Eaton US-S ESF30 SOU2 Mounting And Operating Instructions

Type
Mounting And Operating Instructions
Mounting and Operating Instructions US-S ESF30
Mounting and Operating Instructions
Fire-Resistant Cabinet Type US-S ESF30
Target group: qualified electricians according to DIN VDE 0105 Part 1
Target group. part 2: Electrical instucted persons
2
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
Content
Content
1 Important information ...................3
1.1 General ............................3
1.2 Key to symbols ......................3
1.3 Information for the mounting
and installation instructions ............3
1.4 Applicable documents ................3
1.5 Liability, warranty, and transfer
of custody declaration ................3
1.6 Copyright ...........................4
1.7 Spare parts .........................4
1.8 Disposal ...........................4
2 Safety ................................4
2.1 Approved use .......................4
2.2 Contents of the mounting and
installation instructions ................4
2.3 Changes and alterations to the equipment 5
2.4 Responsibility of the operating entity .....5
2.5 Personnel requirements ...............5
2.6 Work safety ........................5
3 Technical Data ..........................5
4 Layout ................................6
4.1 US-S ESF30 28-P ....................6
4.1.1 Components US-S ESF30 28-P .........6
4.1.2 Dimensioned drawings US-S ESF30 28-P . 6
4.1.3 Detail drawings for ventilation
equipment US-S ESF30 28-P ...........6
4.2 US-S ESF30 13-P ....................7
4.2.1 Components US-S ESF30 13-P ..........7
4.2.2 Dimensioned drawings US-S ESF30 13-P . 7
4.2.3 Detail drawings for ventilation
equipment US-S ESF30 13-P ...........7
4.3 US-S ESF30 SOU5 ...................8
4.3.1 Components US-S ESF30 SOU5 ........8
4.3.2 Dimensioned drawings US-S ESF30 SOU5 8
4.4 US-S ESF30 SOU3 ...................8
4.4.1 Components US-S ESF30 SOU3 ........8
4.4.2 Dimensioned drawings US-S ESF30 SOU3 8
4.5 US-S ESF30 SOU2 ...................9
4.5.1 Components US-S ESF30 SOU2 ........9
4.5.2 Dimensioned drawings US-S ESF30 SOU2 9
4.6 US-S ESF30 SOU1 ...................9
4.6.1 Components US-S ESF30 SOU1 ........9
4.6.2 Dimensioned drawings US-S ESF30 SOU1 9
5 Transport .............................10
5.1 Brief notes about important transport
considerations ......................10
5.2 General transport requirements ........10
6 Assembly/installation US-S ESF30 28-P und
13-P 11
6.1 Assembly/installation ................11
6.2 Opening and closing the door(s) ........11
6.3 Instructions for unhinging the doors .....11
6.4 Fixing the hanging brackets onto the
rear of the enclosure. . . . . . . . . . . . . . . . . 11
6.5 Choosing the wall plugs ..............11
6.6 EHL/ESL wall fixing ..................11
6.7 Switching the door swing US-S ESF30
28-P and 13-P ......................12
6.8 Setup conditions for fire
protection enclosures ................12
6.9 Special features US-S ESF30 28-P
and 13-P ..........................12
6.10 Delivered scope ....................12
6.11 Function check, technical safety
inspection, maintenance and care ......12
6.12 Cable routing in the distribution cabinet ..13
6.13 Pedestal installation .................13
7 Dismantling of the fan unit .............13
6 Setup and installation .................13
6.3 Instructions for unhinging the doors .....13
8 Ventilation diagram .....................14
9 EBEL-VENT-L230 fan ....................14
10 Ventilation unit: technical data ..........15
11 Connection plan ......................16
9 Setup and installation US-S ESF30 SOU5,
SOU3, SOU2, SOU1 ......................17
9.1 Wall-mounted installation .............17
9.2 Feeding the cables ..................17
Attention!
Tipping hazard
3
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
1 Important information
1 Important information
1.1 General
Mounting work must always be performed by qualified
electricians (also refer to DIN VDE 0105 Part 1, the German
Accident Prevention Regulations in BGV A3 issued by the
Association of Commercial and Industrial Workers' Com-
pensation Insurance Carriers [Berufsgenossenschaft] or
equivalent regulations and guidelines of the country where
the equipment is installed and operated). Other persons
are only authorised to perform the work described in these
instructions when
they have received appropriate subject matter and techni-
cal instructions,
their tasks and activities have been precisely defined and
understood,
the activities are carried out under the supervision of
specialists and experts.
Please observe:
the accident prevention guidelines and workplace directive,
the instructions issued by the technical regulatory agency,
DIN4102 to assess fire safety and structural/technical
aspects,
the technical specifications in our catalogue or datasheet,
the proper condition of the products.
Comply with the general building law and the building
requirements.
Comply with the corresponding standards to evaluate fire
protection and building aspects
Screw connections for the framework may only be made
using approved, suitable screws/dowels.
The suitability of the screws/dowels must be checked for
the specific framework.
If the cabinet has not yet been bolted to the building struc-
ture, the stability of the equipment is compromised when
the door is open.
The doors must be kept closed when the equipment is in
operation.
Improper installation can compromise the safety functions.
Only approved and appropriate screws/dowels must be
used as fasteners to the building structure. The suitability
of screws/dowels must be determined specifically for each
building.
The enclosures must not be painted or coated otherwise;
stickers are prohibited. The enclosure body must not be
damaged (drilling holes, screws). The locking systems must
not be modified or replaced.
When working with these mounting and installation instruc-
tions, the following instructions highlighted with an attention
symbol and a keyword must be specifically observed.
1.2 Key to symbols
Important technical safety information in these operating
instructions is designated by symbols.
NOTE:
Provides important tips and pointers on procedures, or for
handling the described equipment or plant components.
ATTENTION!
Calls attention to hazards that can cause damage to equip-
ment or plant components, or can result in environmental
damage.
WARNING!
Calls attention to hazards that can result in bodily injuries or
cause serious damage to equipment or plant components,
or can result in serious environmental damage.
DANGER!
Calls attention to hazards that can cause life threatening
injuries or serious damage that represents a direct danger
for people or the environment.
WARNING!
The figures in these mounting and installation instructions
are partly for the purpose of illustrating the descriptions.
Any time
exact measurements or
accurately modified drawings to reflect local conditions
are required, any drawings specifically prepared for the
installation must be bindingly observed.
WARNING!
Only perform work for which you have sufficient trade quali-
fications, and for which you have been briefed on the local
operating conditions.
Whenever enhancements, modifications, maintenance, or
work not described in this manual are required, these must
be performed by specifically trained specialists and service
personnel (either from CEAG as the manufacturer or sales
and service companies authorised by CEAG)!
1.3 Information for the mounting and installa-
tion instructions
Please store these mounting and installation instructions in
a safe place - they are an integral component of the supplied
mains distribution cabinet. Safe and approved function can
only be assured if this manual is adhered to.
1.4 Applicable documents
The mounting and installation instructions for the central
battery systems ZB-S must be observed in addition to the
mounting and installation instructions.
1.5 Liability, warranty, and transfer of cus-
tody declaration
In order to ensure optimum functionality of our products,
the mounting instructions must be observed without
exception.
CEAG's warranty covers the supplied products.
Modifications or changes of the design are only author-
4
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
2 Safety
ised in consultation with CEAG. The approval / warranty is
otherwise null and void.
The installation contractor shall supply the warranty for
the assembly work.
Warranty and liability claims for bodily injury or property
damage are excluded when these are attributable to one
or several of the following causes:
Fire protection enclosures are not used as intended.
Inappropriate installation, commissioning, operation, and
maintenance.
Non-compliance with instructions regarding transport,
storage, operation, and maintenance.
Unauthorised structural modifications on fire protection
enclosures.
Inadequate monitoring of installed safety features, im-
proper repairs.
Catastrophic failures due to third-party influences and
force majeure.
Industrial property rights
Utility patents were filed with the German patent office to
protect innovations and the design.
General
We expressly reserve the right – also without separate no-
tice – to make technical changes designed to improve the
enclosures or to comply with changes in the law.
All the information and instructions in these mounting and
installation instructions were drawn up in accordance with
the valid provisions, the latest state of technology and our
long-term knowledge and experience. The mounting and
installation instructions must be stored in the immediate vi-
cinity of the equipment, and must be accessible at all times to
persons who work on or with the equipment. These mounting
and installation instructions must be read thoroughly before
beginning work of any kind on or with the equipment!
1.6 Copyright
These mounting and installation instructions must be treated
confidentially. They are strictly intended for use by persons
working on or with the equipment. All the material informa-
tion, texts, drawings, pictures and other illustrations are
protected within the meaning of copyright law.
1.7 Spare parts
Only use the manufacturer's original replacement parts.
Incorrect or faulty spare parts can result in damage, malfunc-
tions, or a complete failure of the equipment.
In the event of the use of unauthorised replacement parts
all the guarantee, service, compensation and liability claims
become null and void.
1.8 Disposal
Unless a return or disposal agreement was concluded, dis-
mantled components must be recycled after having been
properly disassembled.
2 Safety
At the time of its development and production, the device
was manufactured in accordance with the recognised techni-
cal rules and is deemed to be operationally safe.
However, the equipment could be dangerous if is not used
by specially trained personnel, if it is used for purposes for
which it is not intended or if it is used incorrectly.
The special regulations on pages 2 – 6 in this manual must
be observed.
The standards and regulations issued by VDE and DIN must
be observed.
You must ensure:
that the codes issued by fire protection authorities are
observed and adhered to;
that the codes issued by construction oversight agencies
are adhered to;
that the codes in the technical construction codes for your
state are observed - you must review the sample cable
installation guidelines [Musterleitungsanlagen Richtlinie
- MLAR];
that the fire resistance duration and structural integrity
of the fire wall on which the equipment is installed is not
compromised by attaching the enclosure;
that the enclosure has no signs of damage, e.g. cracks or
dislocated insulation;
that the enclosure is closed at all times when in operation;
that the door swing is kept free of obstructions at all times;
that the stability of the enclosure is ensured. Damage or
malfunctions on the enclosure must be repaired by CEAG
authorised staff;
that the additional instructions in the respectively latest
prospectus are adhered to. The regulations in the general
construction oversight permit Z-86.1-46 regarding the lay-
out, mounting, cable feed, etc. must be observed.
2.1 Approved use
The fire resistant cabinet, Type US-S ESF-E30, is used as a
battery-supported monitoring and power supply device for
the safety lighting. It must only:
be used as intended, and
be operated in impeccable safety-technical condition.
The enclosures consist of coated, non-metallic, plate-shaped
components, and are coloured light-gray (similar to RAL7035)
on the outside. The edges have a contrasting colour.
These operating instructions must be accurately observed
when working with these products and to correctly handle
the cable grommet.
Any other uses are not approved. CEAG Notlichtsysteme
GmbH is not liable for any resulting damage and any resulting
consequential damage.
2.2 Contents of the mounting and installation
instructions
Any person authorised to carry out work on or with the
equipment must have read and understood the operating
5
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
2 Safety
been trained in possible hazards that may occur. A qualified
person is anyone who, based on his/her training, expertise
and experience as well as his/her knowledge of the relevant
provisions, is able to assess the work that he/she has been
given and to identify any potential hazards.
2.6 Work safety
Following the safety information and instructions provided in
this operating manual is essential to avoid bodily injuries and
property damage while working on and with the equipment.
instructions before commencing work on the equipment.
This also applies if the person concerned has worked with
the same or similar equipment in the past or was trained by
the manufacturer.
2.3 Changes and alterations to the equip-
ment
In order to avoid hazards and to ensure the best possible
performance, no modifications, retrofits and add-ons are
permitted on the equipment unless these were expressly
approved by the manufacturer.
2.4 Responsibility of the operating entity
These operating instructions must be kept in the direct
vicinity of the equipment and must always be accessible to
people working on or with the equipment. The equipment
must only be operated if it is in an exemplary and operationally
safe condition. The equipment must be checked every time
before it is put into operation. The operating instructions as
set out in the manual must be complied with in full!
2.5 Personnel requirements
Only authorised and qualified personnel may carry out
work on or with the device. These personnel must have
Tabelle 1: Technical Data
Type
US-S ESF30
28-P
US-S ESF30
13-P
US-S ESF30
SOU5
US-S ESF30
SOU3
US-S ESF30
SOU2
US-S ESF30
SOU1
Approvals / Certificates DIBT DIBT VDE VDE VDE VDE
Fire exposure from out-
side (min)
30 30 30 30 30 30
Enclosure specifications
Enclosure Fibre plates Fibre plates External fibre
plates / Internal
plastic
External fibre
plates / Internal
plastic
External fibre
plates / Internal
plastic
External fibre
plates / Internal
plastic
Protection rating IP42 IP42 IP65 IP65 IP65 IP65
Protection class l l l l l I
Dimensions
(W x H x D in mm)
2064 x 914 x 604 1198 x 898 x 449 1140 x 400 x 230 840 x 400 x 230 690 x 400 x 230 535 x 396 x 230
Weight (kg) empty cabinet 330
187 81 61 51 35
Closure Sash fastener Sash fastener Sash fastener Sash fastener Sash fastener Sash fastener
Electronic specifications
Rated voltage 400 V 50 Hz 230 V 50 Hz 230 V 50 Hz 230 V 50 Hz 230 V 50 Hz 230 V 50 Hz
Number of module slots 30 13 5 3 2 1
Max. conductor size /
final circuits (mm²)
4 4 4 4 4 4
Max. conductor size (mm²) 35 35 10 10 10 10
Max. total conductor
size (mm²)
775 625 89 79 74 39
3 Technical Data
6
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
4 Layout
918 36,14
2068 81,42
596 23,46
2068
918
596
918 36,14
2068 81,42
596 23,46
2068
918
596
1
Terminal block
2
Thermostatic control of
internal temperature
3
Thermostatic control of
external temperature
4
Web module
5
DLS module
6
Thermostatic control /
temperature exceeded
7
Control module CU CG-S
8
DC module
9
Circuit switch-overs
SKU CG-S
1
2 4
3
5
8
7
6
9
4.1 US-S ESF30 28-P
4.1.1 Components US-S ESF30 28-P
4.1.2 Dimensioned drawings US-S
ESF30 28-P
4.1.3 Detail drawings for ventilation
equipment US-S ESF30 28-P
4 Layout
918 36,14
2068 81,42
596 23,46
2068
918
596
1
Terminal for external ventilation
1
7
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
4 Layout
1
Terminal block
2
Thermostatic control of
internal temperature
3
Thermostatic control of
external temperature
4
Web module
5
DLS module
6
Thermostatic control /
temperature exceeded
7
Control module CU CG-S
8
DC module
9
Circuit switch-overs
SKU CG-S
4.2 US-S ESF30 13-P
4.2.1 Components US-S ESF30 13-P
4.2.2 Dimensioned drawings US-S
ESF30 13-P
449 1198
898
449 1198
898
449 119 8
898
8
7
6
5
4
3
2
1
9
8
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
4 Layout
4.3 US-S ESF30 SOU5
4.3.1 Components US-S ESF30 SOU5
4.4 US-S ESF30 SOU3
4.4.1 Components US-S ESF30 SOU3
230
396
1135
4.3.2 Dimensioned drawings US-S ESF30
SOU5
230
396
1135
230
396
1135
396
230 835
4.4.2 Dimensioned drawings US-S ESF30
SOU3
396
230 835
396
230
835
1
Enclosure
2
Circuit modules
SOU CG-S 2 x 4 A
1
2
1
Enclosure
2
Circuit modules
SOU CG-S 2 x 4 A
1
2
9
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
4 Layout
4.5 US-S ESF30 SOU2
4.5.1 Components US-S ESF30 SOU2
396
230
685
4.5.2 Dimensioned drawings US-S ESF30
SOU2
396
230
685
396
230
685
1
Enclosure
2
Circuit modules
SOU CG-S 2 x 4 A
1
2
4.6 US-S ESF30 SOU1
4.6.1 Components US-S ESF30 SOU1
230
535
396
4.6.2 Dimensioned drawings US-S ESF30
SOU1
230
535
396
230
535
396
1
Enclosure
2
Circuit module
SOU CG-S 2 x 4 A
1
2
10
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
5 Transport
5 Transport
5.1 Brief notes about important transport
considerations
Note the tipping hazard during transport!
Only remove the protective foil, the protective corner pads,
or other packaging material directly at the setup location!
Note the included assembly materials on the protective
foil or the enclosure!
Never transport the equipment with doors open!
At least 2 persons must always be available when trans-
porting equipment!
When using a forklift for transport, use appropriately long
forks to match the overall dimensions.
Watch for parts that protrude or stick out.
Never step under suspended loads when using a crane
for transport.
Damage must be reported to us immediately.
The products must not be stored outdoors and must be
protected against moisture.
5.2 General transport requirements
ATTENTION!
Transport must be arranged in compliance with safety
regulations!
The enclosures US-S ESF30 28-P and 13-P are shipped
upright on the pallet.
If the packaging is damaged, the damage must be reported
to the freight forwarder in writing on the shipping ticket – a
"clean receipt" from the delivering freight forwarder excludes
acknowledgement of transportation damage. The same
applies for missing packages pursuant to the shipping ticket.
Our plates weigh approximately 65 kg per m² of surface
area. Attention: injury risk!
Open the pallet at the installation location only to prevent
damage while in transit to the installation location.
When opening the pallets, the enclosure can be damaged
when pointy or sharp objects, such as knives are used.
Please use caution!
Dispose of or reuse packaging materials in an environmen-
tally compliant manner.
If the fire protection enclosure is not immediately used or
installed, it needs to be stored in an appropriate location.
Ensure that spray water cannot form or penetrate – do
not store outdoors.
Fire protection enclosures have an integrated base with
fork pockets. The front cover must be removed for use.
Transport must be arranged in compliance with safety
regulations!
Move the enclosure upright on the transport pallet.
Only remove the tie-downs at the setup location.
If the enclosure needs to be laid down, only place it on the
full back or side surfaces in a jerk-free manner.
Do not lay the enclosure down on its door(s)!
The enclosure must be locked when doing this.
Note the considerable weight of the fire protection en-
closure.
ATTENTION!
Any damage to the equipment must be immediately reported
to us in writing!
The recipient is responsible for the receiving inspection
The shipped product and its packaging must be promptly
inspected for damage, completeness, and other anomalies.
Any identified damage must be immediately documented
(sketch, photo, description, etc.) and submitted to CEAG
Notlichtsysteme GmbH.
Unpacking
The packaging must be disposed of in an environmentally
friendly manner.
Intermediate storage
If the enclosures are not used or installed immediately,
they need to be carefully stored in a protected location. The
enclosures must not be stored outdoors.
6 Assembly/installation
US-S ESF30 28-P und 13-P
6.1 Assembly/installation
Check the fixing accessories supplied for complete-
ness:
- 2 Hanging brackets
- 1 two-way (double bit) key
- 10 countersunk screws
- 2 Senkkopfschrauben 6,0x120
6.2 Opening and closing the door(s)
Opening:
• Insert the key into the lock.
Turn the key clockwise by a quarter-turn and pull out
twist lever.
Turn twist lever upwards through 180° anticlockwise.
• Open the door.
Closing:
• Close the door and ensure that the twist lever is open.
Press the door gently and turn twist lever downwards
through 180° clockwise.
Allow the twist lever to audibly latch back into the twist
lever holder.
• Remove the key.
11
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
6 Assembly/installation US-S ESF30 28-P und 13-P
6.3 Instructions for unhinging the doors
The doors are unhinged by pushing the pins from the leafs.
For safety reasons, the door panels should always be un-
hinged by at least 2 persons.
6.4 Fixing the hanging brackets onto the rear
of the enclosure
6.5 Choosing the wall plugs
For the fastening are generally building supervision or Euro-
pean technically approved or European technical rated dowels
with steel screws, which are suitable for the purpose of use,
according to the static requirements.
The special provisions of the respective general building
supervisory or European technical approval or European
assessment shall be observed.
The choice of suitable wall plugs for masonry must be made
depending on the type of blocks (solid or perforated masonry
blocks) and the different materials such as clay brick, lime-
sandstone or normal, lightweight or cellular.
The wall plugs supplied by us are suitable for DIN masonry
and blocks.
In case of unknown masonry, plug pull-out tests must be
performed!
6.6 EHL/ESL wall fixing
The wall for mounting the enclosure on must be flat with
no unevenness!
• Align the fire enclosure horizontally on the wall.
• Mark on the predrilling marks through the hanging brackets
at the top.
• Make the holes for the enclosure fixing.
• Knock in the frame plugs.
• Attach the housing.
• If necessary, the doors must be re-hung.
Seal the connection side wall to the side of the wall with
silicone.
Ventilation openings above and below must kept free!
12
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
6 Assembly/installation US-S ESF30 28-P und 13-P
6.7 Switching the door swing
US-S ESF30 28-P and 13-P
ATTENTION:
THIS WORK MUST BE PERFORMED
BY AT LEAST 2 PERSONS!
The doors are unhinged by removing the pins from the
leafs as described above.
Unscrew leafs from enclosure and bolt to the opposite
side into the pre-drilled holes.
Unscrew leafs from door and bolt to the opposite side into
the pre-drilled holes.
Align door and insert pins.
6.8 Setup conditions for fire protection en-
closures
The floor must be level
Only suited for interior setup
Setup location must be dry and frost-free
Not suited for outdoor setup
Floor/wall must be suited (load-capacity, classification)
Before installing the enclosures, the wall specifications must
be carefully checked with respect to the high weights of the
enclosures
Verify the suitability of the included dowels (only suited for
concrete, solid bricks, solid lime sand bricks iaw. DIN !!) with
respect to the wall specifications.
The enclosure must be aligned at the final setup location.
For this purpose, the enclosure can be lifted at the corners,
and shims can be used to compensate height differences.
The enclosure must then be in a horizontally level position.
The enclosure must be secured against tipping.
Verify that the fire protection seals are undamaged.
Verify that the doors properly close when locking the enclosure.
6.9 Special features US-S ESF30 28-P and
13-P
The door swing can be changed locally – on the right side
by default.
Door can be unhinged to reduce weight for transportation
purposes.
Door locking mechanism via swivel arm with double bit
profile half-cylinder 30/10.
Profile half-cylinder 30/10 can be swapped.
Locking mechanism with push bar with 2-point locking
mechanism.
Support tab for a uniform door gap.
Cable feed-through top + bottom.
Cable partition for combined or individual feed.
Exterior attachment tabs.
Door flush with body, 180° swing angle.
Ventilation system via enclosure rear wall (EH).
Attachment locations to mount the optional mounting
system or for direct installation.
6.10 Delivered scope
Our products are shipped complete with everything nee-
ded and appropriate for installation.
The fire protection enclosures are shipped as described
in the prospectus. Available options are described in the
prospectus.
6.11 Function check, technical safety ins-
pection, maintenance and care
The fire protection enclosures must be maintained and
inspected for proper function at least once annually.
We recommend in your best interest that you conduct a
functional check (visual inspection) on a monthly basis. A
technical safety inspection can only be performed with the
required care by a qualified employee, since this requires
sufficient experienced and extensive knowledge.
Conventional, mild household cleaning agents can be used
to clean the exterior of the fire protection enclosures.
The locking mechanisms on the doors are maintenance-
free. The door hinges can be lubricated with graphite.
13
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
6 Assembly/installation US-S ESF30 28-P und 13-P
6.12 Cable routing in the distribution cabinet
Pre-drill the point where the cable is to be inserted accor-
ding to the cable diameter. Observe internal insulation,
mounting plates and fan!
Insert existing cables through the cable bulkhead of the
housing.
After inserting the cables, please fill the existing gaps with
mineral wool.
Strip cables after feeding and route as shown in Figure 5.
Figure 5
14
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
7 Dismantling of the fan unit
6.13 Pedestal installation
Install the pedestal of the ES enclosure in a manner that
locates the ventilation gap above the pedestal rail (Figure 6).
Figure 6 Ventilation gap
7 Dismantling of the fan unit
at the fire protection enclosure PRIOELEC EHL/ESL
ATTENTION:
The Following installation works have to be done by a qua-
lified electrician!
1. Disconnect the fan unit from the supply voltage taking
care about VDE 0100 230 V mains connection before
beginning to dismantle. Determine freedom from tension.
WARNING 230 V AC
Dangerous Voltage. Can cause death, heavy injuries and
property damage!
2. Disconnect and remove the temperature sensor.
Loosen the cable connection at the contacts of the termi-
nal block. Pull out the temperature-sensor with cable out
of the enclosure.
3. dismantling the fan unit:
Hold on the fan unit with one hand and loosen the two
screws (4,5 x 55 mm) at the fan with the other hand.
4. Remove the fan unit EBEL-VENT-L230 and the supply-
cable from the enclosure.
15
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
8 Ventilation diagram
8 Ventilation diagram
ATTENTION!
The black compriband is part of the ventilation system and
ensures, among other things, that only the „fresh“ supply
air comes from below at the lower/rear side. This band
must not be removed.
9 EBEL-VENT-L230 fan
The fan must be connected with 230V/AC.
EXHAUST AIR
SUPPLY AIR
Schematic diagram of the ventilation
16
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
10 Ventilation unit: technical data
10 Ventilation unit: technical data
Power supply
Operating voltage
185…230…245V/AC
50Hz
Electricity consumption 0.15A
Power 22W
Fan
Speed 2850 min-1
Air flow 164m³/h
Static pressure 8.64mmH2O
Noise level 45 dB(A)
Operating temperature -10…70°C
Thermal fuse
Protection level 77°C
Smoke detector
Light alarm Red LED
Acoustic alarm > 85dB at distance 1m
Power supply Battery 9V
Battery life 2 years
Protection IP32
Operating temperature 0…55°C
Humidity ≤ 93%
Before starting up, the batterie of the smoke detector has
to be inserted and the function has to be guaranteed!
ATTENTION/WARNING/CAUTION
Danger caused by electrical voltage
WARNING 230V AC
Dangerous Voltage. May cause death heavy body injuries
and property damage. Disconnect all poles of the device
before starting to dismantle or changing the composition.
Follow the instructions of VDE 0100 for 230 V main supply.
ENVIRONMENTAL PROTECTION:
Electrical waste products should not be disposed of with
household waste. Please recycle electrical components in
a designated location. You can get advice from your local
authority on professional recycling.
17
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
11 Connection plan
11 Connection plan
ATTENTION
Danger caused by electrical voltage
WARNING 230V AC
Dangerous Voltage. May cause death heavy body injuries
and property damage. Disconnect all poles of the device
before starting to dismantle or changing the composition.
Follow the instructions of VDE 0100 for 230 V main supply.
18
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
9 Setup and installation US-S ESF30 SOU5, SOU3, SOU2, SOU1
The unit is mounted with the included anchor screws, rated
for concrete walls at strength class C20/25 to C50/60 or ma-
sonry walls made with lime sand stone, solid, and perforated
stone bricks, and solid kiln bricks. The anchor screws are
approved for installation in cracked and non-cracked concrete.
9.2 Feeding the cables
After the enclosure is mounted on the wall, the cables are
individually guided through the appropriate opening on the
top. This involves first feeding the cables through the fire
protection foam between the exterior and interior enclosure.
Double diaphragm bushings ensure that the interior cable
lead-throughs are securely sealed.
9 Setup and installation
US-S ESF30 SOU5, SOU3, SOU2, SOU1
9.1 Wall-mounted installation
Only the dowels or anchor screws described in the "General
construction code approval" must be used for a wall-mounted
installation. The wall on which the distribution cabinet will be
installed must have sufficient load-bearing capacity. In this
case, the fire resistance of the load-bearing walls should be
at least as high as those of the distribution cabinet.
Using the included anchor screws, the US-S ESF30 can be
effortlessly screwed to the enclosure with the attachment
holes - in cracked concrete and non-cracked concrete.
A clearance of at least one meter must be maintained bet-
ween the fire protection distribution cabinet in low-voltage
operating mode and adjacent utilities, such as gas or water.
In the proximity of doors, a clearance appropriate for the door
swing must be maintained.
210
95
ø1
0
1. Mark location 2. Drill
3. Secure with screws Dimensions of hanging openings
Detailed installation drawing
19
Mounting and Operating Instructions Fire-Resistant Cabinet Type US-S ESF30 40071860245 (B) February 2020 www.ceag.de
Notes
Notes
Eaton is a registered trademark.
All other trademarks are the property of
their respective owners.
The aim of Eaton is to provide a reliable, efficient and safe
power supply where it is needed most. Eaton's experts have
comprehensive in-depth specialist knowledge in the area
of energy management in the most diverse of sectors and
therefore they are able to provide customer-specific, inte-
grated solutions to meet the most challenging demands of its
customers.
It is our highest priority always to find the right solution for
every application. Our stakeholders therefore expect more
than just innovative products. Companies turn to Eaton
because they know that individual support and the success of
our customers is always our top priority. For more information
visit www.eaton.eu.
You will find your contact partner at www.ceag.de.
Eaton Industries Manufacturing GmbH
Electrical Sector EMEA
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu
CEAG Notlichtsysteme GmbH
Senator-Schwartz-Ring 26
59494 Soest, Germany
Tel.: +49 (0) 2921 69-870
Fax: +49 (0) 2921 69-617
Web: www.ceag.de
© 2019 Eaton
All rights reserved.
Printed in Germany
Order no. 40071860245 (B)
February 2020
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20