVP200 Installation Instructions Manual

Type
Installation Instructions Manual
This manual is also suitable for

Siemens RVP200 is an easy-to-use heating controller that can be used for various heating applications, such as floor or ceiling heating systems, as well as for domestic hot water preparation. It features a clear and user-friendly interface with a backlit display, making it easy to read and adjust settings even in low-light conditions. With its compact design, the controller can be mounted on a DIN rail, control panel, or directly on a wall, providing flexible installation options.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages