CAME CP6099WL Installation guide

Category
Security access control systems
Type
Installation guide
FA00373-EN
BURGLAR ALARM
CONTROL UNIT
INSTALLER MANUAL
CP6099WL
ENGLISH
Page 2 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
INDICE
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . PAG. 3
SYMBOLS AND GLOSSARY . . . . . . . . . . . . . . . . . . . . . . . 3
DESCRIPTION OF USE . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SECURITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
EN 50131 STANDARD - SPECIFIC RECOMMENDATIONS . . . . . . . . . 3
INSTALLING THE SYSTEM . . . . . . . . . . . . . . . . . . . PAG. 4
GENERAL SYSTEM DIAGRAM . . . . . . . . . . . . . . . . . . . . . . 4
RS-485 BUS WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . 5
APPLICATION NOTES REGARDING WIRING THE RS-485 BUS . . . . . . . . . . .5
CHOOSING THE CROSS-SECTION OF THE RS-485 BUS CABLE. . . . . . . . . .5
TRADITIONAL WIRING (in - out) . . . . . . . . . . . . . . . . . . . . . . . . . 6
DOUBLE BRANCH WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
WIRING WITH BRANCHING. . . . . . . . . . . . . . . . . . . . . . . . . . . .6
WIRING WITH BUS AMPLIFIER . . . . . . . . . . . . . . . . . . . . . . . . . .7
INSTALLING THE CONTROL UNIT. . . . . . . . . . . . . . . . PAG. 8
TECHNICAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . 8
MAIN CONTROL UNIT COMPONENTS . . . . . . . . . . . . . . . . . . 8
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SECURING TO THE WALL . . . . . . . . . . . . . . . . . . . . . . . .10
POWERING THE CONTROL UNIT . . . . . . . . . . . . . . . . . . . . .10
230 V AC mains power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
WIRING THE OUTPUTS. . . . . . . . . . . . . . . . . . . . . . . . . .10
PROGRAMMABLE OUTPUT U1. . . . . . . . . . . . . . . . . . . . . . . . . 10
PROGRAMMABLE OUTPUT U2, U3, U4 (Open Collector) . . . . . . . . . . . . 10
GENERAL ALARM RELAY OUTPUTS . . . . . . . . . . . . . . . . . . . . . . 11
PSTN TELEPHONE LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
WIRING THE INPUTS. . . . . . . . . . . . . . . . . . . . . . . . . . .11
STLCDS - STDCSB - STDCSN KEYPADS . . . . . . . . . . . . PAG. 12
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ADDRESSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
KEYPAD DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
SYSTEM STATUS ALERTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SYSTEM STATUS ALWAYS DISPLAYED . . . . . . . . . . . . . . . . . . . . . 13
DISPLAY ICONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
ALPHANUMERIC KEYPAD . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
KEYPAD MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SINTS READER AND SKEYT KEY . . . . . . . . . . . . . . . . PAG. 14
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DISPLAYING THE SYSTEM STATUS. . . . . . . . . . . . . . . . . . . . . . . 15
SRX128D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ADDRESSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . PAG. 16
SIGSM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SSIP/SIFLAN LAN INTERFACES . . . . . . . . . . . . . . . . . . . . .16
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SIFCPKNX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
001SIGPRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
BOARD DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
LED STATUS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INSERTING THE SIM CARD . . . . . . . . . . . . . . . . . . . . . . . . . . 18
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
MANUAL FIRMWARE UPDATE . . . . . . . . . . . . . . . . . . . . . . . . . 18
MANAGING THE CONTROL
UNIT USING THE CAME MOBILE APP. . . . . . . . . . . . . . PAG. 19
CONFIGURING CONNECTIVITY . . . . . . . . . . . . . . . . . . . . . . . . . 19
CAMECONNECT . . . . . . . . . . . . . . . . . . . . . . . . PAG. 21
VIDEO VERIFICATION . . . . . . . . . . . . . . . . . . . . . . PAG. 21
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DESCRIPTION OF THE SYSTEM COMPONENTS . . . . . . . . . . . . . . . . 21
SERVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SYSTEM STARTUP . . . . . . . . . . . . . . . . . . . . . . . PAG. 23
PRELIMINARY INFORMATION . . . . . . . . . . . . . . . . . . . . . .23
ACCESSING THE TECHNICAL MENU . . . . . . . . . . . . . . . . . . . . . . 23
CHOOSING NUMBERS ABOVE 9 . . . . . . . . . . . . . . . . . . . . . . . . 23
OPENING/CLOSING THE CONTROL UNIT . . . . . . . . . . . . . . . . . . . . 23
SYSTEM MAINTENANCE/SERVICING . . . . . . . . . . . . . . . . . . . . . . 23
SWITCHING ON FOR THE FIRST TIME . . . . . . . . . . . . . . . . . .24
POWERING ON THE CONTROL UNIT . . . . . . . . . . . . . . . . . . . . . . 24
SELF-LEARNING MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ADDRESSING AND LEARNING PERIPHERAL DEVICES . . . . . . . . . .25
ACQUIRING KEYPADS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ACQUIRING READERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
ACQUIRING RADIO RECEIVER MODULES ON THE BUS . . . . . . . . . . . . . 26
TOUCH SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
DEFINING SYSTEM AREAS. . . . . . . . . . . . . . . . . . . . . . . .27
PROGRAMMING SCENARIOS . . . . . . . . . . . . . . . . . . . . . .27
CREATING SCENARIOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ASSOCIATING SCENARIOS WITH KEYPADS. . . . . . . . . . . . . . . . . . . 28
ASSOCIATING SCENARIOS WITH READERS . . . . . . . . . . . . . . . . . . 29
PROGRAMMING INPUTS. . . . . . . . . . . . . . . . . . . . . . . . .30
LEARNING RADIO INPUTS . . . . . . . . . . . . . . . . . . . . . . . .31
PROGRAMMING OUTPUTS. . . . . . . . . . . . . . . . . . . . . . . .31
PROGRAMMING TELEPHONE CALLS AND SMSS . . . . . . . . . . . . .31
SETTING PSTN - GSM PRIORITIES . . . . . . . . . . . . . . . . . . . . . . . 31
SETTING TELEPHONE NUMBERS . . . . . . . . . . . . . . . . . . . . . . . 32
RECORDING VOICE MESSAGES FROM PC . . . . . . . . . . . . . . . . . . . 35
SENDING VOICE MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . 35
CREATING USER CODES. . . . . . . . . . . . . . . . . . . . . . . . .35
ENABLING/DISABLING A CODE . . . . . . . . . . . . . . . . . . . . . . . . 36
ACQUIRING KEYS . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
LEARNING TRANSMITTERS . . . . . . . . . . . . . . . . . . . . . . .37
SYSTEM TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
CONNECTING A PC TO THE CONTROL UNIT . . . . . . . . . . PAG. 38
LOCAL PROGRAMMING VIA USB. . . . . . . . . . . . . . . . . . . . .38
RESETTING THE SYSTEM. . . . . . . . . . . . . . . . . . . . PAG. 39
RESETTING CODES . . . . . . . . . . . . . . . . . . . . . . . . . . .39
DEFAULT PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . .39
DEFAULT PARAMETERS VIA DIP SWITCH. . . . . . . . . . . . . . . . .39
ENGLISH
Page 3 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
General information
Symbols and glossary
This symbol indicates parts about safety.
This symbol indicates parts to read carefully.
Light signal on and steady.
Light signal off.
Light signal flashing.
INSTALLER: the person/company responsible for the design, con-
struction and programming of the burglar alarm system.
USER: the person(s) using the burglar alarm system.
Description of use
The CP6099WL burglar alarm control unit is designed to increase
security in residential and service environments, even in places
where a wired system would be particularly difficult to install.
Any installation and operation that differs from what is set
out in this manual is prohibited.
Security
If properly designed, the burglar alarm system guarantees a high
level of security for the environments it is protecting and the users
that are using it.
To ensure this, we need to follow certain rules:
Installation must be carried out by qualified and experienced
personnel in compliance with applicable regulations.
Check the main power connections and relative earth con-
nections.
Once system startup is complete, make sure that the user has
changed the default user code (123456).
EN 50131 STANDARD - SPECIFIC RECOMMENDATIONS
To ensure the system complies with the EN 50131 standard, it
is very important to follow the recommendations below:
the sound signals (buzzers) from the readers cannot be disa-
bled;
the “Memory” type input must not be used;
the inputs configured as “Arming” are only suitable if they are
commanded by devices with more than 10,000 combinations;
the fault signalling of the devices connected to the system is
not required by the standard, but if a device is equipped with this
signal, this must be connected to the input defined as faulty in the
control unit;
the telephone dialler must be active;
an external self-powered siren must be present in the system
to signal that the burglar alarm has been triggered;
the command to force arming of areas with open inputs must
not be armed;
the number of alarms for self-exclusion of an input must be
set between 3 and 10;
the no mains signal time must be set to 1 minute;
the battery test time must be set to more than 5 minutes;
quick arming must not be enabled;
the option to stop communication once the control unit is
switched off must not be enabled;
the Input 1 and Input 2 times can be set to a maximum of 45
seconds;
the system masking time must be set to ≤ 30 seconds;
the pre-arming test must be enabled.
4,7 kohm
ENGLISH
Page 4 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Installing the system
General system diagram
GSM
Antenna
SIGSM
SSIP/SIFLAN SIFCPKNX
SIGPRS
SIFTS01
Touch
screen
Touch
screen
PC-Control Unit
connection via USB
Telephone
PSTN
Telephone line
Self-powered
siren
Siren
Single balancing
input
NC input
230 V AC
power supply
Bus branch
󰽤
󰽥
ENGLISH
Page 5 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Above 12 V DC
YES
NO
Always wire the bus in “in and out” mode. Do not wire the bus in a
star configuration.
If you need this configuration, follow the instructions given in this
chapter.
In the case of long bus stretches, always install 150 ohm resistors
between terminals A and B of both bus heads.
The maximum cable length (maximum 800 m stretches) and the
cross-section of the core depend on the number of modules and
the overall current draw on the various bus stretches. As the cur-
rent draw increases, so does the voltage drop on the cables and the
supply voltage to the devices on the bus decreases.
The voltage at all the + and - terminals of the bus devices (keypads,
readers, modules...) should not be less than 12 V DC.
If it is less, add an auxiliary power supply, disconnecting the positive
and keeping the negative common.
RS-485 bus wiring
APPLICATION NOTES REGARDING WIRING THE RS-485 BUS
The wiring on the bus connecting the control unit to the readers,
keypads and amplifiers must follow the rules dictated by the RS-
485.
Use shielded twisted cables only, with a cross-section of at least:
󰽤 2x0.5 mm² for the power supply and 2x0.22mm² twist-
ed for data.
󰽥 2x0.5 mm² for the power supply and 2x2x0.22mm²
twisted for data (use to create branches).
The braid must be continuous and connected to the negative (-)
terminal on the control unit.
CHOOSING THE CROSS-SECTION OF THE RS-485 BUS CABLE
The recommended cable for the RS-485 bus is:
Twisted and shielded cable - grade 4 (600/1000 V).
One twisted pair for data - cross-section 2x0.22 mm².
One pair for power supply - cross-section 2x0.5 mm²
or higher depending on the distances and currents (see
table below).
Please find a table below to help you calculate the cross-section of
the power cables as the distance and current draw vary.
MAXIMUM LENGTH
OF THE RS-485
CABLE
CURRENT DRAW
0.1 A 0.25 A 0.5 A 1 A
CROSS-
SECTION
0.5 mm2 175 m 70 m 35 m 17 m
0.75 mm2 262 m 105 m 52 m 26 m
1 mm2 350 m 140 m 70 m 35 m
1.5 mm2 525 m 210 m 105 m 52 m
The supply voltage drop should not exceed 1.4 V (voltage
measured on the power supply terminals and the terminals on the
bus device that is furthest away).
If a cable with a suitable cross-section is not available, the use
of additional auxiliary power supplies should be taken into
consideration.
Example: Let’s assume we have connected the following at a
distance of 200 m:
A STDCSB keypad (maximum current draw 60 mA)
A SINTS transponder reader (maximum current draw 100 mA)
A SRX128D radio expansion module (maximum current draw
100 mA)
Having a maximum current draw of 260 mA, in this case, the
alternatives are to use a cable with a cross-section of 1.5 mm²
or a cable with a cross-section of 0.5 mm² and an auxiliary power
supply connected at the end of the line as shown below:
ENGLISH
Page 6 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
WIRING WITH BRANCHING
The branching consists of a cable with 3 pairs of which 2
are twisted (each pair is composed of cores A and B). Analysing the
circuit thus produced, we note that the structure of the RS-485 bus
continues to be linear (in-out).
DOUBLE BRANCH WIRING
RS-485 CABLE
Shielded 2x1.5mm² + 2x0.22mm² twisted
Control unit Device on bus
RS-485 CABLE
Shielded 2x0.5mm² + 2x0.22mm² twisted
Control unit Auxiliary
power supply Device on bus
If the remote devices have been installed correctly, all the
BUS communication LEDs on each device will flash. If some do
not flash, this means that the device has not been installed and
programmed correctly (check control unit wiring, addressing and
programming).
TRADITIONAL WIRING (in - out)
ENGLISH
Page 7 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
WIRING WITH BUS AMPLIFIER
Bus amplifier
SRS485
SRX128D
SRX128D
󰒄
󰒅
󰒉
󰒆
󰒊
󰒇
󰒋
󰒈
󰒌
󰒍
󰒎
󰒏
ENGLISH
Page 8 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Installing the control unit
Technical features
1. 230 V AC mains connection terminals.
Be careful, live parts.
2. Battery connection cables.
Respect the polarity (red = +, black = -)
3. Control unit tamper
4. Mains fuse. Glass fuse, T, 315 mA, plus PTC thermal protector
in the transformer at 120 ° C.
5. Microphone and speaker
6. Battery restraint
7. Acoustic warning device
8. 868 MHz antenna
9. 433 MHz antenna
10. Spirit level for adjusting the tilt
11. Transformer
12. Keypad with graphic display - 160x32 pixels
Main control unit components
Supply voltage 230V AC 50Hz –15% + 10%
Transformer 17 VA
Maximum power supply
delivery 400 mA
Battery 12 V - 2.2 Ah
Operating temperature 0° - 40°C
Relative humidity 25% - 75% non-condensing
Maximum safety rating 2
Environmental class II
Insulation class
Dimensions (HxLxD) 300x250x65 mm
Container ABS RAL9003
IP IP30
Weight 2.7 kg
Areas
8
Scenarios
16
Radio inputs
99
Wired inputs in control unit
6
Type of inputs in control unit
NC, NO; SB, DB, PC
Relay outputs on board
1
Open collector outputs
programmable on the control
unit
4
Radio concentrator modules
on bus
1 built-in + 2 optional on bus
Transponder readers
1 built-in + 2 optional on bus
Keypads
1 built-in + 2 optional on bus
Radio receivers
1 built-in + 2 optional on bus
Touchscreen
Yes
Acoustic warning device
Built-in
Transponder keys
20
Installer codes
1
User codes
20
Transmitters
32
Programmable timer
20 daily operations
Events
999
485 BUS
1
PSTN dialler
Built-in
GSM dialler
Optional
Voice synthesis
Built-in
Audio
Built-in microphone and
speakers for recording and
playback of messages
Telephone numbers
8+1
CONTACT-ID
Yes
FW can be reprogrammed from
control unit Yes
LAN interface
Optional
USB communication port
Built-in
Control via SMS
Yes (with GSM)
Control via VOICE
Yes
LAN Remote Programming and
Assistance Yes (with LAN interface)
PSTN Remote Programming
and Assistance Yes
GSM Remote Programming and
Assistance
Yes (with GSM)
RTC + backup battery
Yes
󰒄
󰒋
󰒌
󰒏
󰒕
󰒎
󰒔
󰒈
󰒅
󰒒
󰒆
󰒇
󰒍
󰒉
󰒓
󰒊
󰒐
󰒑
ENGLISH
Page 9 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Board description
1
RS-485 bus terminals for connecting keypads, radio
concentrators and readers:
[+,-] bus power supply;
[A,B] data;
[F6] self-resetting fuse - 1.35 A.
2
Control unit input terminals - can be NO, NC, SB, DB, PC.
[+,-] power supply;
[1,2,3,4,5,6] inputs (the reference is to negative);
[F3] self-resetting fuse - 1.35 A.
3
Control unit output terminals:
[AUX +, -] output power supply available protected by F5
self-resetting fuse;
[U1] output programmable to positive protected by 100
ohm resistor (ON=13.8 V DC, OFF=NO);
[U2,U3,U4] open collector output programmable to negative
protected by 100 ohm resistor (ON=0 V DC,
OFF=NO);
[NO, C, NC] general alarm relay with dry contacts;
[F5] self-resetting fuse - 1.35 A.
A short circuit with the open collector output active for
an extended time may lead to the breakage of the protection
resistor.
4
[JP3] jumper to enable/disable the anti-opening tamper
(position C to disable it, position O to enable it).
[JP4] jumper to enable/disable the tear-resistant tamper
(position C to disable it, position O to enable it).
5[SW2] Control unit anti-opening slide tamper.
6[SW3] Control unit anti-opening slide tamper.
7[CN2] Connector for GSM module.
[F4] self-resetting fuse - 1.35 A.
Board description
CURRENT DRAW AND BATTERY LIFE OF CP6099WL POWERED
BY 12 V DC BATTERY 2.2Ah
Current draw with control unit
in standby without accesso-
ries and peripheral devices
connected
95 mA with keypad backlight
off
110 mA with keypad back-
light on at maximum intensity
Current draw with control
unit in alarm mode and PSTN
calling
155 mA
Current draw with control unit
in alarm mode and GSM calling 230 mA
Board description
8
1
Dip1 is used to switch the control unit from service to
maintenance (ON= Maintenance, OFF= Service).
2
Dip2 is used to restore the default settings for the
codes.
ON
1
Dip3 is used to reset the default parameters
(parameters + codes + keys).
ON
1
Dip4 is used to reprogram the control unit firmware.
9[P1] button to reboot the control unit (does not reset
parameters; does not alter the configuration).
10
PE] earthing terminal.
[L, L] external PSTN telephone line input terminals.
[T, T] PSTN telephone line output terminals to telephone or
control unit.
11
[CN1] connector for connecting to the Ethernet interface or the
touchscreen via the SIFTS01 interface.
[F4] self-resetting fuse - 1.35 A.
12 [CN9] USB socket for connection to the PC (with A-B USB
cable).
13 [F8] glass fuse, T, 3.15 A.
14 [V AC] 230 V AC mains connection terminals.
15 [CN7] battery connector.
[F2] self-resetting fuse - 1.6 A.
16 [CN13] connector for connecting the control unit base board to
the keypad board.
17 [CN3] connector for connecting the control unit base board to
the audio board.
18 Radio indicator LED
CURRENT DRAW AND BATTERY LIFE OF CP6099WL POWERED
BY 12 V DC BATTERY 2.2Ah
Battery life* with control unit
in standby without accesso-
ries and peripheral devices
connected
Minimum 15 hours
*CAUTION: The battery life decreases depending on the number
of alarms and/or telephone calls and/or manoeuvres performed,
and depending on the number of accessories/peripheral devices
connected
250
300
197 2578
125125
+ - TC TAMPER ALARM
5 6
󰒅
󰒄
ENGLISH
Page 10 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
After disconnecting the mains power supply, remove the Plex-
iglas protection on the terminal block by unscrewing the two
screws attached to the transformer 󰒄.
Connect the 230 V AC Line and Neutral cable to the terminal
block terminals (the power supply cables must enter the pre-
drilled hole󰒅)
Replace the Plexiglas protection on the terminal block, secur-
ing it to the transformer with the two screws.
U1 is an output (freely-programmable) which provides a positive
when active:
U1 ON = 13.8 V DC
U1 OFF = not connected
The default programming is TC for the inhibition of the microwave
with the system is off (U1 = OFF if at least one area is on or in exit
time; U1 = ON if the system is completely off).
The output is protected by a 100 ohm resistor.
It can also be used to command sirens or other loads.
PROGRAMMABLE OUTPUT U2, U3, U4 (Open Collector)
A short circuit to 12 V DC with the output active for an extended
time may lead to the breakage of the protection resistor.
Non-self-powered siren
U2, U3, U4 are open collector outputs (freely-programmable) that
provide a negative when they are active:
U2, U3, U4 ON = 0 V DC
U2, U3, U4 OFF = not connected
The outputs are protected by 100 ohm resistors.
Wiring the outputs
PROGRAMMABLE OUTPUT U1
A short circuit to earth with the output active for an extended
time may lead to the breakage of the protection resistor.
Securing to the wall
Install the control unit away from access points and points that are
difficult to identify.
Secure to a suitable wall that can support the control unit over time.
Make the holes and channel to pass the cables through before in-
stallation.
Use the 2 prepared holes for securing to the wall.
Powering the control unit
230 V AC mains power
Provide a suitable dual-pole disconnection device (circuit
breaker), with a maximum of 3 mm between the contacts, to
disconnect the power supply.
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
4,7 KOHM
4,7 KOHM
+ - TC
+ - TC
TAMPER ALARM
TAMPER ALARM
ENGLISH
Page 11 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
If you want to control a relay with an open collector output (or relay
output), it is necessary to add a diode (1N4007) in parallel with the
relay coil.
GENERAL ALARM RELAY OUTPUTS
The RELAY 1 output is a general alarm output and is not
programmable. It follows the general alarm status and remains
active for the programmed time.
Non-self-powered siren
Self-powered siren
PSTN TELEPHONE LINE
The PSTN telephone line must be connected to the [L, L] terminals
and in output to the [T, T] terminals for switchboards or telephones.
“Simulated” telephone lines (lines coming out from
ADSL routers) can cause disturbances to CONTACT-ID digital
communications to the security companies.
Wiring the inputs
Balances are made using 4.7 kohm resistors at 5%.
Yellow 4
Purple 7
Red 100
Gold 5%
NORMALLY OPEN (NO)
NORMALLY CLOSED (NC)
SINGLE BALANCING (SB)
PULSE COUNT OR INERTIAL (PC)
The U1 output provides a positive with an active output (ON = 13.8
V DC). By default, the U1 output is programmed as TC (output active
when the system is off and active during the exit time and when at
least one area is armed).
DOUBLE BALANCING (DB)
DOUBLE BALANCING SENSOR (DB)
DOUBLE BALANCING SENSOR (DB) WITH MICROWAVE
BLOCK WITH CONTROL UNIT OFF (TC)
󰽤
a
󱎵
08:24 19/03/13
#####UUUPX---
08:24 19/03/13
#####UUUPX---
ENGLISH
Page 12 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
STLCDS - STDCSB - STDCSN keypads
BOARD DESCRIPTION
1. RS-485 bus terminals for connecting keypads and readers:
[+,-] bus power supply;
[A,B] data.
2. [SW1] Anti-opening and tear-resistant tamper.
3. [JP1] Jumper to enable/disable the tamper, see 󰽤
4. Red bus communication alert LED. If this flashes, it
means that the keypad is communicating with the control
unit.
5. Keypad buzzer.
keypads connected on the bus and the local keypad built into the
control unit.
KEYPAD DISPLAY
The display consists of two lines of 16 graphic characters. At rest,
the keypad goes into “Power saving” mode, decreasing the light
intensity after a set time.
On some models of keypad, below the display, there are 16 num-
bers that facilitate the interpretation of the second line of the dis-
play, with the following key:
# = area armed;
U = area being armed (exit time countdown under way);
X = area being armed but not ready for arming due to the present
of open inputs;
P = area partially armed (there is at least one input associated with
the area that is temporarily excluded);
R = area in active patrol mode;
N = disarmed area that is not ready;
- = area off;
= area not managed by the keypad.
Example: reading the display 󱎵 showing:
Areas managed: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13.
Areas not managed: 14, 15, 16.
Areas armed: 1, 2, 3, 4, 5.
Areas being armed: 6, 7, 8.
INSTALLATION
The keypads must be wall-mounted in sheltered environments,
raised or recessed with the 001DC00VISIO01 box (only
STDCSN/STDCSB).
Connect the control unit and keypads on the respective terminals
[+ A B -].
ADDRESSING
The keypad address is assigned by the control unit during ad-
dressing.
User interface
Subsequent descriptions apply to both STDCSN/STDCSB/STLCDS
“Flat” capacitive keypads in black (STDCSN) or white (STDCSB) or
with hatch (STLCDS) which can be connected to the bus. Can be
wall-mounted or recessed.
Blue backlit LCD, touch-sensitive keys (STDCSN/STDCSB) or mem-
brane keys (STLCDS).
STDCSN
STDCSB
STLCDS
Tamper ON Tamper OFF
STLCDS
ENGLISH
Page 13 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
DISPLAY ICONS
Icon Meaning
CAME logo
System armed
System disarmed
System partially armed
Programming
Event log
User menu
Alarm log
Not ready for arming
Generic power failure
230 V mains power failure
Battery failure
PSTN line fault
GSM line fault
Serial connection (local)
Ethernet connection (remote)
ALPHANUMERIC KEYPAD
Keys Functions
The alphanumeric keys allow users to enter codes,
select the areas being armed and edit the param-
eters.
Menu navigation and selection keys.
Parameter editing keys.
After entering the code, users gain access to the
User Menu. If pressed for more than 5 seconds, it
allows access to the keypad menu.
Scenario launch keys.
System shutdown key.
KEYPAD MENU
The Keypad Menu is independent from the control unit menu and
allows users to set various keypad characteristics such as the lan-
guage, the contrast and brightness of the display, the illumination
of the keys and the system status LEDs, and other functions as
shown in the table below.
To enter the Keypad Menu, press and hold for a few seconds,
until the Keypad <|> language screen appears on the display. Then use
the keys to navigate and select as shown.
Keypad <|> cleaning enables users to clean the keypad safely. Entering
the values with 󰯯, a 30-second countdown begins, during which
the keypad is not active. At the end, it automatically returns to the
menu.
Areas partially armed: 9.
Areas not ready: 10.
Areas off: 10, 11, 12, 13.
SYSTEM STATUS ALERTS
The system status alerts behave according to installer program-
ming.
Depending on installer programming, the display can be kept al-
ways visible (LEDs and display visible) or masked for improved
safety (no system status information given to unauthorised per-
sons). Only the alarm LEDs (RED for the readers and YELLOW for
the keypads) remain visible if activated.
Following the activation of a scenario or any other system manage-
ment activity, after a programmed time (30 seconds max.), all the
other LED and display alerts are interrupted and the LEDs go off.
SYSTEM STATUS ALWAYS DISPLAYED
LED
(colour) Status Meaning
(green)
Indicates that there are open inputs. If a sce-
nario is launched, an alarm may be generated.
Check the inputs open when the scenario is
launched.
Indicates that there are NO open inputs. The
system can be turned on without problems.
(green)
Indicates that the managed areas are off (sys-
tem off).
Indicates that all the managed areas are on
(system fully on).
Indicates that at least one managed area is on
(system partially on).
(red)
Indicates that the managed areas are NOT in
alarm mode.
Indicates that at least one managed area is in
alarm mode (system in alarm mode).
Indicates that the associated system has de-
tected an alarm that has been muted. See the
event list for the alarm log.
(yellow)
Indicates that there are no faults on the system.
Indicates that there is a fault.
When the ‘Status masking’ function is active, this
indicates the presence of an event to display.
It may indicate that: the mains power supply
(230 V AC) is absent; the battery of a radio pe-
ripheral device needs to be replaced; a fuse
needs to be replaced; a fault input is unbal-
anced; the clock has not been initialised; there
is a problem on the PSTN or GSM line; the GSM
module SIM has expired.
Indicates that the control unit battery needs to
be replaced
= Off | = On | = Flashing
The reporting of events that occur at the same time follows
the following priority: alarms, exit times, faults. The on-screen dis-
play occurs cyclically.
󰒄
ENGLISH
Page 14 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Keypad <|> version allows users to view the software version of the
keypad only.
Press [#] twice in a row to exit the Keypad Menu. After 60 seconds
have passed with no operation, the keypad automatically exits the
Keypad Menu.
The LEARNING menu is only available on radio keypads.
MENU HEADINGS VALUES

Keypad
language
󰯯 -> 󰯲 ITALIANO / ENGLISH /
FRANÇAIS / ESPAÑOL /
PORTUGUÊS 󰯰
<- 

Keypad
version
󰯯 -> 󰯲 CAME
v. 1.01 󰯰
<- 

Learning
No. 02 SN00000021
󰯯 -> 󰯲 LEARNING
N.--XXXXXXX 󰯰
<- 

Keypad
cleaning
󰯯 -> 󰯲 Keypad cleaning
30 s 󰯰
<- 

Tamper 󰯯 -> 󰯲Tamper
disabled/enabled 󰯰
<- 

Buzzer 󰯯 -> 󰯲 Buzzer
disabled/enabled 󰯰
<- 

Display ON
time
󰯯 -> 󰯲 Dis time ON
10 s 󰯰
<- 

Min status
LED brightness
󰯯 -> 󰯲 MIN. LED BRIGHTN.
▌▌▌▌▌ 󰯰
<- 
MENU HEADINGS VALUES

Max status
LED brightness
󰯯 -> 󰯲 MAX. LED BRIGHTN.
▌▌▌▌▌ 󰯰
<- 

Min keypad
brightness
󰯯 -> 󰯲 MIN. KEYP. BRIGHTN.
▌▌▌▌▌ 󰯰
<- 

Max keypad
brightness
󰯯 -> 󰯲 MAX. KEYP. BRIGHTN.
▌▌▌▌▌ 󰯰
<- 

Min display
brightness
󰯯 -> 󰯲 MIN. DIS. BRIGHTN.
▌▌▌▌▌ 󰯰
<- 
Max display
brightness
󰯯 -> 󰯲 MAX. DIS. BRIGHTN.
▌▌▌▌▌ 󰯰
<- 

Display
contrast
󰯯 -> 󰯲 DIS. CONTRAST
▌▌▌▌▌ 󰯰
<- 

To enter the Keypad Menu, press and hold for a few seconds,
until the KEYPAD LANGUAGE screen appears on the display. Then use
the keys to navigate and select as shown.
KEYPAD CLEANING enables users to clean the keypad safely. Entering
the values with 󰯯, a 30-second countdown begins, during which
the keypad is not active. At the end, it automatically returns to the
menu.
KEYPAD VERSION allows users to view the software version of the key-
pad only.
Press [#] twice in a row to exit the Keypad Menu. After XX seconds
have passed with no operation, the keypad enters STANDBY mode
and after a further xx seconds, it automatically exits the Keypad
Menu.
BOARD DESCRIPTION
SINTS reader and SKEYT key
󰒄- WIRING SERIES HOLE COVER CAP
󰒅- TRANSPONDER READER
󰒆- INDICATOR LED
󰒇- KEY-SENSITIVE AREA
RS-485 bus terminals for connecting keypads and readers:
[+,-] bus power supply;
[A,B] data.
If
PRE ENTER TEST
has been enabled in the technical menu in
SPECIAL FUNCTIONS
, in the event of existing system anomalies (e.g. no
phone line, no communication with at least one system device etc.)
scenario startup via the reader will be disabled (the reader will emit
a beep, cancelling the operation).
The SINTS reader is a transponder reader for SKEYT keys, which
can be used to manage alarm system arming/disarming, using up
to 3 adjustable scenarios.
The key is used to manage the system via the reader. It contains
no batteries and must first be acquired by the control unit in order
to operate.
Each key is recognised uniquely within the control unit and the
event log.
ENGLISH
Page 15 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
INSTALLATION
The connector occupies just one module in the switchboxes of any
residential-use system.
Connect the control unit and readers on the respective terminals
[+ A B -].
For addressing and acquiring the readers and keys, see the relevant
chapters.
The readers must be installed in an area protected from break-
ins or in a guarded area of the system, otherwise the reference
standard is voided.
DISPLAYING THE SYSTEM STATUS
LED Meaning
Indicates that scenario 1 is not active.
Indicates that scenario 1 is active.
during the exit time, it indicates that there is at
least one scenario 1 input open.
when the system is off, it shows whether there
are open inputs belonging to the areas managed
by the reader.
Indicates that scenario 2 is not active.
Indicates that scenario 2 is active.
during the exit time, it indicates that there is at
least one scenario 2 input open.
when the system is off, it shows whether there
are open inputs belonging to the areas managed
by the reader.
Indicates that scenario 3 is not active.
Indicates that scenario 3 is active.
during the exit time, it indicates that there is at
least one scenario 3 input open.
when the system is off, it shows whether there
are open inputs belonging to the areas managed
by the reader.
Indicates that the associated areas are off (sys-
tem off).
Indicates that at least one associated area is on
(system on or partially on).
Slow flashing to indicate that the system is on
and has detected an alarm.
Quick flashing to indicate that the system is off
and is in alarm log mode.
See the event list for the alarm log. To remove
the alert, see the system management chapter.
off, on steady, on flashing ( quick, slow)
With the transponder reader, you can view the system status
through the alerts given by its LEDs, as shown in the table above.
Depending on programming, the display can be kept always visible
(LEDs on steady or flashing) or masked for improved safety (no
system status information given to unauthorised persons). The LED
alerts are only visible following the activation of a scenario or any
other system management activity, after a programmed time (30
seconds max.), they are interrupted and the LEDs go off. Only the
red alarm LED (LED 4) remains visible when activated.
SRX128D
Receiver to for two-way communication with all the radio devices
connected and addressed in the control unit.
BOARD DESCRIPTION
1. RS-485 bus terminals for connecting keypads and readers:
[+,-] bus power supply.
[A,B] data.
2. [BUS] red bus communication alert LED. If flashing, this
means that the module is communicating with the control unit.
3. [ERR] red radio communication LED indicating incorrect
receipt or peripheral device not associated.
4. [OK] green radio communication LED indicating correct
receipt.
5. Green LEDs indicating the intensity of the signal received. A
signal received correctly consists of at least 3 bars.
6. [SW1] 8 dip switches for:
[1..4] setting the module address;
[5] activating the LEDs (ON active);
[6,7] not used;
[8] disabling the tear resistant tamper (ON disabled).
7. [R] Button to reboot the receiver (e.g. after an address
change).
8. [M] Button not used.
9. [SW2] Anti-opening tamper.
10. [SW3] Tear-resistant tamper.
INSTALLATION
The receiver must been installed in a sheltered place and in the
best position to receive the radio signal from the various connected
devices.
Connect the control unit and receiver on the respective terminals
[+ A B -].
ADDRESSING
The local radio module address is 01, therefore the address 02 or
03 can be set for the modules connected on the bus.
C.U. ADDRESS
0 Invalid
1 Invalid
2
3
󰒆
󰒇
󰒅
󰒄
󰒉
󰒊
󰒈
󰒊
󰒅
󰒆
󰒄
󰒇
ENGLISH
Page 16 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Accessories
SIGSM
Telephone dialler suitable for all CP control units, complete with
whip antenna. It allows users to send SMSs and voice messages
as well as receive SMSs and DTMF commands for remote control.
BOARD DESCRIPTION
terminal block, then connect it to the SIGSM interface 󰒆 and se-
cure the latter with the three turrets 󰒇 supplied to the control unit
board 󰒈.
Connect SIGSM from connector 󰒊 to connector CN2 󰒋 on the
control unit board.
Power the control unit and, after a minute, check that the green
LED DL1 󰒉 on SIGSM indicates the SIM has been registered cor-
rectly, flashing slowly .
SSIP/SIFLAN LAN INTERFACES
The SSIP interface enables the user to program, read the
configuration and display the status of the control unit from a PC
using the SWLINK program.
In addition to offering the same functions as the SIFLAN interface,
the SSIP interface also enables the user to control the unit using a
keypad simulated by a web page.
For remote connection to the SSIP and SIFLAN interfaces,
it is necessary to configure the router connected to the domestic
network (see relative instruction manual).
BOARD DESCRIPTION
Attach the interface card 󰒄 to the four turrets 󰒅 positioned on the
Plexiglas bracket 󰒆 already installed in the control unit board 󰒇.
In order to configure the devices, see the relative instruction
manuals.
5. Terminal block for connection
to the master touchscreen (for
SIFLAN only)
6. LAN connection
7. Connector for connecting to the
control unit
8. Button to reset to default
9. Communication type selection
(for SSIP only, default A)
In order for the control unit to operate correctly, the jumpers
[JP1] - [JP2] pos. 󰒈 on SSIP must stay in position A.
The monochromatic touchscreen must be connected to the alarm
control unit using the LAN interface. This is only possible with
SIFLAN using terminal block 1.
INSTALLATION
All operations to enable and disable the board must be carried
out while the control unit is not powered.
1. Connector for connecting to the control unit board.
2. SIM slot.
3. [DL1] Green LED indicating GSM operation:
GSM module off or not present.
Active GSM call (incoming or outgoing).
GSM dialler not registered in the GSM network.
GSM dialler registered correctly in the GSM network.
4. Connector for GSM antenna.
INSTALLATION
All operations to enable and disable the interface must be car-
ried out while the control unit is not powered.
Secure the antenna 󰒄 to the Plexiglas protection 󰒅 covering the
+TX RX
CN2
M1
KNX PROG
M2
+
BUS
KNX
CN1
BUS
a
 
SIM900
+ RX TX -
SIM
SIM900
+ RX TX -
SIM
a
ENGLISH
Page 17 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
SIFCPKNX
The 001SIFCPKNX interface card greatly expands the communica-
tion possibilities of CP control units, enabling them to communicate
with the KNX system. It is connected to the port available on all
control units and in turn makes the communication ports available.
BOARD DESCRIPTION
a Main RS232 port;
USB port. A USB port is available for connecting to a PC in order
to perform programming with the SWLink software. In this case, the
connection between the control unit and the PC is direct and can be
made using a simple USB cable.
- During USB connection to the PC, or when IFLAN connection is
active, communication from the control unit to the KNX BUS is in-
terrupted.
- The USB connection is not active in the presence of IFLAN cards.
KNX key and programming LED;
KNX BUS terminal block;
Second RS232 port: This connects the device to the control unit
via the IFLAN terminal block when present.
INSTALLATION
CAUTION. In order for a security event to be properly published
on the KNX bus, the minimum duration of this event must be equal
to or greater than 3 seconds.
CAUTION. For programming details, contact your service
representative.
CAUTION. The device must be installed by qualified personnel,
following the current regulations and guidelines for KNX installations.
001SIGPRS
Telephone dialler suitable for all CP control units, complete with
whip antenna. It allows users to send SMSs and voice messages
as well as receive SMSs and DTMF commands for remote control.
It also allows users to manage the security system remotely via the
Came Domotic app and/or via Came Touchscreen and also manage
Video Verification in combination with PIR camera sensors.
BOARD DESCRIPTION
a Connector for GSM antenna.
Connector for connecting to the CP control unit
SIM slot
Connector for connecting the IGSM interface on the control unit
board
Status indicator LED
Slot for micro SD (supplied) containing the module software
Connectors for connecting the 001SDGETH/001SDGWF acces-
sories
Connector for Konnex touchscreen/interface
Assembly turrets
Labels with the WiFi credentials (present even if the 001SDGWF
accessory is not installed)
LED STATUS
On, Off, Flashing (2 flashes per second), Slow flashing (1
flash every 3 seconds), Quick flashing (1 flash per second)
DL1 GREEN - Cloud Connection Status
Absent
Connecting
Connected
DL2 RED - Internet connection Status
Absent
Connecting
Connected
001SIGPRS
001SDGETH
001SDGWF
CP6099WL
ENGLISH
Page 18 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
DL3 RED - Module power-on Status
GSM module off
GSM module on
DL4 GREEN - GSM modem Status
Off
GSM network not found
GSM network found
Connected to the GSM network
INSERTING THE SIM CARD
The SIM card must be inserted and removed while the power is
disconnected.
After powering on the control unit, check that the GSM LED indi-
cates that the SIM has been registered correctly.
The SIM card (not included) must have the following characteristics:
- VOICE + SMS: incoming/outgoing calls and SMS management,
- VOICE + SMS + DATA:connection to the Cloud, e-mailing for video
verification,
- VOICE + SMS + MMS: sending MMSs for video verification.
INSTALLATION
With the control unit not powered, connect the connector on the
module to the CN1 connector on the control unit, using the flat cable
supplied and, if present, connect the accessories to the module via
the dedicated connectors.
Insert the SIM into the slot .
Secure the 001SIGPRS module to the control unit board using the
turrets supplied, making sure to connect the IGSM connector
correctly to the CN2 connector.
CONFIGURATION
The device is detected automatically by the control unit. To register
the device on CameConnect (www.cameconnect.net), please refer
to the relative manual.
MANUAL FIRMWARE UPDATE
Use the following link:
http://www.cameconnect.net/came/pages/download.html
to download the latest software version available for the 001SIG-
PRS module: camesecurity_<major>-<minor>.bin
Copy the file “camesecurity_<major>-<minor>.bin” to the first
level of a USB drive.
1. Remove the USB-ETH (001SDGETH) or USB-WIFI (001SDGWF)
dongle to free up a USB port.
2. Insert the drive on which the new software has been saved in the
USB connector.
3. After a few seconds, the red DL2 LED and the green DL1 LED light
up quickly alternately way to indicate the software update phase
(this phase lasts a few dozen seconds).
4. Once the update is complete, all the LEDs go off and the module
reboots.
5. Remove the USB drive and put back the dongle you removed
previously.
6. The module is operational.
a
a
ENGLISH
Page 19 - Manual code: FA00373-EN ver. 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
Managing the control unit using the Came Mobile app
Using the Came Mobile app , just a few clicks means you can
securely connect to your control unit and check the status of all
the environments, activate scenarios and interact with your home
remotely, simply from your smartphone or tablet.
In order to manage the control unit via the Came Mobile app, you
must first install firmware version 2.3.00 or later, install the 001SIG-
PRS GPRS module and install the Came Domotic app 1.4.7 or later
on your smartphone/tablet.
Security can be managed via a local connection, connecting direct-
ly to the IP address of the 001SIGPRS module interfaces (in this
case, the 001SDGWF or 001SDETH accessories are necessary) or
via remote connection - in this case, you need to register on the
CameConnect portal (see CameConnect chapter).
CONFIGURING CONNECTIVITY
The 001SIGPRS module can be connected to CameConnect using
a GPRS connection, Ethernet connection (using the 001SDGETH
accessory) or WiFi connection (using the 001SDGWF accessory).
To program the parameters related to connectivity, use the
following: SWLink in version 2.1.4, while for programming the
graphic maps, Came D Sw software version 1.2.2 or later is re-
quired.
CameConnect connectivity via GPRS [GPRS]
If connecting to CameConnect via GPRS, set the following:
a Select [GPRS] from the types of connection.
Select [Connectivity] [GSM].
Enter the [APN] (Access Point Name).
Generally, telephone operators publish this information on their
websites.
If you need to change the telephone number.
Enter the [User Name] and [Password] for data connection.
Generally, telephone operators publish this information on their
websites.
CameConnect connectivity via Ethernet [ETHERNET]
If connecting to CameConnect via Ethernet , it is necessary to use
the 001SDGETH accessory to connect to the user network.
In the default configuration, the Ethernet interface is config-
ured in static mode with the following IP address: 192.168.1.100.
These settings should be adapted to the customer’s network.
To set up connectivity via Ethernet, you must:
a Select [ETHERNET] from the types of connection.
Select [Connectivity] [ETHERNET].
Enable the DHCP Server if present in the customer’s network.
In this way, the 001SIGPRS module automatically acquires the net-
work parameters.
In the case of programming with DHCP, if a reading of the
control unit configuration is taken, the IP Address/Netmask fields
show the address acquired by the interface dynamically.
If you want to set up the module with a static address, disable this
preference.
Set the parameters in a manner consistent with the network
where the device is connected. You also need to set the DNSs for
connectivity to CameConnect.
Port to connect the PC for programming with SWLink.
Choosing the keypad to emulate.
In addition to connection to CameConnect for remote manage-
ment, the 001SDGETH accessory also allows the control unit to be
connected to a local network so that it can be managed by Came
TouchScreens and using the Came Domotic app on the same local
network.
a
Keycode: 577A13EEFA6F1D27 560121
001SIGPRS
WiFi SSID:CameSecurity - 1D27
WiFi Pass:qtEc35vtggBqgQwc
Keycode: 577A13EEFA6F1D27 560121
PXGPRS
WiFi SSID:CameSecurity - 1D27
WiFi Pass:qtEc35vtggBqgQwc
ENGLISH
Page 20 - Manual code: FA00373-EN ver. 1 05/2016 © CAME S.p.A. - The data and information provided in this manual are subject to change at any time without prior notice.
CameConnect connectivity via WIFI [WIFI]
If connecting to CameConnect via WiFi , it is necessary to use the
001SDGWF accessory. In this case, it is necessary to connect the
module to the user’s WiFi network.
In the default configuration, the WiFi is configured as an Access
Point so that the PIR Camera sensors (IR sensors related to video
verification) or other network devices can connect directly to it.
- The default SSID is “CameSecurity-xxxx” (where xxxx are the last
4 digits of the keycode)
- Password: <Random string of 16 characters>
The WiFi data is written on the label inside the package.
The device’s Wi-Fi network is hidden, so it is not visible on
scanning. To connect to the WiFi network, you have to enter the
SSID/Password credentials (see manual of the operating system of
the PC on which you are working).
To connect to the WiFi network, you have to enter the SSID/Pass-
word credentials (see operating system manual).
To connect the GSM module to a home WiFi network, you must:
a Select [WIFI] from the types of connection.
Select [Connectivity] [WIFI].
Uncheck [Access point mode] in order to set WiFi mode as ‘Sta-
tion’.
Enter [SSID] and select the type of [PROTECTION] of the Cus-
tomer’s network.
Enter the [PASSWORD] for the Customer’s network.
Enable the DHCP Server if present in the customer’s network.
In this way, the 001SIGPRS module automatically acquires the net-
work parameters.
In the case of programming with DHCP, if a reading of the
control unit configuration is taken, the IP Address/Netmask fields
show the address acquired by the interface dynamically.
If the customer’s network does NOT feature a DHCP Server, disable
function and manually enter the parameters related to the cus-
tomer’s network .
In addition to connection to CameConnect for remote manage-
ment, the 001SDGWF accessory also allows the control unit to be
connected to a local network so that it can be managed by Came
TouchScreens and using the Came Domotic app on the same local
network.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40