14
VKP/VKPI/VKPS/VKPF/VKPFI
www.ventilation-system.com
CONNECTION TO POWER MAINS
DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED
ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.
Depending on the fan type it is rated for connection either to single-phase AC 230 V/50/60 Hz or three-phase AC 380-400 V/50/60 Hz
power mains.
The connection must be made using durable, insulated and heat-resistant conductors (cables, wires).
The external lead-in must be equipped with a circuit breaker built into the stationary wiring to disconnect all the mains phases.
The QF external circuit breaker location must ensure free access for quick shutdown of the fan.
The trip current must be in compliance with current consumption.
The recommended rated current of the circuit beaker and the conductor cross section for various types of fans are shown in the table.
The given conductor cross sections are for reference only.
The actual conductor cross–section selection must be based on its type, the maximum permissible heating, insulation, length and
installation method (in the air, pipes or inside walls).
The recommended type of circuit breakers is D.
The recommended circuit breaker rated current and conductor cross section
Model Rated current of
the circuit breaker
Recommended
cable, n x S, where
n is the number
of wires, and S is
the cross section
in mm2
VKP, VKPI 2E 400*200 3 3 x 0.75
VKP, VKPI 2E 500*250 6 3 x 0.75
VKP, VKPI 4E 500*300 2 3 x 0.75
VKP, VKPI 4D 500*300 2 5 x 0.75
VKP, VKPI 4E 600*300 4 5 x 0.75
VKP, VKPI 4D 600*300 2 5 x 0.75
VKP, VKPI 4E 600*350 10 3 x 1.5
VKP, VKPI 4D 600*350 (400 Δ) 4 5 x 0.75
VKP, VKPI 4D 600*350 (400 Y) 3 5 x 0.75
VKP 4D 1000*500 25 5 x 1.5
VKP 6D 1000*500 10 5 x 0.75
VKPS 4E 600*350 10 3 x 0.75
VKP 4D 700*400 6 5 x 0.75
VKP 4D 800*500 10 5 x 0.75
VKPF, VKPFI 4E 400*200 4 3 x 0.75
VKPF, VKPFI 4D 400*200 2 5 x 0.75
VKPF, VKPFI 4E 500*250 10 3 x 0.75
VKPF, VKPFI 4D 500*250 3 5 x 0.75
VKPF, VKPFI 4E 500*300 10 3 x 0.75
VKPF, VKPFI 4D 500*300 6 5 x 0.75
VKPF, VKPFI 4E 600*300 20 3x1
Model Rated current of
the circuit breaker
Recommended
cable, n x S, where
n is the number
of wires, and S is
the cross section
in mm2
VKPF, VKPFI 4D 600*300 10 5x0.75
VKPF, VKPFI 4E 600*350 40 3x1.5
VKPF, VKPFI 4D 600*350 16 5x0.75
VKPF, VKPFI 4D 700*400 20 5x1
VKPF, VKPFI 4D 800*500 32 5 x 1.5
VKPF, VKPFI 6E 500*250 4 3x0.75
VKPF, VKPFI 6D 500*250 2 5x0.75
VKPF, VKPFI 6E 500*300 6 3x0.75
VKPF, VKPFI 6D 500*300 3 5x0.75
VKPF, VKPFI 6E 600*300 10 3x0.75
VKPF, VKPFI 6D 600*300 3 5x0.75
VKPF, VKPFI 6E 600*350 16 3x0.75
VKPF, VKPFI 6D 600*350 6 5x0.75
VKPF, VKPFI 6D 700*400 10 5x0.75
VKPF, VKPFI 6D 800*500 20 5x1
VKPF, VKPFI 6D 900*500 25 5x1
VKPF, VKPFI 6D 1000*500 25 5x1
VKPF, VKPFI 8D 800*500 16 5x0.75
VKPF, VKPFI 8D 900*500 16 5x0.75
VKPF, VKPFI 8D 1000*500 16 5x0.75