Pneumercator TMS2000 Quick Start Up Manual

Type
Quick Start Up Manual

Pneumercator TMS2000 is a factory preprogrammed liquid level control system. It can be used to measure and display product and water levels in various tank types. It can also be used for alarm indication and control functions. The TMS2000 is easy to install and use, and it comes with a variety of features that make it a valuable tool for managing tank levels.

Here are some of the key features of the TMS2000:

  • Preprogrammed for quick and easy setup
  • Can be used to measure and display product and water levels in various tank types
  • Can be used for alarm indication and control functions
  • Easy to install and use

Pneumercator TMS2000 is a factory preprogrammed liquid level control system. It can be used to measure and display product and water levels in various tank types. It can also be used for alarm indication and control functions. The TMS2000 is easy to install and use, and it comes with a variety of features that make it a valuable tool for managing tank levels.

Here are some of the key features of the TMS2000:

  • Preprogrammed for quick and easy setup
  • Can be used to measure and display product and water levels in various tank types
  • Can be used for alarm indication and control functions
  • Easy to install and use
Pneumercator Co., Inc.
1785 Expressway Drive North
Hauppauge NY 11788
Phone (631) 293-8450
Fax (631) 293-8533
Tech Support (800) 209-7858
TMS Quick Start-up Guide.docx www.pneumercator.com November 21, 2017
Quick Start-up Guide
For Factory Preprogrammed
TMS2000 & TMS3000 Systems
© COPYRIGHT 2017 PNEUMERCATOR CO., INC.
1785 EXPRESSWAY DRIVE NORTH
HAUPPAUGE, NY 11788
PNEUMERCATOR
Liquid Level Control Systems
DRAWING NO. 20001 REV. A
Quick Start-up Guide TMS Series
Note: Separate manuals are available for System Operation and Installation.
Page
Introduction
Start-up of preprogrammed systems .................................................................................................. 6
Probe Worksheet ................................................................................................................................ 7
Programming Float Height Offsets using TMS Communicator ........................................................... 8
Programming Float Height Offsets using TMS Front Panel .............................................................. 10
TMS Front Panel Navigation Chart ................................................................................................... 12
TMS Wiring Diagrams ....................................................................................................................... 15
Programming for RA100/RA200 Remote Annunciator ..................................................................... 24
Figures:
1. MP45xS Label ............................................................................................................................... 6
2. MP46xS Label ............................................................................................................................... 6
3. TMSComm Direct Connect Site Default Settings .......................................................................... 8
4. TMSComm Probe Configuration ................................................................................................... 9
5. TMS Front Panel Keys Layout .................................................................................................... 10
6. TMS Edit Enable Button .............................................................................................................. 11
7. TMS Front Panel Navigation Chart ............................................................................................. 12
8. TMS AC Power Wiring ................................................................................................................ 15
9. TMS Probe Wiring ....................................................................................................................... 16
10. TMS2000 Sensor Wiring ............................................................................................................. 17
11. TMS3000 Sensor Wiring ............................................................................................................. 18
12. TMS Series to RA200KR Wiring ................................................................................................. 20
13. TMS Series to RA100R Wiring .................................................................................................... 22
TABLE OF CONTENTS
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx November 21, 2017
Introduction
This guide is intended for use as a field help guide for factory-trained technicians when
performing a start-up on the Pneumercator TMS Series tank gauging system. You can use this
guide for both the TMS2000 and TMS3000 consoles. The first part of this guide shows what is
needed to perform a start-up on a FACTORY PREPROGRAMMED TMS Series console. The
second part has the basic wiring needed for the TMS2000 & TMS3000 systems. For detailed
installation instructions please refer to the appropriate TMS Installation Manual. For systems NOT
factory preprogrammed, please refer to the standard TMS Operations Manual for programming
instructions. Please make sure that the Warranty Start-up paperwork is completely filled out by a
factory authorized technician and returned to Pneumercator in a timely fashion to qualify the
system for warranty consideration.
For information on becoming a factory authorized service/start-up technician, please contact
Pneumercator below, or e-mail at [email protected]. Your local Pneumercator sales
representatives may also be of assistance.
This guide is for reference purposes only. Complete installation guidelines are contained in
the TMS2000 & TMS3000 Installation manuals.
For more information, please contact:
Pneumercator Co.
1785 Expressway Drive North
Hauppauge, NY 11788
(631) 293-8450
Fax (631) 293-8533
Toll Free (800) 209-7858
www.pneumercator.com
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 6 of 24 November 21, 2017
Start-up of Preprogrammed systems
This section is for the start-up of systems that have been preprogrammed at the factory with
information supplied by the customer/distributor.
IT IS THE RESPONSIBILITY OF THE START-UP TECHNICIAN TO VERIFY THE
INFORMATION PROGRAMMED INTO THE TMS SYSTEM MATCHES THE SITE
REQUIREMENTS. IF ANY INFORMATION IS NOT CORRECT, THEY SHOULD CORRECT THE
PROGRAMMING PER THE OPERATIONS MANUAL OR CONTACT THE FACTORY FOR
PROGRAMMING ASSISTANCE.
All systems are supplied with factory configuration sheets showing what was programmed into
the TMS system. Please review these sheets prior to continuing.
1. Verify the list of equipment matches what is found on the packing list.
2. Record probe serial number(s), model number(s), calibration factor(s) (Probe C.F.), and length(s)
on the worksheet on the next page. This information must match the factory programming printout
provided with the console to avoid reprogramming the console.
Figure 1 – MP45xS Label Figure 2 – MP46xS Label
3. Confirm the TMS system (includes probes, sensors, and any other wires terminating within the
TMS) has been installed in accordance with the corresponding Installation Manual. This includes
but is not limited to the following:
a. Confirm TMS system is on a separate circuit breaker. (See Figure 8)
b. Confirm there are two (2) 12 AWG wires connected to the IS ground terminals going
to the main circuit panel ground buss bar. (See Figure 8)
c. Verify the intrinsically safe wiring is properly separated from all other wiring as per
Article 504 in the National Electric Code.
d. Verify the probes and sensor cabling is properly terminated. (See Figures 9-11)
4. Power up TMS.
5. Observe and record any alarms or errors. Power Fail, Warning 21 is expected on power-up.
6. Stick tanks for product level & water level and record on the worksheet on the next page.
Note: Stick readings should be taken in the same opening the TMS probe is installed for greater
accuracy. The Product Float must be floating in the product in order to calibrate the TMS.
7. Record the Product and Water level readings (inches or millimeters) displayed on the TMS on the
worksheet on the next page. To access the product level readings on the TMS, hold the MODE
button until the TMS beeps. Repeat until the level unit LED (IN/mm) is lit. Hold the MODE button
until the TMS beeps to access the water level. A “w(w) will be displayed to the left of the reading.
8. For multi-tank systems, hit the TANK SELECT button and repeat steps 8 & 9 for each tank.
9. Calculate float height offsets using the worksheet on the following page.
Note: If programming via the front panel buttons is desired, skip to Page 10.
MODEL
PROBE C.F.
LENGTH
SERIAL No.
MP
PNEUMERCATOR
Liquid Level Control Systems
F1234TM-1
450S
9.128
100
MODEL
PROBE C.F.
LENGTH
SERIAL No.
MP
PNEUMERCATOR
Liquid Level Control Systems
F1234TM-1
450S
9.128
100
SERIAL NUMBER:
R1234-2
BASE P/N:
MP463SA-460-21
PROBE CAL. FACTOR:
9.104
EFFECTIVE LENGTH:
446"
PNEUMERCATOR
Liquid Le vel Control Systems
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 7 of 24 November 21, 2017
Probe Worksheet
Ex: F1 Probe 1 Probe 2 Probe 3 Probe 4 Probe 5 Probe 6
Probe Information
Serial # R1234-1
Model # MP450S
C.F. 9.128
Length 100”
Product Level Information
Stick 42.5”
TMS 43.7”
Prod HO -1.2”
Water Level Information
Stick 0.0”
TMS 1.7”
H2O HO* -1.5”
Ex: F2 Probe 7 Probe 8 Probe 9 Probe 10 Probe 11 Probe 12
Probe Information
Serial # R1234-2
Model # MP463SA
C.F. 9.104
Length 446”
Product Level Information
Stick 242.5”
TMS 224.7”
Prod HO +17.8”
Water Level Information
Stick 0.0”
TMS 5.5”
H2O HO* -5.0”
*Note: The final water level should be set to at least 0.2” for MP45xS or 0.5” for MP46xS to allow for
thermal expansion and/or contraction of the system. The MP46xS Series probes should be allowed
to settle for a couple of days before performing the float offset adjustments. If this is not feasible,
adjust the final water level to 1.0” to allow for probe straightening/settling. If the TMS has a negative
water level calculation, the Water alarm will immediately activate.
The expected value for the offset should not exceed the combination of the float height with the
distance between the bottom of the probe and the tank floor. If the calculated value exceeds
expectations, check the floats are not stuck at the top of the tank. Also confirm the TMS has been
properly configured.
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 8 of 24 November 21, 2017
Programming Float Height Offsets using TMS Communicator
1) Install TMSComm on your computer.
a. Insert TMSComm CD-ROM and follow on-screen instructions.
2) Start TMSComm by clicking on Pneumercator in the Start menu under Programs or All
Programs and then clicking TMSComm.
3) Sign into the TMSComm Administrator account.
a. Click on the Options menu and click on the Security tab.
b. Click the Login… button and enter the User Name and Password.
User Name: ADMIN Password: ROBUST
Note: the password for TMSComm before version 94 is JONESTOWN.
4) Create a Site to connect to.
a. Click on the Sites menu and click Select Sites.
b. Click the New Record button.
Note: If you already have a site configured, simply select the site by clicking on its name
and clicking the Close button. Proceed with Step 5.
c. Enter a Site Name.
d. Verify the settings below Site Name match Figure 3, the default values for the TMS.
Note: COM Port must be set according to your computers hardware settings.
e. Click the Close button.
Figure 3 – TMSComm Direct Connect Site Default Settings
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 9 of 24 November 21, 2017
5) Connect to the Site by clicking Connect in the Sites menu.
6) Read the configuration from the TMS.
a. Click on the Configurations menu.
b. Click on the File menu in the Configurations window and choose Read Configuration From
Connected Device.
7) Click on the Tanks tab and select the desired Tank Channel.
8) Click on the Probe button.
9) Verify the Probe Information (Calibration Factor, Type, and Length) from the worksheet on Page
2 matches the data shown in TMSComm. If this is correct, proceed to the next step. If this is not
correct, make the appropriate changes, close the Probe window, and proceed to Step 13. Return
to Step 7 to begin the calibration process.
10) Enter the Height Float Offset (HO) information from the worksheet on Page 7 as shown in
Figure 4 for both the Product and Water floats.
11) Click the close button.
12) If there is more than one tank enabled, click on the next enabled tank tab and return to Step 8.
13) Click on the File menu and select the Write configuration to Connected Device option.
Figure 4 - TMSComm Probe Configuration Window
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 10 of 24 November 21, 2017
Programming Float Height Offsets using TMS Front Panel
Refer to the Figure 5 below for the relative locations of the buttons. Note that each button has three
labels depending upon your display status. Without entering programming mode, the main labels
printed on the buttons are used. Once in programming mode, a nonflashing display represents
Review Mode where a flashing display represents Edit Mode. Note that this represents the latest front
panel button configuration available. Earlier systems maintained the same labeling system but had
physically different buttons.
Figure 5 - TMS Front Panel Keys Layout (TMS3000 colors shown)
1) Enter programming Mode by pressing and holding the TEST button and then pressing the
MODE button at the same time until Log (Log) appears. Release both buttons.
2) Press the EDIT (TEST) button repeatedly until Config (Config) appears flashing.
3) Press the ► (MODE) button one time. Header (Header) appears.
4) Press the EDIT (TEST) button repeatedly until Probe (Probe) appears flashing.
5) Press the ► (MODE) button one time. The value for Probe CF for Tank Channel 1 is displayed.
6) Press the GROUP SELECT (TANK SELECT) button until the desired Tank Channel number is
displayed over the TANK ID label on the display.
7) Press and hold the STEP (MODE) button until it beeps ONE TIME and immediately release the
button. Repeat this twice more and Prod HO (Prod HO) will appear briefly then the current value
for the Product Float Height Offset will appear. Note that this number will start with a + (+) or a -
(-) sign indicating a positive or negative number.
DWG NO. 20043 REV. N/C
REVIEW
EDIT
STEP GROUP SELECT EDIT
TEST
MODE TANK
SELECT
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 11 of 24 November 21, 2017
8) Press the EDIT ENABLE/THEFT ALARM ACKNOWLEDGE button on the inside of the front door
up one time. This will NOT cause the display to change but will authorize you to make
programming changes to the TMS for the duration of the programming session.
Figure 6 - Edit Enable Button
9) Press the EDIT (TEST) button one time and the first digit (cursor) will start flashing. This digit
indicates a positive or negative number. Use the ▼ (GROUP SELECT) and/or ▲ (TEST) buttons
to change the value of what’s flashing. Use the ► (MODE) button to move the cursor to the right.
Once the last digit is flashing the correct value, enter by pressing the (MODE) button. It will
stop flashing and show you the current value for the Product Float Height Offset.
10) Press and hold the STEP (MODE) button until it beeps ONE TIME and immediately release the
button. h2o HO (H2O HO) will appear briefly then the current value for the Water Float Height
Offset will appear. Note that this number will start with a + (+) or a - (-) sign indicating a positive
or negative number.
11) Press the EDIT (TEST) button one time and the first digit (cursor) will start flashing. This digit
indicates a positive or negative number. Use the ▼ (GROUP SELECT) and/or ▲ (TEST) buttons
to change the value of what’s flashing. Use the ► (MODE) button to move the cursor to the right.
Once the last digit is flashing the correct value, enter by pressing the (MODE) button. It will
stop flashing and show you the current value for the Water Float Height Offset.
12) If there is more than one tank enabled, go to Step 6 to calibrate the next tank.
13) Press and hold the STEP (MODE) button until it beeps TWO TIMES and immediately release the
button. Return (Return) appears.
14) Press the EDIT (TEST) button two times. Probe (Probe) will appear flashing on the display.
15) Press the GROUP SELECT (TANK SELECT) button until Return (Return) appears flashing.
16) Press the ► (MODE) button one time. Config (Config) appears.
17) Press the EDIT (TEST) button until Return (Return) appears flashing.
18) Press the ► (MODE) button one time. The system returns to normal operating mode.
DWG NO. 20045 REV. N/C
EDI T ENABLE/
THEFT ALARM
ACKN OW LED GE
ACKNOWLEDGE
THEFT ALARM
EDIT ENABLE/
PUSH UP AND
RELEASE
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 12 of 24 November 21, 2017
TMS Front Panel Navigation Chart
Figure 7A - TMS Front Panel Navigation Chart - Legend
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 13 of 24 November 21, 2017
Figure 7B - TMS Front Panel Navigation Chart - All menus except Configuration
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 14 of 24 November 21, 2017
Figure 7C - TMS Front Panel Navigation Chart - Configuration menu only
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 15 of 24 November 21, 2017
TMS Wiring Diagrams
Figure 8 - TMS AC Power Wiring
PNEUMERCATOR
Liquid Level Control Systems
Bulletin 172 Rev. A (01/19/07) Page 1 of 1
IMPORTANT! LC2000 AND TMS SERIES GROUND WIRING INSTRUCTIONS
NOTE:
ALL GROUNDS MUST BE TERMINATED AT THE GND BUSS BAR IN THE SAME SERVICE PANEL AS LC2000
AND/OR TMS POWE R. A G ROUNDING ROD, COLDWAT ER PIPE OR OTHER CONNECTION SHOULD NOT BE
USED.
BREAKER 6
BREAK ER 5
BREAK ER 4BREAK ER 3
BREAKER 2
BREAK ER 1
GND BUSS BAR
NEUTRAL
BUSS BAR
LINE 2 BUSS
BAR
LINE 1 BUSS
BAR
PARTIAL VIEW OF A TYPICAL
SERVICE PANEL
NEUT
GND
ISGND
ISGND
HOT
PARTIAL VIEW OF
LC2000/TMS CONSOLE
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 16 of 24 November 21, 2017
Figure 9 - TMS Probe Wiring
Page 1 of 1
IMPORTANT! PROBE WIRING INSTRUCTIONS - MODELS TMS2000/TMS3000/TMS4000
PNEUMERCATOR
Liquid Level Control Systems
NON-INTRINSICALLY SAFE WIRING
INTRINSICALLY SAFE WIRING
HAZARDOUS AREA
CLASS 1, GROUPS C,D
NON-HAZARDOUS AREA
CONDUIT AND VAPOR SEAL FITTING
(SIZE AND LOCATION TO BE
DETERMINED BY QUALIFIED INSTALLER) REDUCER FITTING
(IF NEEDED)
JUNCTION BOX
(PROVIDED BY
INSTALLER)
1/2" NPT OR EQUIV. CABLE GRIP
REQ'D ONLY ON MP45xS MODELS
(JUNCTION BOX MOUNTS DIRECTLY
TO PROBE ON MP46xS MODELS)
WIRE SPLICE SEAL CONNECTOR (BY PCO *)
FOLLOW SUPPLIED WIRE SPLICE INSTRUCTIONS
BULLETIN 179; KIT P/N 10585-2 (FOR MP46xS)
BULLETIN 181; KIT P/N 10585-2L (FOR MP45xS) FIELD WIRING CABLE (BY CUSTOMER)
EXAMPLE: BELDEN 8441, AVAILABLE
FROM PCO * AS CW1-0500 (500' SPOOL)
TMS CONSOLE
TYPICAL
TANK
W/ PROBE
GRN
RED
BLK
FIELD CABLE
Note for all probe models:
Conductor colors may vary
depending on cable manufacturer.
The field cable shield wire must
be connected to the PROBE
SHIELD TERMINAL in the console
I.S. compartment and should be cut
back and left unterminated at the
probe junction box.
WHT
BLK
GND
STUD
TO
TO
TO
TMS2000 PROBE INPUT WIRING TMS3000/TMS4000 PROBE INPUT WIRING
+V
+V
SIG
GND
SHD
GND
+V
2
1
SHD
BLK
RED
C
H
A
N
N
E
L
1
S
E
N
S
O
R
S
P
R
O
B
E
PROBE 2
SHIELD
GND
+V
SHIELD
GND
+V
SHD
BLK
RED
PROBE 1
TYPICAL WIRING FOR TMS CONSOLES
* "PCO" REFERS TO PNEUMERCATOR COMPANY.
FROM
PROBE
TO CONSOLE
(AS SHOWN ABOVE)
3/4" NPT (TMS2000)
1" NPT (TMS3000/TMS4000)
OR EQUIVALENT
CONDUIT FITTING
WIRING MUST BE DONE IN WATERTIGHT RATED BOX/HOUSING
PROBE MODELS
COVERED BY THIS BULLETIN
MP461SC
MP461S[A], [V]
MP462S[A], [V]
MP463S[A], [V]
MP450S
MP451S
MP452S
Refer to TMS installation manual for
WARNINGS and CAUTIONS before
proceeding. FAILURE TO COMPLY
MAY RESULT IN PERSONAL INJURY,
PROPERTY LOSS AND EQUIPMENT
DAMAGE.
WARNING
MP45xS
RED
BLK
RED
BLK
TO
TO
MP46xS
Bulletin 199 Rev. B (03/25/16)
!
Page 1 of 1
IMPORTANT! PROBE WIRING INSTRUCTIONS - MODELS TMS2000/TMS3000/TMS4000
PNEUMERCATOR
Liquid Level Control Systems
NON-INTRINSICALLY SAFE WIRING
INTRINSICALLY SAFE WIRING
HAZARDOUS AREA
CLASS 1, GROUPS C,D
NON-HAZARDOUS AREA
CONDUIT AND VAPOR SEAL FITTING
(SIZE AND LOCATION TO BE
DETERMINED BY QUALIFIED INSTALLER) REDUCER FITTING
(IF NEEDED)
JUNCTION BOX
(PROVIDED BY
INSTALLER)
1/2" NPT OR EQUIV. CABLE GRIP
REQ'D ONLY ON MP45xS MODELS
(JUNCTION BOX MOUNTS DIRECTLY
TO PROBE ON MP46xS MODELS)
WIRE SPLICE SEAL CONNECTOR (BY PCO *)
FOLLOW SUPPLIED WIRE SPLICE INSTRUCTIONS
BULLETIN 179; KIT P/N 10585-2 (FOR MP46xS)
BULLETIN 181; KIT P/N 10585-2L (FOR MP45xS) FIELD WIRING CABLE (BY CUSTOMER)
EXAMPLE: BELDEN 8441, AVAILABLE
FROM PCO * AS CW1-0500 (500' SPOOL)
TMS CONSOLE
TYPICAL
TANK
W/ PROBE
GRN
RED
BLK
FIELD CABLE
Note for all probe models:
Conductor colors may vary
depending on cable manufacturer.
The field cable shield wire must
be connected to the PROBE
SHIELD TERMINAL in the console
I.S. compartment and should be cut
back and left unterminated at the
probe junction box.
WHT
BLK
GND
STUD
TO
TO
TO
TMS2000 PROBE INPUT WIRING TMS3000/TMS4000 PROBE INPUT WIRING
+V
+V
SIG
GND
SHD
GND
+V
2
1
SHD
BLK
RED
C
H
A
N
N
E
L
1
S
E
N
S
O
R
S
P
R
O
B
E
PROBE 2
SHIELD
GND
+V
SHIELD
GND
+V
SHD
BLK
RED
PROBE 1
TYPICAL WIRING FOR TMS CONSOLES
* "PCO" REFERS TO PNEUMERCATOR COMPANY.
FROM
PROBE
TO CONSOLE
(AS SHOWN ABOVE)
3/4" NPT (TMS2000)
1" NPT (TMS3000/TMS4000)
OR EQUIVALENT
CONDUIT FITTING
WIRING MUST BE DONE IN WATERTIGHT RATED BOX/HOUSING
PROBE MODELS
COVERED BY THIS BULLETIN
MP461SC
MP461S[A], [V]
MP462S[A], [V]
MP463S[A], [V]
MP450S
MP451S
MP452S
Refer to TMS installation manual for
WARNINGS and CAUTIONS before
proceeding. FAILURE TO COMPLY
MAY RESULT IN PERSONAL INJURY,
PROPERTY LOSS AND EQUIPMENT
DAMAGE.
WARNING
MP45xS
RED
BLK
RED
BLK
TO
TO
MP46xS
Bulletin 199 Rev. B (03/25/16)
!
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 17 of 24 November 21, 2017
Figure 10 - TMS2000 Sensor Wiring
Liquid Level Control Systems
PNEUMERCATOR
Bulletin 173 Rev. A (11/01/07) Page 1 of 1
IDENTIFY THE TYPE OF SENSOR(S) TO BE INSTALLED. WIRING MUST BE TERMINATED ON THE
TERMINALS INDICATED BELOW TO ENSURE CORRECT OPERATION.
IMPORTANT! TMS2000 SENSOR WIRING INSTRUCTIONS
2-WIRE SENSORS
3-WIRE SENSORS
+V
SRED
BLK
W
I
R
I
N
G
HS100-ND
M
O
D
E
L
RSU800
(NON-DISCRIMINATING)
RSU801
NOTE : CONDUCTOR COLOR PAIR PER
SWITCH POINT. REFER TO THE TAG
ATTACHED TO THE SENSO R.
LS600
LS600 LD / LS610
+V
SGRN
BLK
ES825-200 SERIES
ES825-100 SERIES
M
O
D
E
L
HS100D
RSU800
(DISCRIMINATING)
RED
BLK
WHT OR GRN
RED
WHT OR GRN
BLK
*
GRN
RED
BLK
W
I
R
I
N
G
Questions? Contact Technical Support at (800) 209-7858
+V
S
+V
S
+V
S
+V
S
+V
S
* RED IS COMMON GROUND WIRE
NOTE: "S" = SIGNAL AND IS CONSECUTIVELY NUMBERED "S1"
THROUGH "S8" ON THE TMS2000 CIRCUIT BOARD
NOTE: "S" = SIGNAL AND IS CONSECUTIVELY NUMBERED "S1"
THROUGH "S8" ON THE TMS2000 CIRCUIT BOARD
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 18 of 24 November 21, 2017
Figure 11A - TMS3000 Sensor Wiring
Liquid Level Control Systems
PNEUMERCATOR
Bulletin 174 Rev. B (12/07/15) Page 1 of 2
IDENTIFY THE TYPE OF SENSOR(S) TO BE INSTALLED. WIRING MUST BE TERMINATED ON THE
TERMINALS INDICATED BELOW TO ENSURE CORRECT OPERATION.
IMPORTANT! TMS3000/TMS4000 SENSOR WIRING INSTRUCTIONS
2-WIRE SENSORS
3-WIRE SENSORS
Questions? Contact Technical Support at (800) 209-7858
BLK
RED
GND
SIG
+V
RSU801
NOTE: LS600 SUPPLIED WITH
CONDUCTOR COLOR PAIR PER
SWITCH POINT. REFER TO THE
TAG ATTACHED TO THE SENSOR.
LS600
LS600LD / LS610 BLK
RED
+V
SIG
4-PROBE/8-SENSOR
CARD WIRING
MODEL 16-SENSOR
CARD WIRING
GND
SIG
+V
ES825-200 SERIES
ES825-100 SERIES
+V
SIG
RED
W OR G
BLK
RED
W OR G
BLK
MODEL
16-SENSOR
CARD WIRING
4-PROBE/8-SENSOR
CARD WIRING
RED
BLK
W OR G
GND
SIG
+V
+V
SIG
GND
RED
BLK
W OR G
+V
SIG
+V
SIG
GRN
RED
BLK
+V
SIG
+V
SIG
GRN
RED
BLK
GND
SIG
+V
+V
SIG
GND
"W" = WHITE; "G" = GREEN
*
*
"W" = WHITE; "G" = GREEN
* RED IS COMMON GROUND WIRE
SEE PAGE 2 FOR TMS3000 SENSOR NUMBERING SEQUENCE
NOTE THE REVERSE ORDERING OF SENSOR INPUT NAMES
HS100D
(NON-DISCRIMINATING)
HS100D
(DISCRIMINATING)
RSU800
(DISCRIMINATING)
HS100ND
FIELD CABLE CONDUCTOR COLORS SHOWN.
FIELD CABLE CONDUCTOR COLORS SHOWN.
FIELD CABLE CONDUCTOR COLORS SHOWN.
RSU800
(NON-DISCRIMINATING)
FIELD CABLE CONDUCTOR COLORS SHOWN.
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 19 of 24 November 21, 2017
Figure 11B - TMS3000 Sensor Wiring
Bulletin 174 Rev. B (12/07/15) Page 2 of 2
GROUP 3
GROUP 2
(2)
16-SENSOR
CARDS
(1)
4-PROBE/
8-SENSOR
CARD
(2)
4-PROBE/
8-SENSOR
CARDS
(1)
16-SENSOR
CARD
(3)
4-PROBE/
8-SENSOR
CARDS
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
1
2
3
4
5
6
7
8
NUMBERING
NUMBERING
NUMBERING
GROUP 1
8
7
6
5
4
3
2
1
9
10
11
12
13
14
15
16
24
23
22
21
20
19
18
17
SENSOR 16
SENSOR 15
SENSOR 14
SENSOR 13
SENSOR 12
SENSOR 11
SENSOR 10
SENSOR 9
SENSOR 8
SENSOR 7
SENSOR 6
SENSOR 5
SENSOR 4
SENSOR 3
SENSOR 2
SENSOR 1
SENSOR 1
SENSOR 2
SENSOR 3
SENSOR 4
SENSOR 5
SENSOR 6
SENSOR 7
SENSOR 8
SENSOR 9
SENSOR 10
SENSOR 11
SENSOR 12
SENSOR 13
SENSOR 14
SENSOR 15
SENSOR 16
SENSOR 16
SENSOR 15
SENSOR 14
SENSOR 13
SENSOR 12
SENSOR 11
SENSOR 10
SENSOR 9
SENSOR 8
SENSOR 7
SENSOR 6
SENSOR 5
SENSOR 4
SENSOR 3
SENSOR 2
SENSOR 1
C
H
4
PROBE
SENSOR 1
SENSOR 2
C
H
3
PROBE
SENSOR 1
SENSOR 2
C
H
2
PROBE
SENSOR 1
SENSOR 2
SENSOR 2
SENSOR 1
PROBE
C
H
1
PROBE
SENSOR 1
SENSOR 2
SENSOR 2
SENSOR 1
PROBE
SENSOR 2
SENSOR 1
PROBE
SENSOR 2
SENSOR 1
PROBE
PROBE
SENSOR 1
SENSOR 2
PROBE
SENSOR 1
SENSOR 2
PROBE
SENSOR 1
SENSOR 2
SENSOR 2
SENSOR 1
PROBE
PROBE
SENSOR 1
SENSOR 2
PROBE
SENSOR 1
SENSOR 2
PROBE
SENSOR 1
SENSOR 2
SENSOR 2
SENSOR 1
PROBE
PROBE
SENSOR 1
SENSOR 2
SENSOR 2
SENSOR 1
PROBE
SENSOR 2
SENSOR 1
PROBE
SENSOR 2
SENSOR 1
PROBE
PROBE
SENSOR 1
SENSOR 2
PROBE
SENSOR 1
SENSOR 2
PROBE
SENSOR 1
SENSOR 2
SENSOR 2
SENSOR 1
PROBE
C
H
4
C
H
3
C
H
2
C
H
1
C
H
4
C
H
3
C
H
2
C
H
1
C
H
4
C
H
3
C
H
2
C
H
1
C
H
4
C
H
3
C
H
2
C
H
1
C
H
4
C
H
3
C
H
2
C
H
1
Quick Start-up Guide TMS Series
TMS Quick Start-up Guide.docx Page 20 of 24 November 21, 2017
Figure 12A - TMS Series to RA200KR Wiring
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Pneumercator TMS2000 Quick Start Up Manual

Type
Quick Start Up Manual

Pneumercator TMS2000 is a factory preprogrammed liquid level control system. It can be used to measure and display product and water levels in various tank types. It can also be used for alarm indication and control functions. The TMS2000 is easy to install and use, and it comes with a variety of features that make it a valuable tool for managing tank levels.

Here are some of the key features of the TMS2000:

  • Preprogrammed for quick and easy setup
  • Can be used to measure and display product and water levels in various tank types
  • Can be used for alarm indication and control functions
  • Easy to install and use

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI