Regency PG36LPG4-R, PG36, PG36LPG5-R, PG36NG4-R, PG36NG5-R Owner's Installation Manual

  • Hello! I am an AI chatbot trained to assist you with the Regency PG36LPG4-R Owner's Installation Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Models: PG36NG5-R
PG36LPG5-R
Owners &
Installation
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Manual
09/11/12
LISTINGS AND CODE APPROVALS
These gas appliances have been tested in
accordance with AS4553, NZS 5262 and
have been certifi ed by the Australian Gas
Association for installation and operation
as described in these Installation and
Operating Instructions.
Your unit should be serviced annually
by an authorised service person.
918-744b
PG36 Gas Log Fireplace
WARNING:
Improper installation, adjustment, alteration,
service or maintenance can cause injury or
property damage. Refer to this manual. For
assistance or additional information consult
an authorised installer, service agency or the
gas supplier.
FOR YOUR SAFETY:
Do not store or use gasoline or other ammable
vapours and liquids in the vicinity of this or
any other appliance.
Installation and service must be performed by
an authorised installer, service agency or the
gas supplier.
FOR YOUR SAFETY:
What to do if you smell gas:
Do not try to light any
appliance
Do not touch any electrical
switch: do not use any phone
in your building.
Immediately call your gas
supplier from a neighbour's
phone. Follow the gas
supplier's instructions.
If you cannot reach your
gas supplier, call the re
department.
Regency® PG36-5 Gas Log Fireplace
2
TO THE NEW OWNER:
Congratulations!
You are the owner of a state-of-the-art Gas Log Fireplace by FPI FIREPLACE PRODUCTS INTERNATIONAL
LTD. The PG36 has been designed to provide you with all the warmth and charm of a wood replace at the
ick of a switch. The model PG36 has been approved by the Australian Gas Association for both safety and
ef ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for
many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions
and the many features of your Regency® Fireplace.
Regency® PG36-5 Gas Log Fireplace 3
TABLE OF CONTENTS
Lighting Instructions.....................................................31
Resetting The Unit .......................................................31
Shutdown Instructions .................................................31
First Fire ......................................................................31
OPERATING INSTRUCTIONS
Adjusting Flame Height ...............................................32
Summary of Controls ..................................................32
Pilot Adjustment ...........................................................32
Normal Operating Sounds of Gas Appliances .............32
Copy of The Lighting Plate Instructions ......................33
MAINTENANCE
Maintenance Instructions.............................................34
Gold or Brass Louvres & Trim .....................................35
Log Replacement ........................................................35
Glass Gasket ...............................................................35
Door Glass...................................................................35
Removing Valve Tray ...................................................36
Fan Replacement ........................................................37
Manual Control Switch Replacement ..........................38
PARTS LIST
Electronic Components Parts List ...............................39
Main Assembly ............................................................40
Burner Assembly & Log Set.........................................41
Bay Front Assembly.....................................................42
Flush Front Accessories ..............................................43
Premium Flush Front Assembly...................................44
Cast Faceplate Assembly ............................................45
WARRANTY
Warranty ......................................................................47
DATA BADGE
Data Badge....................................................................4
INSTALLATION
Important Message ........................................................5
Before You Start ............................................................5
General Safety Information............................................5
Installation Checklist ......................................................5
Clearances ....................................................................6
Locating Your Fireplace .................................................6
Manufactured Mobile Home Additional Requirements ..6
Combustible Mantels .....................................................7
Mantel Leg Clearances..................................................8
Framing And Finishing ...................................................8
Unit Assembly Prior To Installation ................................9
Flueing Introduction .......................................................9
Exterior Flue Termination Locations ............................10
Flueing .........................................................................11
Simpson Dura-vent Flueing .........................................12
Simpson Dura-vent Flueing Components List .............12
Flueing Arrangements - Horizontal Terminations .........13
Flueing Arrangements - Horizontal Terminations .........14
Flueing Arrangements - Vertical Terminations .............15
Horizontal Terminations ...............................................17
Vertical Terminations ...................................................18
Gas Connection ...........................................................19
Gas Pipe Pressure Testing ..........................................19
Aeration Adjustment ....................................................19
Conversion From NG To LPG ......................................20
Optional Brick Panels ..................................................22
Log Set Installation ......................................................22
Standard Flush Door ...................................................24
Premium Flush Front Installation .................................25
Wiring ..........................................................................29
Remote Control ..........................................................31
Operating Instructions ................................................31
Regency® PG36-5 Gas Log Fireplace
4
DATA BADGE
This is a copy of the label that accompanies
each PG36 Zero Clearance Room Sealed Gas
Fireplace. We have printed a copy of the contents
here for your review.
DO NOT
DO NOT
DO NOT
DO NOT
DO NOT
DO NOT
OPERATE THIS APPLIANCE BEFORE READING THE
INSTRUCTIONS BOOKLET.
PLACE ARTICLES ON OR AGAINST THIS APPLIANCE
STORE CHEMICALS OR FLAMMABLE MATERIALS
SPRAY AEROSOLS IN THE VICINITY OF THIS
APPLIANCE WHILE IN OPERATION.
OPERATE WITH PANELS, COVERS OR GUARDS
REMOVED FROM THIS APPLIANCE.
ENCLOSE THIS APPLIANCE.
DO NOT MODIFY THIS APPLIANCE.
NEAR THIS APPLIANCE.
DO NOT
908-602a
(Australia Only)
The label is located on the front inside base of the
unit, visible when the bottom louvre is open. DATA BADGE NOTE: Regency® units are
constantly being improved. Check the label on
the unit and if there is a difference, the label on
the unit is the correct one.
Gas Type NG LPG
Model
Gas Consumption 33 . 31 .
Manifold Pressure 1.0 2.6
Injector Size 1x 1x 52
PG36-NG PG36-LPG
mj mj
kPa kPa
##
37
Electrical: 240VAC 50Hz 1.0 amp max.
Serial
Number
918-285c
Model
N2134
Regency Gas Fireplace
2.65mm 1.61mm
AGA 5815G
AS4553
262
Distributed by:
Western Australia:
To be installed by an authorised person in
accordance with installation instructions
provided with the appliance.
Air Group Australia
28-30 Division St
Welshpool, WA 6106
Fireplace Products
Australia Pty. Ltd.
21-23 South Link Blvd.
Dandenong, VIC 3175
Eastern Australia:
Regency® PG36-5 Gas Log Fireplace 5
INSTALLATION
CHECKLIST
1) Locate appliance. Refer to the following
sections:
a) Locating Your Gas Fireplace
b) Combustible Mantels
c) Mantel Leg Clearances
d) Framing and Finishing
e) Flueing
2) Assemble Top Standoffs and Top Facing
Support and Side Nailing Strips. Refer to the
"Unit Assembly Prior to Installation" section.
(NOTE: must be done before installing unit
into replace.)
3) Install flue, refer to the "Horizontal
Termination" & "Vertical Termination"
sections.
4) Make gas and electrical connections. Test
the pilot. Must be as per diagram. Refer to
the " Pilot Adjustment" section.
5) Install standard and optional features. Refer
to the following sections where applicable:
a. Brick Panels
b. Log Set Installation
c. Flush Door
d. Premium Flush Front
e. Bay Door
f. Hampton Cast Faceplate
g. Hampton Cast Grills
h. Remote Controls
6) Final check.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
ring correctly and operation fully explained
to customer.
This includes:
1) Clocking the appliance to ensure the correct
ring rate (rate noted on label 30,000 Btu/h)
after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the ame does not carbon. First allow
the unit to burn for15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE INSTRUCTIONS
The PG36-NG or PG36-LPG Room Sealed
Fireplace must be installed in accordance with
AS5601-2004 and NZS 5261 5261 and these
instructions. Carefully read all the instructions
in this manual rst. Consult the "authority
having jurisdiction" to determine the need for
a permit prior to starting the installation. It is
the responsibility of the installer to ensure
this replace is installed in compliance with
manufacturer's instructions and all applicable
codes.
BEFORE YOU START
NOTE:
NOT INTENDED AS A FIREPLACE INSERT.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
INSTALLATION AND REPAIR SHOULD
BE DONE BY A AUTHORISED SERVICE
PERSON. THE APPLIANCE SHOULD
BE INSPECTED BEFORE USE AND AT
LEAST ANNUALLY BY AN AUTHORISED
SERVICE PERSON. MORE FREQUENT
CLEANING MAY BE REQUIRED
DUE TO EXCESSIVE LINT FROM
CARPETING, BEDDING MATERIAL,
ETC. IT IS IMPERATIVE THAT CONTROL
COMPARTMENTS, BURNERS AND
CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS OF
HIGH SURFACE TEMPERATURES,
ESPECIALLY THE FIREPLACE GLASS,
AND SHOULD STAY AWAY TO AVOID
BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS THE
APPLIANCE.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE. DO NOT
USE AEROSOLS IN THE VICINITY OF
THIS APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance shall be installed in
accordance with the manufacturer's
installation instructions,local gas tting
regulations, municipal building codes,
water supply regulations, electrical wiring
regulations, with AS5601-2004 (AGA gas
installation code) NZS 5261 (New Zealand)
2) Installation and repair should be done
ONLY by an authorised person.
3) THIS APPLIANCE IS NOT INTENDED AS A
FIREPLACE INSERT. DO NOT CONNECT
TO MASONARY FLUE.
4) This appliance must be connected to
the speci ed ue and termination cap
to the outside of the building envelope.
Never ue to another room or inside a
building. Make sure that the ue is tted
as per Flueing instructions.
5) Inspect the ueing system annually for
blockage and any signs of deterioration.
6) Flueing terminals shall not be recessed into
a wall or siding.
7) Any safety glass removed for servicing must
be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
replace.
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
11) Under no circumstances should this
appliance be modi ed. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by an authorised service
person. An authorised service person should
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other ammable vapours and liquids).
Regency® PG36-5 Gas Log Fireplace
6
INSTALLATION
Clearances for Bay or Flush Front
NOTE: The minimum oor clearance must
be maintained from the top surface of the
carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel* Minimum 7" (177mm)
Ceiling from top of unit. 32" (1016mm)
Side Wall Clearance
Bay or Flush Front 6" (152mm)
Horizontal Flue Clearances
Top 2" (51mm)
Side 1-1/2" (38mm)
Bottom 1-1/2" (38mm)
Vertical Flue Clearances 1-1/4" (32mm)
Alcove Clearances**:
Max. Depth 36" (914mm)
Min. Width 48" 1219mm)
Min. Height 72" 1829mm)
* see mantle clearance instructions
(Refer to the "Combustible Mantels," & "Mantel
Leg Clearances" sections.)
CLEARANCES
The clearances listed below are Minimum
distances unless otherwise stated:
A major cause of chimney related res is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this replace and
ue system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back 0" (0mm)
Side 0" (0mm)
Floor 0"
(0mm)
Diagram 1
LOCATING YOUR
FIREPLACE
1) When selecting a location for your replace,
ensure that the clearances outlined on this
page are met.
2) Provide adequate clearances for servicing.
3) The appliance must be installed on a at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the oor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
ooring, the appliance must be installed on
a metal or wood panel extending the full
width and depth of the appliance.
4) The PG36 Co Axial Flue Gas Fireplace
can be installed in a recessed position or
framed out into the room as in A, B, C, D.
See Diagram 1.
5) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The PG36 Co Axial Flue Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) We recommend that you plan your installation
on paper using exact measurements for
clearances and oor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For ue terminations see the "Exterior
Flue Termination Locations" section.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided. Refer to the "Wiring"
section.
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into Wall/Alcove
D) Corner
WARNING
Fire hazard is an extreme
risk if these clearances
are not adhered to.
Regency® PG36-5 Gas Log Fireplace 7
INSTALLATION
Due to the extreme heat this replace emits, the mantel clearances are critical. Combustible mantel clearances from the top of unit are shown
in the diagrams below.
COMBUSTIBLE MANTELS
These drawings are to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area or higher using the
above scale.
Note: Ensure the paint that is used on the mantel and the facing
is "heat resistant" or the paint may discolour.
Note: A non-combustible mantel may be installed at a lower
height if the framing is made of metal studs covered with
a non-combustible board.
Regency® PG36-5 Gas Log Fireplace
8
INSTALLATION
Note: 40-1/2" (1029mm) is the minimum
height for both ex termination or
Simpson Dura-Vent ueing.
MANTEL LEG
CLEARANCES
Combustible mantel leg clearances as per
diagram below:
FRAMING AND
FINISHING
1) Determine the total thickness of facing
material (e.g. drywall plus ceramic tiles) to
allow the nished surface to be ush with
the front of the unit. Total facing thickness
can vary from 1/2" (13mm) to 1-1/4" (32mm)
thick.
152m m Side Wall
127m m
51m m
Mantel leg
Mantel leg
P36
Fire p lace
Allow able m antel leg
projection.
76m m
38m m
Maximum
38mm
projection
at 51mm
minimum
clearance.
Note:The unit does not have to be completely
enclosed in a chase. The clearance on
top of the unit is 0" to the standoffs so
combustible building materials can be
laid directly on top of the standoffs. You
must maintain 1-1/2" (38mm) clearance
from the ue to combustible materials
for ex (1-1/4" (32mm) for Simpson
Dura-Vent).
5) Use steel studs for framing where the
1-1/2" (38mm) clearance from the ue to
combustible material cannot be maintained,
e.g. front top header.
2) Frame in the enclosure for the unit with
framing material.
12-3/4"
(324mm)
3-1/2"
(89mm)
4"
(102mm)
2”
(51mm)
40-1/2" (1029mm)
36" (914mm)
32-1/2" (826mm)
10" (254mm) dia. hole
through wall for Flex
or for DuraVent
Top Header
Opening for gas
connection
1/2"
(13mm)
Drywall
Install Side Nailing Strips, Top Facing
Support, and Top Standoffs before
unit is slipped into position. See "Unit
Assembly Prior to Installation" section
for assembly details.
NOTE:
When using the Premium Flush Front
option, a nishing trim (962mm cover)
needs to be installed to cover the
spacers.
Maintain a physical gap between lining
and spacers 2-5mm. (5mm clearance to
framing each side).
Standard Framing Dimensions
A B C D
36-1/4" 36-1/4" 12-3/4" 46"*
921mm 921mm 324mm 1126mm*
Framing Dimensions with
Premium Flush Front Option
A B C D
37-1/4" 37-1/4" 17-3/8" 46-1/2"*
944mm 946mm 432mm 1182mm*
* 'D' is Minimum height to combustible mate-
rials including the Minimum 2" (51mm) Top
clearance to the Horizontal Flue, see ue
clearances in section "Clearances."
3) For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and drywall, as per
local installation codes. (Do not insulate
the replace itself.)
4) The top of the unit must not be closer than
32" (813mm) to the ceiling.
Premium Flush Front Framing
Do not use combustible material as lining (eg.
timber) around the replace as shown in the
shaded area in the diagram below.
Regency® PG36-5 Gas Log Fireplace 9
INSTALLATION
FLUEING
INTRODUCTION
The PG36 uses the "balanced ue" technology
Co Axial system. The inner liner ues products
of combustion to the outside while the outer
liner draws outside combustion air into the
combustion chamber thereby eliminating the
need to use heated room air for combustion and
losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and ue system must be
ued directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each Co Axial Flue gas appliance must use
it's own separate ue system. Common ue
systems are prohibited.
Before the unit is slid into position, install the
provided spacers to the side of the replace
as follows;
1) Align the screw locations on spacer with
screw locations on the side of the rebox
and secure in place using 3 screws.
2) Repeat for other side.
NOTE: The side nailing strips are to be in-
stalled to the spacer after the spacer
is attached to the unit.
Spacer
Left Side Shown
Premium Flush Front
Spacer Installation
Side
Nailing Strips
"C" Screw Position:
For a facing material depth of 1-1/4" (32mm),
the top facing support must be reversed.
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The Top Facing Support, the Side Nailing Strips
and the 2 Top Standoffs must be correctly
positioned and attached to the top before unit
is slipped into position.
Top Standoff Assembly
The top standoffs are shipped in a at position
and must be folded into shape and attached.
1) Remove the standoffs from the replace top.
2) Take each standoff and bend into the correct
shape. Bend up at the bend lines until the
screw holes in the standoff and the pre-
punched screw holes on the replace top
line up.
3) Attach the standoff securely to the top with
2 screws per standoff (on opposite corners).
Top Facing Support
Side Nailing Strips
Determine the total thickness of facing material
(e.g. drywall plus ceramic tiles) to allow the
nished surface to be ush with the front of the
unit. Total facing thickness can vary from 1/2"
(13mm) to 1-1/4" (32mm) thick.
The Top Facing Support can be mounted in 3
different positions depending on the thickness
of the facing material.
2) Fold out the two nailing strips on each side.
Screw
Position Facing Material
Depth
A 1/2" / 13mm
B 7/8" / 22mm
C* 1-1/4" / 32mm
* For "C" screw position the top facing
support is reversed.
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched
screw holes on the top front of the unit. Use
hole positions A, B, or C depending on your
facing depth.
Regency® PG36-5 Gas Log Fireplace
10
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced ue terminals or
the ue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
Minimum
Clearance (mm)
a Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input 300
- Appliances over 50 MJ/h input 500
b From the ground or above a balcony 300
c From a return wall or external corner 500
d From a gas meter (M) 1000
e From an electricity meter or fuse box (P) 500
f From a drain or soil pipe 150
g Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal 500
h From any other ue terminal, cowl or combustion air intake 500
j Horizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub- oor ventilation
(see also Note (I)):
- Appliances up to 150 MJ/h input 500
- Appliances over 150 MJ/h input 1500
k Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub- oor ventilation
(see also Note (I)): see table below
Clearance 'k' in mm
Space Heaters All Other Appliances
Up to 50 MJ/h Up to 50 MJ/h input Over 50 MJ/h input Over 150 MJ/h input
input to 150 MJ/h input
150 500 1000 1500
NOTES:
(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.
(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal.
(III) Prohibited area below electricity meter or fuse box extends to ground level.
(IV) A ue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free ow
of air at the appliance is achieved.
Regency® PG36-5 Gas Log Fireplace 11
INSTALLATION
FLUEING
Regency® Direct Vent System (Flex)
Horizontal Terminations Only
These ueing systems, in combination with the PG36 Room Sealed Gas Fireplace, have been tested and listed as a Direct Vent type ue system
by the Australian Gas Association. The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram in
the "Exterior Flue Termination Locations" section.
Regency® Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the PG36 with a maximum
run of 1200mm.
1) 175mm dia. exible liner (1200mm length)
2) 100mm dia. exible liner (1200mm length)
3) spring spacers (4)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
If longer runs are needed, the Regency®
Direct Vent system (Flex) # 946-516 includes
all the parts needed to install the PG36 with
a maximum 3.0m run.
1) 175mm dia. exible liner (3.0m length)
2) 100mm dia. exible liner (3.0m length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency® may be used for Flex installations.
3) If you are installing the PG36 into a Regency® Mantel Kit, use the minimum horizontal vent height (centre-line of 1029mm). Remember
to include the mantel base in your calculations and to maintain the 32mm clearance (38mm with Flex) to the underside of the mantel
top.
6-7/8"
(173mm)
dia. Flue pipe
4" (102mm)
dia. flue pipe
spring spacer
Termination Cap
(Part# 946-578/P)
AstroCap
(patented)
Wall Thimble
Regency® PG36-5 Gas Log Fireplace
12
Flue Adapter
(Part# 510-994)
Pipe Length
Round Support
Box/Wall Thimble
(Part # 940)
Round
Support Box/
Wall Thimble
(Part # 940)
Vertical
Terminal
Storm Collar
Part # 953
Flashing
943 or 943S
Ceiling Firestop
(Part # 963)
24" (610mm)
Pipe Length
Adj.Pipe Length
11" - 14-5/8"
(279mm - 372mm)
90 Elbow
o
AstroCap
Wall Thimble
Part # 942
Vinyl Siding
Standoff (Optional)
Part #950
INSTALLATION
Simpson Dura-Vent
Co-Axial Flue GS
SIMPSON DURA-VENT FLUEING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Co Axial Flue System offers a complete line of component parts for installation of both horizontal and vertical installations. Many
items are offered in decorative black, as well as galvanized nish. We recommend using the galvanized nish for installation with the PG36.
The minimum components required for a basic
horizontal termination are:
1 Horizontal Termination Cap
1 90o Elbow
1 Flue Adaptor
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
SIMPSON DURA-VENT FLUEING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from Masport.
971 Horiz. Termination Kit includes: 90o black
elbow, wall thimble cover, horiz. square
termination cap, 24" black pipe, and 11"
-14" 5/8" adjustable black pipe
970 Basic Horiz. Termination. Kit includes:
90
o black elbow, wall thimble cover,
horiz. square termination cap
978 Vert. Termination Kit includes 0/12 -
6/12 pitch adjustable ashing, storm
collar, low pro le term. cap
908B 6" (152mm) Pipe Length - Black
907B 9" (229mm) Pipe Length - Black
906 12" (305mm) Pipe Length - Galv.
906B 12" (305mm) Pipe Length - Black
904 24" (610mm) Pipe Length - Galv.
904B 24" (610mm) Pipe Length - Black
903 36" (914mm) Pipe Length - Galv.
903B 36" (914mm) Pipe Length - Black
902 48" (1219mm) Pipe Length - Galv.
902B 48" (1219mm) Pipe Length - Black
911B 11"-14 5/8" (279mm - 372mm) Adjustable
Pipe Length - Black
917B 17"- 24" (432mm - 610mm) Adjustable
Length - Black
945 45O Elbow - Galv.
945B 45O Elbow - Black
945G 45O Elbow - Swivel - Galv.
945BG 45O Elbow - Swivel - Black
990 90O Elbow - Galv.
990B 90O Elbow - Black
990G 90O Elbow - Swivel - Galv.
990BG 90O Elbow - Swivel - Black
991 High Wind Termination Cap (Vertical)
980 Vertical Termination Cap
984 Horizontal Square Termination Cap
985 Horiz. Square High Wind
Termination Cap
982 Snorkel - 14"(356mm) Rise Term.Cap
981 Snorkel - 36" (914mm) Rise
Termination Cap
940 Wall Thimble - Support/Box
941 Cathedral/Ceiling - Support/Box
3951 Brass Trim for Wall Thimble/
Ceiling Sup.
963 Firestop Spacer
943 Flashing 0/12-6/12
943S Flashing 7/12-12/12
953 Storm Collar
950 Vinyl Siding Standoff
988 Wall Strap
942 Wall Thimble
Parts not supplied by Dura-Vent
946-506/P Flue Guard (Optional)
510-994 Dura-Vent Flue Adaptor
640-530/P Riser Flue Terminal
946-205 Vinyl Siding Shield for Riser Flue
Terminal
Part # Description Part # Description Part # Description
Flat Wall Installation
Wall Thickness
(inches) Vent Length Required
(inches)
4" - 5-1/2" 6"
7" - 8-1/2" 9"
10" - 1-1/2" 12"
9" - 14-1/2" 11" - 14-5/8" Adj. Pipe
15" - 23-1/2" 17" - 24" Adj.
Corner Installation
Wall Thickness
(inches) Vent Length Required
(inches)
3-1/4" - 6-3/4" 11" - 14-5/8" Adj. Pipe
7-3/4" - 16-1/4" 17" - 24" Adj. Pipe
7-1/4" - 8-3/4" 6" + 12"
9" + 9"
4-1/4" - 5-3/4" 6" + 9"
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl furring
strips may be used, instead of the vinyl siding
standoff, to create a level surface to mount the
ue terminal. The Terminal must not be recessed
into siding. Measure the wall thickness including
furring strips.
Regency® PG36-5 Gas Log Fireplace 13
INSTALLATION
18
20
24
22
2
0
12
6
16
26
28
30
32
34
36
38
4
14
8
10
2
0
4
5
2
0
3.5
1
5.5
4
4.5
1.5
0.5
3
2.5
2
0
3.5
1
1.5
0.5
3
2.5
1029mm
Minimum
Height
Requirement
Meters
Meters
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT FLUE GS SYSTEM and
REGENCY® DIRECT FLUE SYSTEM (FLEX)
(LPG & NG)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal
one 90o elbow).
Note: Must use optional ue adapter (Part # 510-994) when using Simpson Dura-Vent pipe.
Simpson Dura-Vent
4" (102mm) inner diameter
6-5/8" (168mm) outer diameter
Regency® Flex Vent
4" (102mm) inner diameter
6-7/8" (175mm) outer diameter
Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas Fireplace," "Combustible Mantels,"
"Mantel Leg Clearances" & "Framing and Finishing" sections.
Horizontal ue must be supported every 3 feet (0.9 meters).
Firestops are required at each oor level and whenever passing through a wall.
A ue guard should be used whenever
the termination is lower than the
speci ed minimum or as per local
codes.
Note: Regency® Co Axial Flue System
(Flex) is only approved for
horizontal terminations.
Regency® PG36-5 Gas Log Fireplace
14
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT FLUE GS SYSTEM and
REGENCY® CO AXIAL FLUE SYSTEM (FLEX)
(LPG & NG)
The diagram below shows examples of horizontal termination arrangements using two 90o elbows (two 45o elbows equal one 90o elbow).
Note: 1) A maximum of two 90o elbows are permitted.
2) A minimum of 6 ft. (1.8m) vertical from base of unit is required if two 90o elbows are used.
3) Minimum distance between elbows is 2 ft. (0.6m).
4) Determine the permitted range of horizontal termination arrangements by using chart in the "Simpson Dura-Vent
Flueing" section and deducting 3 ft. (0.9m) from the maximum horizontal distance for the second 90o elbow.
Simpson Dura-Vent
4" (102mm) inner diameter
6-5/8" (168mm) outer diameter
Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas Fireplace," "Combustible Mantels," "Mantel
Leg Clearances" & "Framing and Finishing" sections.
Horizontal ue must be supported every 3 feet (0.9 meters).
Firestops are required at each oor level and whenever passing through a wall.
A ue guard should be used whenever the
termination is lower than the speci ed minimum
or as per local codes.
If length "B" is increased, length "A" must be
decreased by a corresponding amount.
INSTALLATION
Regency® PG36-5 Gas Log Fireplace 15
INSTALLATION
FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT CO AXIAL FLUE GS SYSTEM (LPG & NG)
The PG36 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset using
two 90o elbows (two 45o elbows equal one 90o elbow) with Simpson Dura-Vent Co Axial Flue GS ue
systems for LPG and NG, as per diagram 1.
The PG36 is approved for a 37 ft. (11.3m) straight vertical, including a 20" (0.5m) horizontal offset
using two 90o elbow (two 45o elbows equal one 90o elbow) with Simpson Dura-Vent Co Axial Flue
GS ue systems for LPG and NG, as per the diagram 2.
Flue must be supported at offsets
Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas
Fireplace," "Combustible Mantels," "Mantel Leg Clearances" & "Framing and Finishing"
sections.
Note: Must use optional ue adapter when using Simpson Dura-Vent pipe
(Part # 510-994).
Note: Regency® Co Axial Flue System (Flex) is only approved for horizontal terminations.
Diagram 1 Diagram 2
Regency® PG36-5 Gas Log Fireplace
16
The PG36 is approved for a 37 ft. (11.3m) straight vertical, with Simpson
Dura-Vent Co Axial Flue GS ue systems for LPG and NG, as per the
diagram 3.
The shaded area in the diagram 3 shows all allowable combinations of straight
vertical and offset to vertical terminations with Simpson Dura-Vent Co Axial
Flue GS ue systems for LPG and NG. Maximum two 45o elbows allowed.
Flue must be supported at offsets
Firestops are required at each oor level and whenever passing
through a wall.
Maintain clearances to combustibles as listed in the "Clearances,"
"Locating Your Gas Fireplace," "Combustible Mantels," "Mantel Leg
Clearances" & "Framing and Finishing" sections.
Diagram 3
INSTALLATION
Regency® PG36-5 Gas Log Fireplace 17
INSTALLATION
Diagram 5
8) Slide the appliance and ue assembly
towards the wall carefully inserting the
ue pipe into the ue cap assembly. It is
important that the ue pipe extends into
the ue cap suf cient distance so as to
result in a minimum pipe overlap of 1-1/4
inches. Secure the connection between the
ue pipe and the ue cap by attaching the
two sheet metal strips extending from the
ue cap assembly into the outer wall of the
ue pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 4.
9) Install wall thimble in the center of the
10" square and attach with wood screws
(Diagram 5).
HORIZONTAL
TERMINATIONS
Install the ue system according to the
manufacturer's instructions included with
the components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
the way when the ueing system is attached.
If this is the case, you may want to adjust
the location of the unit. Rough in the gas
preferably on the right side of the unit and
the electrical (junction block is on the left
side) on the left.
2) Co Axial Flue pipe and ttings are designed
with special twist-lock connections to connect
the ueing system to the appliance ue outlet.
A twist-lock appliance adaptor is an available
option that must be used in conjunction with
the Simpson Dura-Vent Co Axial Flue GS
system.
3) Put a bead of silicone inside the outer section
of the adapter and a bead of Stove Mate on
the inner collar. Slip the adapter over the
existing inner and outer ue collar and fasten
to the outer collar only with the 3 supplied
screws (drilling pilot holes will make this
easier). Level the replace and fasten it to
the framing using nails or screws through
the nailing strips.
4) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Note:
a) Twist-lock procedure: Four indentations,
located on the female ends of pipes and
ttings, are designed to slide straight
onto the male ends of adjacent pipes
and ttings, by orienting the four pipe
indentations so they match and slide
in to the four entry slots on the male
ends, Diagram 1. Push the pipe sections
completely together, then twist-lock
one section clockwise approximately
one-quarter turn, until the two sections
are fully locked. The female locking lugs
will not be visible from the outside, on
the Black Pipe or ttings. They may be
located by examining the inside of the
female ends.
Diagram 1
b) Horizontal runs of flue must be
supported every three feet. Wall straps
are available for this purpose.
5) Mark the wall for a 10" x 10" (254mm x
254mm) square hole. The center of the
square hole should line up with the centerline
of the horizontal pipe. Cut and frame the 10
inch (254mm) square hole in the exterior
wall where the ue will be terminated. If the
wall being penetrated is constructed of non-
combustible material, i.e. masonry block or
concrete, a 7"(178mm) dia. (7-1/2"(191mm)
dia. for ex) hole is acceptable.
Diagram 2
Note:
a) The horizontal run of ue must be level,
or have a 1/4 inch (6mm) rise for every 1
foot (.3m) of run towards the termination.
Never allow the ue to run downward.
This could cause high temperatures and
may present the possibility of a re.
b) The location of the horizontal flue
termination on an exterior wall must meet
all local and national building codes, and
must not be blocked or obstructed. For
External Flue Terminal Locations, see
diagram in the "Exterior Flue Termination
Locations" section.
6) The arrow on the flue cap should
be pointing up. Insure that the 1-1/2"
clearances to combustible materials are
maintained. Install the termination cap,
diagram 5.
The four wood screws provided should
be replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.
Note: If installing termination on a siding
covered wall, a vinyl siding standoff
or furring strips must be used to
ensure that the termination is not
recessed into the siding.
7) Before connecting the horizontal run of
ue pipe to the ue termination, slide the
Wall Thimble (Part # 620-926) over the ue
pipe.
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature silicone
sealant to outer pipe on every twist-
lock joint.
Note: With Dura-Vent,
the minimum
height is
achieved by
installing a 90o
elbow directly
to the flue
adaptor.
Diagram 4
Diagram 3
Regency® PG36-5 Gas Log Fireplace
18
Offset Chart
Galvanized pipe is desirable above the roo ine
due to its higher corrosion resistance. Continue
to add pipe sections through the ashing until
the height of the ue cap meets the minimum
height requirements speci ed in Diagram 5 or
local codes. Note that for steep roof pitches,
the vertical height must be increased. A poor
draft, or down drafting can result from high wind
conditions near big trees or adjoining roof lines,
in these cases, increasing the ue height may
solve the problem.
7) Ensure ue is vertical and secure the base
of the ashing to the roof with roo ng rails,
slide storm collar over the pipe section and
seal with a mastic.
8) Install the vertical termination cap by twist-
locking it.
Note: Any closets or storage spaces, which
the ue passes through must be
enclosed.
Diagram 3
Diagram 5
Diagram 1
Diagram 2
Note: Apply sealant "Mill-Pac" to inner pipe
and high temperature silicone seal-
ant to outer pipe on every twist-lock
joint.
VERTICAL
TERMINATIONS
1) Maintain the 1-1/4" (32mm)
clearances (air spaces) to
combustibles when passing
through ceilings, walls, roofs,
enclosures, attic rafter, or other
nearby combustible surfaces.
Do not pack air spaces with
insulation. Check seciotn
"Simpson Dura-vent Flueing"
for the maximum vertical rise of
the ueing system and the
maximum horizontal offset
limitations.
2) Set the gas appliance in its
desired location. Drop a
plumb bob down from the
ceiling to the position of
the appliance ue exit, and mark the location
where the ue will penetrate the ceiling. Drill
a small hole at his point. Next, drop a plumb
bob from the roof to the hole previously
drilled in the ceiling, and mark the spot where
the ue will penetrate the roof. Determine
if ceiling joists, roof rafters o r
other framing will obstruct the
ueing system.
You may wish
to relocate the
appliance or to
offset, as shown
in Diagram 2
to avoid cutting
load bearing
members.
3) A Firestop spacer must be installed in the
oor or ceiling of every level. To install the
Firestop spacer in a at ceiling or wall,
cut a 10 inch square hole. Frame the hole
as shown in Diagram 3 and install the
restop.
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of suf cient size to meet
the minimum requirements for clearance
to combustibles of 1-1/2" (38mm). Slip the
ashing under the shingles (shingles should
overlap half the ashing) as per Diagram
4.
Roof Pitch Minimum Flue Height
Feet Meters
at to 7/12 2 0.61
over 7/12 to 8/12 2 0.61
over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14/12 5 1.52
over 14/12 to 16/12 6 1.83
over 16/12 to 18/12 7 2.13
over 18/12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
Diagram 4: The upper half of the ashing is
installed under the roo ng material and not
nailed down until the chimney is installed. This
allows for small adjustments.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important
to support the ue pipe every 3 feet,
to avoid excessive stress on the
elbows, and possible separation.
Wall straps are available for this
purpose (Diagram 2).
INSTALLATION
Regency® PG36-5 Gas Log Fireplace 19
INSTALLATION
PG36-NG4 System Data
For 0 to 4500 feet altitude
Burner Inlet Ori ce Sizes: #37( 2.65mm)
Max. Input Rating 33 mj
Min. Input Rating 20 mj
Supply Pressure min.1.13 kPa
Manifold Pressure
(High) 0.9 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 240 CFM.
Log Set: Ceramic bre, 7 per set.
Flue System: Simpson Dura-Vent Direct
Vent System or Regency® Direct
Vent System (Flex)
PG36-LPG4 System Data
For 0 to 4500 feet altitude
Burner Inlet Ori ce Sizes: #52 (1.61mm)
Max. Input Rating 31 mj
Min. Input Rating 18 mj
Supply Pressure min 2.75 kPa
Manifold Pressure
(High) 2.6 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 240 CFM.
Log Set: Ceramic bre, 7 per set.
Flue System: Simpson Dura-Vent Co Axial
Flue System AERATION
ADJUSTMENT
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
through the bottom louvre opening. Open the air
shutter for a blue ame or close for a yellower
ame. The burner aeration is factory set but
may need adjusting due to either the local gas
supply or altitude. This adjustment is performed
by the gas tter.
Minimum Air Shutter Opening:
8 mm NG
Full Open LPG
CAUTION: Carbon will be produced if air shutter
is closed too much.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Closed - Tall yellow
Open - Short Blue
GAS CONNECTION
The gas line should be rigid pipe. Copper may
also be used if approved by AS5601-2004.
The gas connection at the valve is 1/2 male.
For minimum and maximum supply pressure
see the System Data Table.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise
with a 1/8" wide at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID
hose.
4) Seal and or check the pilot outlet (# 8)
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits speci ed on the safety
label.
6) When nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" at
screwdriver. Screw should be snug, but do
not over tighten.
EV1
EV2
R.Q.
ADJ.
P.OUT
MD
4321
Pin
11
8
9
10
1
2
3
4
6
7
5
SIT 845 VALVE DESCRIPTION
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection for Pressure Regulator /
Combustion Chamber Compensation
6) Pressure Regulator for Minimum and
Maximum Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet
11) Main Gas Inlet
Regency® PG36-5 Gas Log Fireplace
20
INSTALLATION
Conversion From NG To LPG Kit #513-968
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION!!
1) Shut off the gas supply and unplug the
power cord.
2) Carefully remove the glass, logs and
lava rock.
3) Remove burner.
4) Remove burner orifi ce with a 1/2"
wrench and discard. Use a wrench to
hold on to the elbow behind the orifi ce.
5) Reinstall new burner orifi ce stamped #52
and tighten.
6) Pull out the pilot hood by hand.
9) Adjust the burner aeration setting to and
re-install the burner.
10) Open the bottom louver.
8) Put in the new LPG orifi ce with the allen
key. Then put back the pilot hood.
Burner Orifi ce
Pilot
Hood
Pilot
Hood
removed
7) Remove the pilot orifi ce with the allen
key.
LPG Conversion Kit Contains:
Qty. Part # Description
1 904-390 Burner Orifi ce #52
1 904-529 5/32" Allen Key
1 918-590 Label "Converted to LP"
1 908-528 Red "LPG" label
1 910-037 #30 ULPG Pilot Orifi ce
1 918-577 Instruction Sheet
11) Remove the front cover by undoing the 2
screws.
Front Cover
12) Stick the conversion label "This unit has
been converted to LPG" over top of the
serial number decal.
13) Replace the yellow "NG" label with the
red "LPG" label.
14) Carefully pull out the control box from
underneath the fi rebox.
Note: The control box is held in place with
velcro.
Pilot
Orifi ce
/