Service Guide | Advanced Defrost AK-SC 255
© Danfoss | ADAP-KOOL® | 2018.08
6 | AX279033330245en-000101
NOTE:
1. Go to the defrost (or Man. defrost) state if the pump-out feature
is disabled.
2. Go to the dripdown state if the equalize phase is disabled.
3. Go to the dripdown state if manual defrost OFF is set, or if
the pump-out timer is timeout and if setup for some type of
defrost terminations and it's done in the pump-out period.
Termination
Any programmed termination temperatures and/or inputs will not
affect the pump-out time period. The pump-out period cannot be
stopped by defrost termination. Only a manual defrost override
can stop the pump-out phase, and then the drip down time will
start and finish as programmed. Don’t need to go through the
equalize phase because a defrost phase is not involved.
Any programmed termination temperatures and/or inputs will not
affect the Equalize time period. The equalize time period cannot
be stopped by defrost termination. If a defrost is stopped, the
equalize time will start and finish as programmed.
Manual Defrost
When a manual defrost is initiated and the pump-out feature is
activated, the pump-out period will occur as programmed. Only a
manual defrost override can stop the pump-out phase, and then
the drip down time will start and finish as programmed.
When a manual defrost is initiated and the pump-out feature
is activated, the Equalize period will occur as programmed. A
manual defrost cannot circumvent the programmed Equalize
period.
Fan Control
The evaporation fan is always ON during the pump-out period
and the evaporation fan’s operation during defrost is dependent
on its control setup. After the defrost period ends, the evaporation
fan will honor temperature and time restart parameters.
Added a question “Fan start sensor on …?” in the configure
circuit screen to handle the following fan control situations: The
defrost termination sensor setup 1:
The termination sensor type is selected as “Defrost sensor”, The
number case/box sensors is larger than 1,
The termination input for each case is “YES”. and the fan control
setup:
Fan control is “YES”,
Fan delay control is “YES”, Start fan on time is “NO”.
The defrost termination sensor setup 2:
The termination sensor type is not selected as “Defrost sensor”,
The number case/box sensors is larger than 1,
and the fan control setup:
Fan control is YES,
Fan delay control is YES, Start fan on time is NO.
The reason for this question is that the AK-SC255 needs to know
which of defrost sensors should be chosen to compare with the
fan start temperature set point because the number of defrost
sensors is larger than 1. The fan control algorithm should be
looking at the defrost sensors not the case sensors. For the
question “Fan start sensor on …?” we have the following choice:
All, Any, Average and Individual defrost sensor. The default is
set to Any.
A failsafe timer is added for restarting the fan on temperature
in case the defrost sensors may be failed. The default time is 5
minutes.
NOTE (related to the fan control):
(1). “Stop fan on high temperature” is based on the Circuit or Case
temperature sensor(s).
(2). “Start fan on temperature” (i.e. “Start fan on time…?” is set to
NO) is based on the Defrost sensor(s).
(3). The defrost termination could be based on temperature or
inputs. If it is based on the temperature, the defrost sensor(s)
should be chosen to decide the termination.
(4). Refresh the question “Start fan on time....?” after changed the
following each setup:
a). “Num case/box sensors ….?”
b). “Termination type ….?”
c). “Term input for each case?”