Eaton C600M, Box 1, C899B001, C899B043, C899B093, C899B130, C899B137, C899B156, C899B168, C899B174 Instructions And Operation

  • Hello! I am an AI chatbot trained to assist you with the Eaton C600M Instructions And Operation. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Box 1 Non-Combination Enclosed Control and
C600M Cover Control Kit Wiring
General Information ................................................................... 2
Cover Control Installation .............................................................. 2
Starter/Contactor Wiring Diagrams ....................................................... 3
C600M Kit Wiring Instructions .......................................................... 4
Starter/Contactor Mounting Locations .................................................... 8
Enclosures without Starters or Contactors ................................................. 9
Reset Rod Kits ....................................................................... 9
Reset Rod Installation ................................................................ 10
Contents
Description
Page
Instructions and Operation P52899
Supersede February 2014
Effective May 2015
General Information
This publication is to be used for Eaton non-combination enclosures
designed to accept the M22 series 22mm cover control devices.
If the enclosure catalog number already has cover control devices
mounted, the existing reverse “c” shape bracket can be reused.
If the enclosure catalog number includes a blank rectangular cover,
remove it prior to installing the cover control kit (see instructions
below).
1. Remove rectangular blank cover by pushing on the blank
cover from the back side.
2. Discard blank cover .
Cover Control Installation
3. Using the included mounting screws, mount the C600M
cover control to the base of the enclosure in the holes desig-
nated by the arrows below.
4. Terminate the wires from the M22 operators onto the starter/
contactor as illustrated in “C600M Kit Wiring Instructions“
(see page 5).
2
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
Wiring Diagrams: FVNR NEMA and IEC Starters
and Contactors
Wiring Diagrams: FVR NEMA and IEC Starters
and Contactors
3
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
Wiring Diagrams: Lighting Electrically Held
ote:N source drawing reference wiring diagram 286979.
ote:N For kits with a green OFF light, an additional top added
NC auxiliary is needed to be supplied by the customer.
NC1 NC2
STOP/OFF
NO4
NO3
START/ON
2/13 3/14
R1
M
A2
A1
M
X2X1
RUN
R
1
2
96
95
OL
X2X1
OFF
G
1
2
T1
6261
M
T1
5453
M
9897
OL
1
2
4
3
1
2
1
2
WIRING FOR DC STARTERS ONLY
STOP/START OR OFF/ON OVAL. OPTIONS SHOWN: RUN LIGHT AND OFF LIGHT
BLK/REDBLK/RED
RED
RED
RED
RED
BLK/WHT
BLK/WHT
RED
RED
YEL
BLK
RED
(BLU IF DC)
RED
(BLU/WHT IF DC)
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR CONTROL POWER WIRING OPTIONS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
A1
M HOLD
A2
M PICKUP
X2X1
RUN
R
R1
M LATE OPENING
96
95
OL
9897
OL
BLU
RED
BLK/RED BLK/RED
BLU BLU
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX)
4
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
C600M Wiring Kit Diagrams
ote:N source drawing reference wiring diagram 286979. ote:N For kits with a green OFF light, an additional top added
NC auxiliary is needed to be supplied by the customer.
NO4
NO3
STOP/OFF START/ON
OX
2/13 3/14
R1
M
A2
A1
M
X2X1
RUN
R
1
2
96
95
OL
X2X1
OFF
G
1
2
T1
6261
M
9897
OL
1
2
1
2
1
2
BLK/RED
BLK/RED
RED
RED
RED
RED
BLK/WHT
BLK/WHT
RED
BLK
RED
(BLU IF DC)
RED
(BLU/WHT IF DC)
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR CONTROL POWER WIRING OPTIONS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
STOP/START OR OFF/ON 2-POSTION SELECTOR SWITCH
OPTIONS SHOWN: RUN LIGHT, AND OFF LIGHT
WIRING FOR DC STARTERS ONLY
A1
M HOLD
A2
M PICKUP
X2X1
RUN
R
R1
M LATE OPENING
96
95
OL
9897
OL
BLU
RED
BLK/RED BLK/RED
BLU BLU
T1
6261
M
T1
5453
M
4
3
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX)
BLK/RED
X2X1
OFF
G
1
2
1
2
RED
RED
BLK/WHT
BLK/WHT
T1
6261
M
X2X1
RUN
R
1
2
1
2
RED
RED
1
2
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR CONTROL POWER WIRING OPTIONS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
YEL
RED
(BLU/WHT IF DC)
RED
(BLU/WHT IF DC)
NO4 NO3
XOO
HAND/TEST 0 AUTO
NO4 NO3
OOX
A2
A1
M
96
95
OL
9897
OL
2/13 3/14
R1
M
REMOTE
SWITCH
HAND/OFF/AUTO OR TEST/OFF/AUTO 3-POSTION SELECTOR SWITCH
OPTIONS SHOWN: RUN LIGHT, AND OFF LIGHT
WIRING FOR DC STARTERS ONLY
A1
M HOLD
A2
M PICKUP
X2X1
RUN
R
R1
M LATE OPENING
96
95
OL
9897
OL
BLU
RED
BLK/RED BLK/RED
BLU BLU
T1
6261
M
T1
5453
M
4
3
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX)
5
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
ote:N source drawing reference wiring diagram 286979.
ote:N For kits with a green OFF light, an additional top added
NC auxiliary is needed to be supplied by the customer.
NC2
NC1
STOP/OFF
2/13 3/14
R1
M
A2
A1
M
X2X1
RUN
R
1
2
96
95
OL
X2X1
OFF
G
1
2
T1
6261
M
9897
OL
1
2
1
2
1
2
BLK/RED
BLK/RED
RED
RED
RED
RED
BLK/WHT
BLK/WHT
RED
BLK
RED
(BLU IF DC)
RED
(BLU/WHT IF DC)
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR CONTROL POWER WIRING OPTIONS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
4
NO4
NO3
START/ON
2/13 3/14
R1
M
BLK
4
YEL
WIRING FOR START/ON ONLY
START/ON OR STOP/OFF PUSHBUTTON
OPTIONS SHOWN: RUN LIGHT, AND OFF LIGHT
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
OPTION FOR START/ON OR STOP/OFF PB
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX)
WIRING FOR DC STARTERS ONLY
A1
M HOLD
A2
M PICKUP
X2X1
RUN
R
R1
M LATE OPENING
96
95
OL
9897
OL
BLU
RED
BLK/RED BLK/RED
BLU BLU
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
5
T1
6261
M
T1
5453
M
5
3
R
F
OLF
FWD/UP
0
REV/DWN
REDBLK
REV/OFF/FWD OR DWN/OFF/UP 3-POSITION SELECTOR SWITCH
OPTIONS SHOWN: REV/DWN LIGHT AND FWD/UP LIGHT
RED
(BLU IF DC)
RED
(BLU IF DC)
BLU
RED
RED
BLU
BLU
BLU
BLU
BLU/WHT
BLK/RED BLK/RED
BLK/RED BLK/RED
BLK/RED BLK/RED
BLK/RED
A2
R PICKUP
A2
F PICKUP
X2X1
REV/DWN
R
X2X1
FWD/UP
R
A1
R HOLD
9897
OL
9695
OL
A1
F HOLD
2
1
2
1
RED
RED
2
1
RED
2
1
X2X1
REV/DWN
R
X2X1
FWD/UP
R
NO4 NO3
XOO
NO4 NO3
OOX
3/14/542/13/53
L1
A2
A1
R
L1
_/21/617/22/62
F
5/14/544/13/53
R1
R
9897
OL
9695
A2
A1
R1
_/21/616/22/62
RED
(BLU IF DC)
RED
(BLU IF DC)
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
1
1
2
RED
2
WIRING FOR DC STARTERS ONLY
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
TWO 2NO TOP ADDER AUX INCLUDED FOR ALL COIL VOLTAGES.
WHEN COIL VOLTAGES 120V AND LESS, CONTROL WIRING ROUTED
TO NO. 63 TERMINAL FOR SEPARATE CONTROL.
1
2
3
T2
6463
R
6463
T1
F
T2
5453
R
5453
T1
F
3
L1
F LATE OPENING
BLK/RED
R1
R LATE OPENING
SEPARATE CONTROL WIRES
REFERENCE NOTES BELOW FOR CONTROL POWER WIRING OPTIONS
CONTROL POWER WIRING NOTES
CAUTION
SEPARATE CONTROL POWER
COMMON CONTROL POWER
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 63 OR NO. 61 TERMINAL PER DIAGRAM ON THE TOP ADDER AUX. AND TO THE NO.
96 TERMINAL ON THE OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 OR NO. 63 TERMINAL PER
DIAGRAM ON THE TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER
DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
6
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
ote:N source drawing reference wiring diagram 286979.
ote:N For kits with a green OFF light, an additional top added
NC auxiliary is needed to be supplied by the customer.
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
3
2
2
1
1
T1
6261
F
T2
6261
R
X2X1
OFF
G
1
2
1
2
RED REDRED BLK/WHT BLK/WHT
R1
_/21/616/22/62
R
A2
A1
F
9695
OL
9897
OL
5/14/544/13/53
R1
R
L1
_/21/617/22/62
F
A2
A1
R
CUSTOMER
CONTROL
CIRCUIT
3/14/542/13/53
L1
F
RED
RED
RED
A2A1
FWD/UP
R
A2A1
REV/DWN
R
BLK/RED BLK/RED
BLK/RED BLK/RED
REDRED
REDRED
1
2
1
2
1
2
1
2
RED
(BLU/WHT
IF DC)
RED
(BLU IF DC)
RED (BLU IF DC)
RED
(BLU IF DC)
REV/FWD OR DWN/UP CUSTOMER CONTROL
OPTIONS SHOWN: REV/DWN LIGHT AND FWD/UP LIGHT, OFF LIGHT
OPTION FOR RUN LIGHT (RED TYPICAL)
REQUIRED FOR 480V OPTION
TWO 2NO TOP ADDER AUX INCLUDED FOR ALL COIL VOLTAGES EXCEPT
WHEN OPTION FOR OFF LIGHT IS USED AND ONE 2NO TOP ADDER AUX
IS SWAPPED OUT FOR ONE 1NO-1NC.
1
2
3
4
OPTION FOR OFF LIGHT (GREEN TYPICAL) (INCLUDES 1NO-1NC AUX IN PLACE OF 2NO AUX IN POSITION T1)
BLU
BLU
BLU
BLU
BLU/WHT
BLK/RED BLK/RED
BLK/RED
A2
R PICKUP
A2
F PICKUP
X2X1
REV/DWN
R
X2X1
FWD/UP
R
A1
R HOLD
9897
OL
9695
OL
A1
F HOLD
WIRING FOR DC STARTERS ONLY
L1
F LATE OPENING
BLK/RED
R1
R LATE OPENING
T2
6463
R
6463
T1
F
T2
5453
R
5453
T1
F
4
CONTROL POWER WIRING NOTES
CAUTION
SEPARATE CONTROL POWER
COMMON CONTROL POWER
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 63 OR NO. 61 TERMINAL PER DIAGRAM ON THE TOP ADDER AUX. AND TO THE NO.
96 TERMINAL ON THE OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 OR NO. 63 TERMINAL PER
DIAGRAM ON THE TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER
DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
NOT INCLUDED FOR SEPARATE CONTROL COIL VOLTAGES 120V AND LESS
1/L1 OR SEPARATE CONTROL
3/L2 OR SEPARATE CONTROL
RED
RED
NC1 NC2
OFF
NO4
NO3
ON
2/13 3/14
R1
M1
A2
A1
M1
X2X1
RUN
R
1
2
X2X1
OFF
G
1
2
R1
6261
M1
1
2
1
2
BLK/RED
BLK/RED
REDRED
RED RED
BLK/WHT BLK/WHT
RED
RED YEL BLK
RED
(BLU IF
DC)
RED
(BLU/WHT IF DC)
A2
A1
M2
LIGHTING 2 CONTACTOR/COIL REF.: OFF/ON OVAL PUSHBUTTON
RUN LIGHT AND OFF LIGHT
T1
5453
M
1
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER!
THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR MULTIPLE CONTROL
MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
: CONNECT SEPARATE CONTROL LINES TO THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE NO. 96 TERMINAL ON THE
OVERLOAD RELAY.
: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE
"C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT SEPARATE CONTROL
LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM
AND TO THE NO. 96 TERMINAL ON THE OVERLOAD RELAY.
: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
SEPARATE CONTROL POWER
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
FOR COIL VOLTAGES 120V AND LESS
FOR COIL VOLTAGES GREATER THAN 120V
1NO-1NC TOP ADDER AUX INCLUDED FOR COIL VOLTAGES 120V AND
LESS FOR SEPARATE CONTROL. FOR HIGHER COIL VOLTAGES, 1/L1 IS
CONNECTED TO PILOT DEVICE TERMINAL FOR COMMON CONTROL
1
7
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
ote:N All indicated mounting holes represent contactor or starter top or top left mount-
ing location. Additional screws are required for full contactor or starter assembly.
ote:N Cover control bracket mounting holes are on the far right of the base.
ote:N Letters are not stamped in the box.
XT Top Location
Size B
Size C
2C
2B
Lighting Top Location
All Contactors 1
DP Top Location
A25/B25
A27/B27
14A
4A
NEMA Size Top Location
AN16AN
AN19AN
AN16BN
AN19BN
AN16DN
AN19DN
AN19GN
All Other
00
00
0
0
1
1
2
00-2
14B
14B
14B
14B
14A
14A
14A
1
Starter/Contactor Mounting Locations
Example: If you want to mount a AN16AN, you would put the top
hole in the 14B location.
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
EATON CORPORATION - CONFIDENTIAL AND PROPRIETARY
NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION
THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE
EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY EATON AT ANY TIME.
BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT
BE USED IN ANY MANNER A
DVERSE TO THE INTERESTS OF EATON AND THAT NO PORTION OF THIS DOCUMENT MAY BE
COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING
CONTRACTUAL PROVISIONS, THIS NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT.
C Eaton Corporation, All Rights Reserved
TITLE
DRAWING
NUMBER
SIZE
D
CHANGE RESPONSIBILITY
REVISION
CLASS CODE SHEETSCALE
OF
1 1
DATE (YYYY/MM/DD)
DRAFTER/DESIGNER
MANUFACTURING
REVISION DESCRIPTION
DIMENSIONS IN
UNLESS OTHERWISE SPECIFIED
DRAWING IN ACCORDANCE WITH
ASME Y14.5M-1994
ENG/MFG REFERENCE
X.XX+/-XX
ST
SYMBOLS PER
468-1143
J. UPHAUS
ENGINEERING APPROVED
ECO#
INCHES
X.X
X.XX
X.XXX
X°
X.X°
±0.1
±0.02
±0.005
±1°
±.5°
NA
N/A
2015/03/18
J. UPHAUS
N/A
N/A
N/A
N/A
P52899 HOLE PATTERN VIEW
N/A
N/A
2015
A
A
B
B
C
8
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
XT Top Location
Size B
Size C
2C
2B
Lighting Top Location
All Contactors 1
DP Top Location
A25/B25
A27/B27
14A
4A
NEMA Size Top Location
AN16AN
AN19AN
AN16BN
AN19BN
AN16DN
AN19DN
AN19GN
All Other
00
00
0
0
1
1
2
00-2
14B
14B
14B
14B
14A
14A
14A
1
Enclosures without Starters or Contactors
Rod Shaft
Length Catalog Number Starter Type Description
None C899B001 N/A Empty Box 1 Enclosure without reset (includes
blank cover on reset hole)
0.43 C899B043 ECN SSOL Size 00/0/1/2 Empty Box 1 Enclosure with 0.43 inch reset rod
length
0.93 C899B093 ECX SSOL Size B
ECX SSOL Size C
Empty Box 1 Enclosure with 0.93 inch reset rod
length
1.30 C899B130 ECX Fixed Overload Size C
A27/B27 Fixed Overload
Empty Box 1 Enclosure with 1.30 inch reset rod
length
1.37 C899B137
A27/B27_XTOB_40, 45 A
Empty Box 1 Enclosure with 1.37 inch reset rod
length
1.56 C899B156 A27/B27 Fixed Overload Empty Box 1 Enclosure with 1.56 inch reset rod
length
1.68 C899B168
ECN_C306 Size 00/0/1
A25/B25 C306
Empty Box 1 Enclosure with 1.68 inch reset rod
length
1.74 C899B174 ECX Fixed Overload Size B Empty Box 1 Enclosure with 1.74 inch reset rod
length
Reset Rod Lengths
Rod Shaft
Length Starter Type
0.43 to
1.74
For all starter types below
0.43 ECN SSOL Size 00/0/1/2
0.74 ECX SSOL Size B
ECX SSOL Size C
1.30 ECX Fixed Overload Size C
A27/B27 Fixed Overload
1.37 A27/B27_XTOB_40,45 A
1.56 A27/B27_XTOB_15, 25, 30 A
1.68
ECN_C306 Size 00/0/1
A25/B25 C306
1.74 ECX Fixed Overload Size B
9
Instructions and Operation P52899
Effective May 2015
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
EATON www.eaton.com
1. From the top of the box cover, insert the M22 button into the
box cover.
2. From the bottom of the cover, tighten the nut onto M22 but-
ton.
3. From the bottom of the cover, snap the shroud (if supplied)
cut to the appropriate length for the reset rod into the M22
button.
4. If the reset paddle is not already assembled to the required
reset rod (see Reset Rod Kit table), assemble as shown by
inserting reset rod into reset paddle.
5. From the bottom of the cover, snap the required reset rod
into M22 button. The flat side of the paddle should face
away from the box covers rectangular opening with the
“Up” arrow facing toward the top of the box.
Reset Rod Installation
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
EATON CORPORATION - CONFIDENTIAL AND PROPRIETARY
NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION
THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE
EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY EATON AT ANY TIME.
BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT
BE USED IN ANY MANNER A
DVERSE TO THE INTERESTS OF EATON AND THAT NO PORTION OF THIS DOCUMENT MAY BE
COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING
CONTRACTUAL PROVISIONS, THIS NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT.
C Eaton Corporation, All Rights Reserved
TITLE
DRAWING
NUMBER
SIZE
D
CHANGE RESPONSIBILITY
REVISION
CLASS CODE SHEETSCALE
OF
1 1
DATE (YYYY/MM/DD)
DRAFTER/DESIGNER
MANUFACTURING
REVISION DESCRIPTION
DIMENSIONS IN
UNLESS OTHERWISE SPECIFIED
DRAWING IN ACCORDANCE WITH
ASME Y14.5M-1994
ENG/MFG REFERENCE
X.XX+/-XX
ST
SYMBOLS PER
468-1143
J. UPHAUS
ENGINEERING APPROVED
ECO#
INCHES
X.X
X.XX
X.XXX
X°
X.X°
±0.1
±0.02
±0.005
±1°
±.5°
NA
N/A
2015/03/18
J. UPHAUS
N/A
N/A
N/A
N/A
P52899 RESET ASSEMBLY VIEW
N/A
NTS
2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2014 Eaton
All Rights Reserved
Publication No. P52899 / 002
May 2015
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Box 1 Non-Combination Enclosed Control
and C600M Cover Control Kit Wiring
Instructions and Operation P52899
Effective May 2015
/