WURM CRC-BL-EEV Product information

Type
Product information

WURM CRC-BL-EEV - is a versatile and feature-rich cold location controller designed for top-hat rail installation. It supports up to 4 cold locations or 2 control circuits with EEV (via an expansion module). With its pre-programmed functional sequences and parameters, it simplifies setup and configuration based on the selected cold location type.

Key capabilities of the WURM CRC-BL-EEV include:

  • Advanced defrost control with multiple defrosting methods (electric defrost, forced air defrost, hot gas defrost, and cool gas defrost) and defrost synchronization for multiple controllers.

  • Intelligent fan control with compressor oscillation protection and fan delay, ensuring efficient temperature management.

WURM CRC-BL-EEV - is a versatile and feature-rich cold location controller designed for top-hat rail installation. It supports up to 4 cold locations or 2 control circuits with EEV (via an expansion module). With its pre-programmed functional sequences and parameters, it simplifies setup and configuration based on the selected cold location type.

Key capabilities of the WURM CRC-BL-EEV include:

  • Advanced defrost control with multiple defrosting methods (electric defrost, forced air defrost, hot gas defrost, and cool gas defrost) and defrost synchronization for multiple controllers.

  • Intelligent fan control with compressor oscillation protection and fan delay, ensuring efficient temperature management.

Cold location controller for top-hat rail installation with extended operating modes for 4 cold loca-
tions or 2 control circuits with EEV
CRC-BL-EEV_V2.2.0_PI_2020-04B_EN 1
Sous réserve de modifications techniques
CRC-BL-EEV
1 CRC-BL-EEV
Cold location controller for top-hat rail installation with extended operating modes
for 4 cold locations or 2 control circuits with EEV
1.1 Front view
Fig. 1: Front view
1.2 Features
Suitable for 4 cold locations max.
Up to 2 electronic expansion valves possible by expansion module
Basic functional sequences and parameters preprogrammed by selection of cold location type
Intelligent fan control, compressor oscillation protection, fan delay
Thermal fan control and draining time after defrosting
Suitable for electric defrost, forced air defrost, hot gas defrost and cool gas defrost
Defrost control by real-time clock with power reserve
Simple defrost synchronisation of multiple controllers (master-slave)
6 defrost times by integrated weekly timer
Digital inputs for setpoint switchover, manual defrost initiation and door contact
Option to select 3-point control
Control sensor weighting can be set separately for day operation and night operation
Support for higher baud rates on the C-BUS
Can be locked to prevent unwanted parameter adjustment
Plain text name for each parameter on the display, language selectable
Unique parameter identification with Quicklinks
1-finger operation
Connection of max. 2 external displays
Plug-in screw terminals
Large data memory for temperature history
Connection to the Wurm system via Wurm CAN communication bus (C-BUS) and
FRIGODATA XP
Cold location controller for top-hat rail installation with extended operating modes for 4 cold loca-
tions or 2 control circuits with EEV
2 CRC-BL-EEV_V2.2.0_PI_2020-04B_EN
Sous réserve de modifications techniques
CRC-BL-EEV
1.3 Safety instructions
Writing conventions
AVERTISSEMENT
Avoid the described hazard: otherwise, electric voltage poses a hazard that could lead to death
or serious bodily injury.
ATTENTION Avoid the described hazard: otherwise, minor or medium physical injury or damage to property
will result.
For your safety
For safe operation and to avoid personal injury and equipment damage through operator error, always
read these instructions, become familiar with the device, and follow all safety instructions on the pro-
duct and in this document, as well as the safety guidelines of Wurm GmbH & Co. KG Elektronische
Systeme. Keep these instructions ready to hand for quick reference and pass them on with the device
if the product is sold.
Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in the event of improper use or use
for other than the intended purpose.
AVERTISSEMENT
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire plant when installing, wiring or removing. Otherwise, mains vol-
tage and/or external voltage may still be present, even if the control voltage is switched off.
Always remove both power plugs (L and N).
The device should only be wired by a qualified electrician.
Always use the correct tools for all work.
Check all wiring after connection.
Take note of the maximum loads on all connections.
Never expose the device to moisture, for example, condensation or cleaning agents.
Take the device out of operation if it is faulty or damaged and is therefore compromising safe
operation.
Do not open the device.
Do not repair the device yourself. If required, send it in for repair with an exact description of the
fault.
ATTENTION ELECTROMAGNETIC INTERFERENCE CAN CAUSE FAULTS!
Always use shielded data cables and place them far away from power lines.
Target group This manual is intended for "service technicians".
Intended use The CRC-BL-EEV is a cold location controller for max. 4 cold locations
or max. 2 control circuits with EEV via X-tra module.
Wurm Infocenter paperless info
Cold location controller for top-hat rail installation with extended operating modes for 4 cold loca-
tions or 2 control circuits with EEV
CRC-BL-EEV_V2.2.0_PI_2020-04B_EN 3
Sous réserve de modifications techniques
CRC-BL-EEV
Version and validity of the documentation
Any versions not listed are special solutions for individual projects and are not described in detail in this document.
This document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme, Morsbachtalstraße 30, D-42857 Remscheid
You can find more information on our website at www.wurm.de.
1.4 Connection diagram
Fig. 2: Connection diagram
Version Date
V2.2.0 and higher 2020-04B Documentation status
Item Designation Function
1C-BUS interface Data communication (H = CAN high, S = shield, L = CAN low)
2Display sockets External displays DSP002, DSP100, DSP-LCD, DSP-Booster
3Output relays K1...K4 Dependent on cold location type, floating contact, 230V~,
4(2)A
4Power supply for L 230V~/50Hz
5X-tra interface Expansion module for 2 electronic
expansion valves
6Power supply for N Neutral conductor
7Digital inputs Di1...Di4 Dependent on cold location type
8Defrost bus Defrost synchronisation
9Sensor inputs S1...S4 Temperature sensor
12 13 14 15 16 17 18
11 22 23 24 25 26 27 28 29
21
38 37 36 35 34 33 32 3139
4321
12 13 14 15 16 17 18
11 22 23 24 25 26 27 28 29
21
38 37 36 35 34 33 32 3139
CRC-BL-EEV
Frigoentry Blueline
2sec.
74451213
d
c
13
68
4
7
9
2
S2
S3
S4
S1
GND
Di2
Sync.
Di3
N
Di1
Di4
L
K1
K2
K3
K4
DSP1
DSP2
H
5
0V
S
L
Cold location controller for top-hat rail installation with extended operating modes for 4 cold loca-
tions or 2 control circuits with EEV
4 CRC-BL-EEV_V2.2.0_PI_2020-04B_EN
Sous réserve de modifications techniques
CRC-BL-EEV
1.5 Installing the device
This device is designed for top-hat rail installation. The housing has standard dimensions according
to DIN 43880 and is also suitable for operation in fuse boxes and distribution cabinets.
The device can be positioned immediately next to another without gaps.
AVERTISSEMENT
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire plant before installing. Otherwise, mains voltage and/or exter-
nal voltage may still be present, even if the control voltage is switched off. Always remove both
power plugs (L and N).
The entire system must be free of voltage.
1. (A) Place the device with the leading edge at an acute angle to the top-hat rail.
2. (B) Push the device downwards onto the top-hat rail.
The device snaps into place with the fastening safety catch (a) on the top-hat rail.
You can now connect the device.
Fig. 3: Top-hat rail installation
1.6 Technical data
Power supply 230V~, +10% / -15%, max. 8VA
Display 1 x display with plain text display
2 x green LED, C-BUS data traffic (CAN Tx, CAN Rx)
C-BUS communication 3-wire CAN bus interface with integrated power supply,
galvanically isolated
Expansion module
communication
Interface for connecting the X-tra module
Temperature sensors 4 x TRK277/7 PLUS, DGF
(T2015, T3000, TF201/TF231, K243)
Digital inputs 4 x floating
Output relay 4 x normally open contacts, 230V~, 4(2)A
Display connection 2 x socket for prefabricated cable to display DSP002, DSP100,
DSP-LCD, DSP-Booster
Real-time clock Battery-buffered
Monitoring system Monitoring of data memory and connected sensors
Dimensions (W x H x D) 106mm x 90mm x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature Operation: 0...+55°C, storage: -25...+70°C
Weight About 450g
CE conformity - 2014/30/EU (EMC Directive)
- 2014/35/EU (Low Voltage Directive)
EAC conformity - TR CU 004/2011
- TR CU 020/2011
RoHS II
Valid from Version 2.2.0
A
B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

WURM CRC-BL-EEV Product information

Type
Product information

WURM CRC-BL-EEV - is a versatile and feature-rich cold location controller designed for top-hat rail installation. It supports up to 4 cold locations or 2 control circuits with EEV (via an expansion module). With its pre-programmed functional sequences and parameters, it simplifies setup and configuration based on the selected cold location type.

Key capabilities of the WURM CRC-BL-EEV include:

  • Advanced defrost control with multiple defrosting methods (electric defrost, forced air defrost, hot gas defrost, and cool gas defrost) and defrost synchronization for multiple controllers.

  • Intelligent fan control with compressor oscillation protection and fan delay, ensuring efficient temperature management.