Carrier AQUAFORCE 30XA080-500 User manual

Type
User manual

This manual is also suitable for

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300026-01 Printed in U.S.A. Form 30XA-10SI Pg 1 11-09 Replaces: 30XA-5SI
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-78
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 1
Step 2 — Place, Mount and Rig Unit. . . . . . . . . . . . . 2
•PLACING UNIT
MOUNTING UNIT
RIGGING UNIT
Step 3 — Cooler Fluid and Drain Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
GENERAL
UNITS WITH A HYDRONIC PUMP PACKAGE
UNITS WITHOUT A HYDRONIC PUMP PACKAGE
DUAL CHILLER CONTROL
COOLER PUMP CONTROL
BRINE UNITS
PREPARATION FOR YEAR-ROUND OPERATION
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . . . 56
WATER SYSTEM CLEANING
WATER TREATMENT
SYSTEM PRESSURIZATION
FILLING THE SYSTEM
SET WATER FLOW RATE
PUMP MODIFICATION/TRIMMING
FREEZE PROTECTION
PREPARATION FOR WINTER SHUTDOWN
Step 5 — Make Electrical Connections . . . . . . . . . . 62
POWER SUPPLY
FIELD POWER CONNECTIONS
•POWER WIRING
FIELD CONTROL POWER CONNECTIONS
CARRIER COMFORT NETWORK®
COMMUNICATION BUS WIRING
NON-CCN COMMUNICATION WIRING
FIELD CONTROL OPTION WIRING
DUAL CHILLER LEAVING WATER SENSOR
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . . . 77
ENERGY MANAGEMENT MODULE
REMOTE ENHANCED DISPLAY
LOW AMBIENT TEMPERATURE OPERATION
MINIMUM LOAD ACCESSORY
UNIT SECURITY/PROTECTION ACCESSORIES
COMMUNICATION ACCESSORIES
SERVICE OPTIONS
CONTROL TRANSFORMER
Step 7 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . . . . . . 77
Step 8 — Refrigerant Charging. . . . . . . . . . . . . . . . . . 77
DEHYDRATION
REFRIGERANT CHARGE
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location. Only trained, qualified installers and service
mechanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the
literature, and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky equipment.
INTRODUCTION
These instructions cover installation of 30XA080-500 air-
cooled liquid chillers with electronic controls and units with
factory-installed options (FIOPs). See Fig. 1.
INSTALLATION
Storage —
If the unit is to be stored for a period of time be-
fore installation or start-up, be sure to protect the machine
from construction dirt. Keep protective shipping covers in
place until the machine is ready for installation.
Step 1 — Inspect Shipment — Inspect unit for dam-
age upon arrival. If damage is found, immediately file a claim
with the shipping company, and contact your local Carrier
representative.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
IMPORTANT: This equipment generates, uses, and
can radiate radio frequency energy and if not installed
and used in accordance with these instructions may
cause radio interference. It has been tested and found
to comply with the limits of a Class A computing
device as defined by FCC (Federal Communications
Commission, U.S.A.) regulations, Subpart J of Part 15,
which are designed to provide reasonable protection
against such interference when operated in a commer-
cial environment.
AQUAFORCE
®
30XA080-500
Air-Cooled Liquid Chillers
2
Step 2 — Place, Mount, and Rig the Unit —
When considering a location for the unit, be sure to consult
NEC (National Electrical Code, U.S.A.) and/or local code
requirements. Allow sufficient space for airflow, wiring, pip-
ing, and service. See Fig. 2-14.
NOTE: To facilitate refrigerant vent piping, all units have fus-
ible plugs with
1
/
4
in. SAE (Society of Automotive Engineers)
flares and pressure reliefs with
3
/
4
in. NPT fittings (if required
by local codes).
PLACING UNIT Locate the unit so that the condenser
airflow is unrestricted both above and on the sides of the unit.
Airflow and service clearances are 6 ft (1.8 m) around the unit.
Acceptable clearance on the sides or ends without control boxes
can be reduced to 3 ft (1 m) without sacrificing performance as
long as the remaining three sides are unrestricted. Acceptable
clearance on the side with a control box can be reduced to 4 ft
(1.3 m) due to NEC regulations, without sacrificing performance
as long as the remaining three sides are unrestricted. Provide am-
ple room for servicing and removing the cooler. See Fig. 2-14 for
required clearances. Local codes for clearances take precedence
over the manufacturers recommendations when local codes call
for greater clearances.
If multiple units are installed at the same site, a separation of
10 ft (3 m) between the sides of the machines is required to
maintain proper airflow and minimize the chances of condens-
er air recirculation.
MOUNTING UNIT The unit may be mounted on a level
pad directly on the base rails, on a raised mounting rail around
the unit, or on vibration isolation springs. For all units, ensure
placement area is strong enough to support unit operating
weight. See Tables 1A and 1B. Mounting holes are provided
for securing the unit to the pad, mounting rail or vibration
isolation springs. Bolt the unit securely to pad or rails. If vibra-
tion isolators (field-supplied) are required for a particular
installation, refer to unit weight distribution in Fig. 15A-15C to
aid in the proper selection of isolators. The 30XA units can be
mounted directly on spring isolators. Once installed, the unit
must be level to within
1
/
8
-in. per ft (1 cm per meter) along the
long axis of the oil separator. This is required for oil return to
the compressor(s).
3
Fig. 1 — AquaForce
®
Chiller Model Number Designation
a30-4401
LEGEND
CFSP Coil Face Shipping Protection
EMM Energy Management Module
LON Local Operating Network
MCHX Microchannel Heat Exchanger
XL Across-the-Line Starter
30XA – AquaForce® Air-Cooled Chiller
Design Series
Unit Sizes
080 140 240 350
090 160 260 400
100 180 280 450
110 200 300 500
120 220 325
Voltage
1 – 575-3-60
2 380-3-60
4 – 230-3-60
6 – 460-3-60
7 – 200-3-60
Condenser Coil/Ambient/Low Sound Options
-Aluminum Fin/Copper Tube, High Ambient Temperature
0 – Copper Fin/Copper Tube, High Ambient Temperature
1Aluminum Pre-Coat Fin/Copper Tube, High Ambient Temperature
2Aluminum E-Co
at Fin/Copper Tube, High Ambient Temperature
3Copper E-Coat Fin/Copper Tube, High Ambient Temperature
4Novation® Heat Exchanger (MCHX), High Ambient
Temperature
5MCHX E-Coat, High Ambient Temperature
6Aluminum Fin/Copper Tube, High Ambient Temperature,
Low Sound
7 – Copper Fin/Copper Tube, High Ambient Temperature, Low Sound
8Aluminum Pre-Coat Fin/Copper Tube, High Ambient Temperature,
Low Sound
9 – Aluminum E-Coat Fin/Copper Tube, High Ambient Temperature,
Low Sound
BCopper E-Coat Fin/Copper Tube, High Ambient Temperature,
Low Sound
C MCHX, High Ambient Temperature, Low Sound
DMCHX E-Coat, High Ambient Temperature, Low Sound
FAluminum Fin/Copper Tube, Standard Ambient Temperature,
Low Sound
G Copper Fin/Copper Tube, Standard Ambient Temperature,
Low Sound
HAluminum Pre-Coat Fin/Copper Tube, Standard Ambient
Temper
ature, Low Sound
JAluminum E-Coated Fin/Copper Tube, Standard Ambient
Temperature, Low Sound
KCopper E-Coat Fin/Copper Tube, Standard Ambient Temperature,
Low Sound
LMCHX, Standard Ambient Temperature, Low Sound
MMCHX E-Coat, Standard Ambient Temperature, Low Sound
NAluminum Fin/Copper Tube, Standa
rd Ambient Temperature
P Copper Fin/Copper Tube, Standard Ambient Temperature
QAluminum Pre-Coat Fin/Copper Tube, Standard Ambient
Temperature
RAluminum E-Coat Fin/Copper Tube, Standard Ambient
Temperature
SCopper E-Coat Fin/Copper Tube, Standard Ambient Temperature
TMCHX, Standard Ambient Temperature
VMCHX E-Coat, Standard Ambient Temperat
ure
Cooler/Brine Options
0Integral Cooler with Heater
3Integral Cooler with Heater, Minus One Pass
5Integral Cooler with Heater, Plus One Pass
7Integral Cooler with Heater, Full End Screen
H – Integral Cooler with Heater, Plus One Pass, Brine
K – Integral Cooler with Heater, Minus One Pass, Full End Screen
MIntegral Cooler with Heater, Plus One Pass, Full End Screen
VIntegral Cooler with Heater, Plus One Pass, Brine, Full End Screen
Packaging/Security Options
0Coil Fa
ce Shipping Protection (CFSP), Skid
1CFSP, Skid, Top Crate, Bag
3CFSP, Coil Trim Panels
4CFSP, Skid, Coil Trim Panels
5CFSP, Skid, Top Crate, Bag, Coil Trim Panels
7CFSP, Coil Trim Panels, Upper and Lower Grilles
8CFSP, Skid, Coil Trim Panels, Upper and Lower Grilles
9CFSP, Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles
C – CFSP, Trim Panels, Upper and Lower Grilles, Upper Hail G
uards
D – CFSP, Skid, Coil Trim Panels, Upper and Lower Grilles, Upper Hail Guards
FCFSP, Skid, Top Crate, Bag, Trim Panels, Upper and Lower Grilles,
Upper Hail Guards
LCFSP
Controls/Communication Options
-Navigator™ Display
0Navigator Display, EMM
1Navigator Display, Service Option
2Navigator Display, EMM, Service Option
3Tou
ch Pilot™ Display
4Touch Pilot Display, EMM
5Touch Pilot Display, Service Option
6Touch Pilot Display, EMM, Service Option
7Navigator Display, BACnet Translator
8Navigator Display, BACnet Translator, EMM
9Navigator Display, BACnet Translator, Service Option
BNavigator Display, BACnet Translator, EMM, Service Option
CTouch Pilot Display, BACnet Translator
DTouch Pilot Display, BACnet Translator, EMM
FTouch Pilot Display, BACnet Translator, Service Option
GTouch Pilot Display, BACnet Translator, EMM, Service Option
HNavigator Display, LON Translator
JNavigator Display, LON Translator, EMM
K – Navigator Displa
y, LON Translator, Service Option
LNavigator Display, LON Translator, EMM, Service Option
MTouch Pilot Display, LON Translator
NTouch Pilot Display, LON Translator, EMM
PTouch Pilot Display, LON Translator, Service Option
QTouch Pilot Display, LON Translator, EMM, Service Option
Electrical Options
-Single Point Power, XL, Terminal Block, No Control Transformer
0
Single Point Power, Wye-Delta, Terminal Block, No Control Transformer
3Dual Point Power, XL, Terminal Block, No Control Transformer
4 – Dual Point Power, Wye-Delta, Terminal Block, No Control Transformer
7 Single Point Power, XL, Disconnect, No Control Transformer
8Single Point Power, Wye-Delta, Disconnect, No Control Transformer
C – Dual Point Power, XL, Disconnect, No Control Transformer
D – Dual Point Power, Wye-Delta, Disconnect, No Control Transformer
HSingle Point Power, XL, Terminal Block, Control Transformer
JSingle Point Power, Wye-Delta, Terminal Block, Control Transformer
MDua
l Point Power, XL, Terminal Block, Control Transformer
N – Dual Point Power, Wye-Delta, Terminal Block, Control Transformer
RSingle Point Power, XL, Disconnect, Control Transformer
S Single Point Power, Wye-Delta, Disconnect, Control Transformer
W Dual Point Power, XL, Disconnect, Control Transformer
XDual Point Power, Wye-Delta, Disconnect, Control Transformer
Refrigeration Circuit Options
- None
0 Suction Line Insulation
1 Suction Service Valves
2 Low Ambient Temperature Head Pressure Control
3 Su
ction Line Insulation, Suction Service Valves
4 Suction Line Insulation, Low Ambient Temperature Head Pressure Control
5 Suction Service Valves, Low Ambient Temperature Head Pressure Control
6 Suction Line Insulation, Suction Service Valves, Low Ambient Temperature
Head Pressure Control
7 – Minimum Load Control
8 Suction Line Insulation, Minimum Load Control
9 Suction Service Valves, Minimu
m Load Control
B Low Ambient Temperature Head Pressure Control, Minimum Load Control
C Suction Line Insulation, Suction Service Valves, Minimum Load Control
D Suction Line Insulation, Low Ambient Temperature Head Pressure
Control, Minimum Load Control
F Suction Service Valves, Low Ambient Temperature Head Pressure
Control, Minimum Load Control
G Suction Line Insulation, Suction Service Valves, Low Ambient Temperature
Head Pressure Control, Minimum Load Control
Hydronic Pump Package Options
- – None
1 Single Pump, 5 HP
2 Single Pump, 7.5 HP
3 Single Pump, 10 HP
4 Single Pump, 15 HP
7 Dual Pump, 5 HP
8 Dual Pump, 7.5 HP
B Dual Pump, 10 HP
C Dual Pump, 15 HP
Quality Assurance
Certified to ISO 9001:2000
4
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
[1114]
[1729]
[2236]
[508]
[1670]
[3587]
[3078]
[148]
[2769]
[80]
[863]
Fig. 2 — 30XA080 Air-Cooled Liquid Chiller Dimensions
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid surface.
2. Temperature relief devices are located on liquid line and econo-
mizer assemblies and have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in each cooler head at each
end of cooler.
4. Drawing depicts unit with single point power and standard two-
pass cooler. Refer to the Packaged Chiller Builder program for
other configurations.
5. Dimensions are shown in inches. Dimensions in [ ] are in
millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for condenser coil removal.
a30-4402
TOP VIEW
5
5" Victaulic Entering Water
5" Victaulic Leaving Water
90.55
[2300]
19.06
[484]
10.8
[274]
88.04
[2236]
68.06
[1729]
[1223]
[147]
[2300]
[1199]
[564]
[2236]
[863]
[874]
[531]
[564]
[881]
8.8
[224]
3/4 NPT Relief
Conn. Female
5" Victaulic
Entering Water
5" Victaulic
Leaving Water
Cooler Vent
3/8 NPT
Cooler Drain
3/8 NPT
Mounting Holes
Rigging Holes
(See Detail A)
Control Box All Voltages
90.55
[2300]
19.06
[484]
10.8
[274]
141.22
[3587]
121.17
[3078]
109.03
[2769]
16.1
[409]
3.15
[80]
a30-4403
LEFT END VIEW
RIGHT END VIEW
FRONT VIEW
Fig. 2 — 30XA080 Air-Cooled Liquid Chiller Dimensions (cont)
6
A
[1475]
[1729]
[2236]
[913]
[508]
[1270]
[4780]
[3070]
B
[140]
[2769]
[80]
[863]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid surface.
2. Temperature relief devices are located on liquid line and economizer assem-
blies and have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in each cooler head at each end of cooler.
4. Drawing depicts unit with single-point power and standard two-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches. Dimensions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for condenser coil removal.
30XA UNIT A B
090 44.11 [1120] 86.93 [2208]
100 44.11 [1120] 87.22 [2215]
110 44.11 [1120] 87.62 [2226]
120 44.11 [1120] 87.12 [2213]
a30-4404
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
TOP VIEW
Fig. 3 — 30XA090-120 Air-Cooled Liquid Chiller without Pump Dimensions
7
[2300]
[1729]
[2236]
[274]
[484]
[2300]
[1199]
[564]
[2236]
[874]
[863]
[531]
[564]
[881]
[147]
[1223]
[2300]
[484]
[274]
[1982]
[4780]
[1982]
[3070]
[80]
[564]
[409]
8.8
[224]
a30-4405
RIGHT END VIEWLEFT END VIEW
FRONT VIEW
Fig. 3 — 30XA090-120 Air-Cooled Liquid Chiller without Pump Dimensions (cont)
8
A
[2032]
[2173]
[2236]
[2242]
[356]
[1270]
[4780]
[4002]
[3422]
B
[3048]
[2769]
[80]
[863]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid surface.
2. Temperature relief devices are located on liquid line and economizer assem-
blies and have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in each cooler head at each end of cooler.
4. Drawing depicts unit with single-point power and standard two-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches. Dimensions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for condenser coil removal.
30XA UNIT A B
090 44.11 [1120] 86.93 [2208]
100 44.11 [1120] 87.22 [2215]
110 44.11 [1120] 87.62 [2226]
120 44.11 [1120] 87.12 [2213]
a30-4404
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
TOP VIEW
Fig. 4 — 30XA090-120 Air-Cooled Liquid Chiller with Pump Dimensions
9
90.55
[2300]
19.06
[484]
10.27
[261]
88.04
[2236]
88.28
[2242]
85.56
[2173]
5" Victaulic Leaving Water
5" Victaulic Entering Water
[147]
[1223]
[881]
[564]
[531]
[863]
[874]
[2173]
[2236]
[2242]
[261]
[484]
[564]
[1199]
[2300]
3/4 NPT Relief Conn. Female
Cooler Vent
3/8 NPT
Cooler Drain
3/8 NPT
Mounting Holes
Rigging Holes
(See Detail A)
Control Box All Voltages
90.55
[2300]
19.06
[484]
10.27
[261]
188.2
[4780]
157.54
[4002]
78.02
[1982]
78.02
[1982]
16.1
[409]
8.8
[224]
134.73
[3422]
5" Victaulic Entering Water
5" Victaulic Leaving Water
Drain
in
a30-4405
LEFT END VIEW
RIGHT END VIEW
FRONT VIEW
Fig. 4 — 30XA090-120 Air-Cooled Liquid Chiller with Pump Dimensions (cont)
10
[2410]
[1872]
[162]
[397]
[148]
[2769]
[508]
B
[3086]
[3810]
[5975]
[508]
[885]
[2236]
[1756]
[1502]
A
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid
surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts unit with single-point
power, standard two-pass cooler, and
nominal voltage range of 380 to 575 v.
Refer to the Packaged Chiller Builder pro-
gram for other configurations.
5. Dimensions are shown in inches. Dimen-
sions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for
condenser coil removal.
30XA UNIT A B
140 44.63 [1134] 115.88 [2943]
160 44.61 [1133] 115.64 [2937]
a30-4404
TOP VIEW
FRONT VIEW
LEFT END VIEW
[2300]
[2236]
[748]
[208]
[162]
[397]
Fig. 5 — 30XA140,160 Air-Cooled Liquid Chiller without Pump Dimensions
11
[132]
[1500]
[5975]
[1872]
[2409]
[2410]
[2833]
[2300]
[748]
[614]
[532]
[208]
[2300]
[748]
[208]
[162]
[397]
[1756]
[2236]
[541]
[269]
a30-4407
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
BACK VIEW
RIGHT END VIEW
Fig. 5 — 30XA140,160 Air-Cooled Liquid Chiller without Pump Dimensions (cont)
12
[748]
[208]
[162]
[397]
[2236]
[2270]
[541]
[2300]
A
[2032]
[2174]
[2236]
[2270]
[356]
[1270]
[2769]
[397]
[162]
[1872]
[2410]
[5975]
[4162]
[3431]
[3048]
B
3/4 NPT Relief Conn. Female
5" Victaulic Entering
5" Victaulic Leaving Water
Water
Cooler Drain
3/8 NPT
Cooler Vent
3/8 NPT
Mounting Holes
Rigging Holes
(See Detail A)
Control Box
incoming power
supply (200,230v)
90.55
[2300]
22.02
[559]
235.24
[5975]
121.49
[3086]
109.03
[2769]
58.08
[1475]
33.96
[863]
16.1
[409]
8.8
[224]
7.2
[182]
2.8 [72]
21.28
[541]
135.03
[3431]
163.87
[4162]
in
out
Drain
a30-4407
TOP VIEW
FRONT VIEW
LEFT END VIEW
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid
surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts unit with single-point
power, standard two-pass cooler, and
nominal voltage range of 380 to 575 v.
Refer to the Packaged Chiller Builder pro-
gram for other configurations.
5. Dimensions are shown in inches. Dimen-
sions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for
condenser coil removal.
30XA UNIT A B
140 44.63 [1134] 115.88 [2943]
160 44.61 [1133] 115.64 [2937]
Fig. 6 — 30XA140,160 Air-Cooled Liquid Chiller with Pump Dimensions
13
[559]
[541]
[2174]
[2236]
[2270]
[162]
[397]
[208]
[748]
[2300]
a30-4407
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
BACK VIEW
RIGHT END VIEW
[132]
[1500]
[5975]
[1872]
[2409]
[2410]
[2833]
[2300]
[748]
[614]
[532]
[208]
Fig. 6 — 30XA140,160 Air-Cooled Liquid Chiller with Pump Dimensions (cont)
14
[459]
[1475]
[863]
[1982]
[4502]
[7168]
[1982]
[287]
[571]
[2300]
[1555]
[2769]
B
[4502]
[7168]
[914]
[508]
[860]
[162]
A
[1528]
[1782]
[2236]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid
surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts unit with single point
power, standard two-pass cooler, and a
nominal voltage range of 380 to 575 v.
Refer to the Packaged Chiller Builder pro-
gram for other configurations.
5. Dimensions are shown in inches. Dimen-
sions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for
condenser coil removal.
30XA UNIT A B
180 46.12 [1171] 143.04 [3633]
200 46.15 [1172] 142.97 [3631]
a30-4408
TOP VIEW
FRONT VIEW
LEFT END VIEW
[2300]
[2236]
[748]
[208]
[162]
[397]
Fig. 7 — 30XA180,200 Air-Cooled Liquid Chiller Dimensions
15
[2300]
[748]
[208]
[162]
[397]
[1782]
[2236]
[287]
[571]
[2300]
[748]
[532]
[208]
[1500]
[3013]
[3551]
[3552]
[3975]
[7168]
[132]
[614]
a30-4174
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
BACK VIEW
RIGHT END VIEW
Fig. 7 — 30XA180,200 Air-Cooled Liquid Chiller Dimensions (cont)
16
3/4 NPT Relief Conn. Female
6" Victaulic Entering Water
6" Victaulic Leaving Water
Cooler Vent
3/8 NPT
Cooler Drain
3/8 NPT
Mounting Holes
Rigging Holes
(See Detail A)
90.55
[2300]
22.48
[571]
11.3
[287]
329.26 [8363]
224.65 [5706]
109.03 [2769]58.08 [1475]
58.08 [1475]
33.97 [863]
33.96 [863]
18.07
[459]
[162]
[397]
A
[1528]
[1782]
[2236]
[508]
[860]
[508]
[4799]
[4260]
[8363]
[6147]
[5706]
B
[2758]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid
surface.
2. Temperature relief devices are located on liq-
uid line and economizer assemblies and have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with single point power,
standard two-pass cooler and nominal voltage
range of 380 to 575 v. Refer to the Packaged
Chiller Builder program for other configura-
tions.
5. Dimensions are shown in inches. Dimensions
in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for con-
denser coil removal.
30XA UNIT A B
220 46.17 [1173] 171.42 [4354]
240 46.23 [1174] 170.83 [4339]
a30-4409
TOP VIEW
LEFT END VIEW
FRONT VIEW
[2300]
[2236]
[748]
[208]
[162]
[397]
Fig. 8 — 30XA220,240 Air-Cooled Liquid Chiller Dimensions
17
[1500]
[748]
[614] [532]
[208] [132]
[2300]
[4260]
[4798]
[4799]
[5221]
[8363]
a30-4176
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
BACK VIEW
RIGHT END VIEW
[2300]
[748]
[208]
[162]
[397]
[1782]
[2236]
[287]
[571]
Fig. 8 — 30XA220,240 Air-Cooled Liquid Chiller Dimensions (cont)
18
3/4 NPT Relief Conn. Female
8" Victaulic Entering Water
8" Victaulic Leaving WaterCooler Vent
3/8 NPT
Cooler Drain
3/8 NPT
Mounting Holes
Rigging Holes
(See Detail A)
90.55
[2300]
23.63
[600]
12.21
[310]
376.2 [9555]
304.71 [7740]
78.02 [1982]
78.02 [1982]
78.02 [1982]78.02 [1982]
31.96 [812]
16.1
[409]
[162]
[317]
A
[1805]
[2236]
[508]
[9555]
[7740]
B
[4784]
[5011]
[5747]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from
solid surface.
2. Temperature relief devices are located
on liquid line and economizer assem-
blies and have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in
each cooler head at each end of
cooler.
4. Drawing depicts unit with single point
power and standard two-pass cooler.
Refer to the Packaged Chiller Builder
program for other configurations.
5. Dimensions are shown in inches.
Dimensions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit
for condenser coil removal.
30XA UNIT A B
260 44.22 [1123] 216.16 [5490]
280 44.30 [1125] 215.86 [5483]
300 44.32 [1126] 216.18 [5491]
a30-4177
TOP VIEW
LEFT END VIEW
FRONT VIEW
[2300]
[2236]
[748]
[208]
[162]
[397]
Fig. 9 — 30XA260-300 Air-Cooled Liquid Chiller Dimensions
19
[722]
[614]
[532]
[208] [132]
[1900]
[9555]
[6184]
[5760]
[5747]
[5011]
[2300]
[2300]
[722]
[208]
[317]
[162]
[1805]
[2236]
[600]
[310]
a30-4178
3.93
7.88
[200]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
[100]
MOUNTING HOLE
0.875 DIA.[22.2]
MOUNTING
PLATE
1.50 DIA. [38.1]
RIGGING HOLE
[127]
5.0
[33]
1.31
1.75
[44]
BACK VIEW
RIGHT END VIEW
Fig. 9 — 30XA260-300 Air-Cooled Liquid Chiller Dimensions (cont)
20
3/4 NPT Relief Conn. Female
8" Victaulic Entering Water
8" Victaulic Leaving Water
Cooler Vent
3/8 NPT
Cooler Drain
3/8 NPT
Mounting Holes
Rigging Holes
(See Detail A)
90.55
[2300]
23.63
[600]
12.21
[310]
423.24
[10750]
349.02
[8865]
109.03
[2769]
78.02
[1982]
78.02
[1982]
58.08 [1475]
33.97
[863]
33.96
[863]
16.1
[409]
FRONT VIEW
[162]
[317]
A
[1805]
[2236]
[508]
[10750]
[8865]
B
[5910]
[6205]
[6941]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict
Sides and Ends — 6 ft (1.8 m) from solid
surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have
1
/
4
-in. flare connection.
3.
3
/
8
-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with single point power
and standard two-pass cooler. Refer to the
Packaged Chiller Builder program for other
configurations.
5. Dimensions are shown in inches. Dimen-
sions in [ ] are in millimeters.
6. Allow 8 ft (2.4 m) on either side of unit for
condenser coil removal.
30XA UNIT A B
325 42.92 [1090] 246.16 [6252]
350 42.92 [1090] 246.72 [6267]
TOP VIEW
FRONT VIEW
LEFT END VIEW
[2300]
[2236]
[748]
[208]
[162]
[397]
Fig. 10 — 30XA325,350 Air-Cooled Liquid Chiller Dimensions
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80

Carrier AQUAFORCE 30XA080-500 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI