VKOM fans are easy to install. The fans are supplied with fastening
brackets and can be installed both vertically and horizontally. The
fans can be wired through a wall switch in the room or with an
optional control that corresponds to power and current of the
fan.
External rotor motor on ball bearing with thermal protection
ensures long life of the fans.
Fan’s body is made of steel with polymeric coating, while the
impeller is made of aluminum.
Specially designed for mounting inside ventilation shaft, VKOM
fans are the perfect air movers. High outflow capacity allows
ventilating premises with contaminated air.
These fans can effectively and quietly handle major ventilation
challenges such as large warehouses without taking up valuable
space.
Motor
Housing
Mounting
Installation example
AXIAL FANS
Tel: 888-640-0925
513-348-3853
Fax: 513-268-4597
VentsUS.com
11013 Kenwood Road,
Cincinnati, Ohio 45242
Model Measurements [in.]
Ø DL K
VKOM 150
6
5/16
”8
11/16
”1
9/16
VKOM 200
8
1/8
”8
11/16
”1
9/16
Model Measurements [in.,]
Ø D Ø D1 H H1
RМ 148/158
5
13/16
”6
1/4
”5
1/2
”2
3/16
RМ 198/204
7
13/16
”8
1/16
”5
1/2
”2
3/16
Dimensions
Dimensions
Performance
Specification
Voltage: 120 V, 60 Hz
Motor: Single-phase asynchronous motor
Duct compatibility: Ø 6”, 8”
Airflow capacity: up to 262 CFM
Sones: 1.6 – 5.1
Power consumption: 28 – 109 W
Suitable for working airstreams up to 32-104 °F
IPX4 protection
Thermal overload protection
Five year warranty
Reducer RM for VKOM series fan
Flow Chart Graphs can be viewed at www.VentsUS.com
K
2013/03
Contacts
Tel: 888-640-0925
513-348-3853
Fax: 513-268-4597
VentsUS.com
11013 Kenwood Road, Cincinnati, Ohio 45242
VENTS-US reserves the rights to modify any of its products features, designs, components,
and specifications at any time and without notice to maintain the development and
quality of manufactured goods.
Model
RPM
Sones
Duct dia
Max Watts
Max Amps
CFM vs. Static Pressure (Ps) in
WG
Max. Ps
Volts
0” 0.125” 0.25” 0.375”
VKOM 150
1650 1.6 6” 28 0.41
115
61 - - 0.22 115
VKOM 200
1680
2.5 8” 43
0,63
262 211 56 - 0.30
115
  • Page 1 1