Johnson Controls IOM3710 Installation Instructions Manual

Type
Installation Instructions Manual

This manual is also suitable for

Johnson Controls MS-IOM3710-0U is a powerful and versatile input/output module designed for use with the Metasys system. It provides increased capacity to larger Field Equipment Controller (FEC) applications when used on the Sensor-Actuator (SA) Bus. Additionally, it can be utilized on the Field Controller (FC) Bus to connect extra I/O points to the system. The MS-IOM3710-0U features universal outputs, relay outputs, universal inputs, and an SA/FC Bus port for connecting various devices such as the Wireless Commissioning Converter.

Johnson Controls MS-IOM3710-0U is a powerful and versatile input/output module designed for use with the Metasys system. It provides increased capacity to larger Field Equipment Controller (FEC) applications when used on the Sensor-Actuator (SA) Bus. Additionally, it can be utilized on the Field Controller (FC) Bus to connect extra I/O points to the system. The MS-IOM3710-0U features universal outputs, relay outputs, universal inputs, and an SA/FC Bus port for connecting various devices such as the Wireless Commissioning Converter.

IOM2710 and IOM3710 Input/Output Modules Installation Instructions 1
Applications
The Input/Output Module (IOM) 2710 and IOM3710 are
members of the Metasys® system Field Equipment
Controller (FEC) family. The IOM controller provides
increased capacity to larger FEC applications when
used on the Sensor-Actuator (SA) Bus. The IOM
controller can also be used on the Field Controller (FC)
Bus to connect additional I/O points to the system.
North American Emissions Compliance
United States
Canada
Installation
Observe the following guidelines when installing the
IOM controller:
Transport the IOM controller in the original
container to minimize vibration and shock damage
to the IOM.
Do not drop the IOM controller or subject it to
physical shock.
Materials and Special Tools Needed
You need either of the following items to install the IOM
controller:
three fasteners appropriate for the mounting
surface (#8 screws or M4 screws)
one 20.3 cm (8 in.) or longer piece of DIN rail and
appropriate hardware for mounting the DIN rail
Mounting
Follow these guidelines when mounting an IOM
controller:
Ensure that the mounting surface can support the
IOM controller and any user-supplied enclosure.
Mount the IOM controller in the proper orientation.
See the Wall Mount Applications
and DIN Rail
Mount Applications sections.
Mount the IOM controller on an even surface
whenever possible.
Use shims or washers to mount the unit securely
on the mounting surface.
Mount the IOM controller in areas free of corrosive
vapors and observe the environmental limitations
listed in the Technical Specifications
section.
IMPORTANT: In Metasys system smoke control
applications, use only the IOM2710 and IOM3720
models that are UL Listed, UUKL 864 Listed, Smoke
Control Equipment. See Repair Information
on page
8 for UUKL 864 Listed IOM2710 and IOM3710
models. For Metasys system smoke control
applications, you must refer to the Metasys System
UL 864 UUKL Ninth Edition Smoke Control System
Technical Bulletin (LIT-12011252) for detailed
requirements and procedures for installing and
operating UUKL 864 Listed Metasys system
devices. Failure to meet the requirements or follow
the procedures in the Metasys System UL 864
UUKL Ninth Edition Smoke Control System
Technical Bulletin (LIT-12011252) can void the
UUKL 864 listing for Smoke Control Equipment.
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
IOM2710 and IOM3710 Input/Output Modules
Installation Instructions
MS-IOM2710-0, MS-IOM3710-0
Part No. 24-10144-17, Rev. G
Release 5.0
Issued January 4, 2010
Supersedes October 6, 2008
IOM2710 and IOM3710 Input/Output Modules Installation Instructions2
Do not mount the IOM controller on surfaces that
are prone to vibration, such as duct work, or in
areas where electromagnetic emissions from other
devices or wiring can interfere with IOM controller
communication.
Allow sufficient space for cable and wire
connections (minimum of 51 mm [2 in.] in each
direction).
On panel or enclosure mount applications, observe
these guidelines:
Do not install the IOM controller in an airtight
enclosure.
Mount the IOM controller so that the enclosure wall
or the transformer does not obstruct ventilation of
or radiate heat into the IOM controller housing.
Wall Mount Applications
Use the holes in the mounting clips for wall mount
applications.
To mount the IOM controller on a wall or other vertical
surface:
1. Ensure that the bottom mounting clip(s) are pulled
outward and snapped firmly into the extended
position and that the top clip is securely installed
(Figure 2).
2. Mark the location of the wall mount holes using the
dimensions in Figure 3, or hold the IOM controller
up to the wall as a template and mark the locations.
Note: Mount the IOM controller horizontally for proper
airflow.
Figure 1: IOM3710 Controller Physical Features
and Wiring Terminals
FAULT
POWER
ADDRESS
ON
+15V
+5V
IN 1
ICOM 1
IN 2
ICOM 2
+15V
+5V
IN 3
ICOM 3
IN 4
ICOM 4
UNIVERSAL
COM
+
+
COM
SA
PWR
COM
HOT
OUT 7
OCOM 7
OUT 8
OCOM 8
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 4 NO
OCOM 4
OUT 4 NC
OUT 3 NO
OCOM 3
OUT 3 NC
OUT 2 NO
OCOM 2
OUT 2 NC
OUT 1 NO
OCOM 1
OUT 1 NC
ADDRESS Ø = ALL OFF
EOL
O
N
SA/FC Bus
Terminals
Status LEDs
FAULT
POWER
ADDRESS
ON
+15V
+5V
IN 1
ICOM 1
IN 2
ICOM 2
+15V
+5V
IN 3
ICOM 3
IN 4
ICOM 4
UNIVERSAL
COM
+
+
COM
SA
PWR
COM
HOT
OUT 7
OCOM 7
OUT 8
OCOM 8
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 4 NO
OCOM 4
OUT 4 NC
OUT 3 NO
OCOM 3
OUT 3 NC
OUT 2 NO
OCOM 2
OUT 2 NC
OUT 1 NO
OCOM 1
OUT 1 NC
ADDRESS Ø = ALL OFF
EOL
O
N
SA/FC Bus
Port
EOL Switch
Universal Inputs
Universal Outputs
24 VA
C
Power Terminal
Device Address
DIP Switches
Relay Outputs
FIG:IOM2710_3710_wir
R
ET SY
FA ULT
POWER
ADDRESS
ON
+
1
5
V
+
5
V
I
N
1
I
C
O
M
1
I
N
2
I
C
O
M
2
+
1
5
V
+
5
V
I
N
3
I
C
O
M
3
I
N
4
I
C
O
M
4
UNI VERSAL
C
O
M
+
+
C
O
M
S
A
P
W
R
C
O
M
H
O
T
O
U
T
7
O
C
O
M
7
O
U
T
8
O
C
O
M
8
O
U
T
5
O
C
O
M
5
O
U
T
6
O
C
O
M
6
O
U
T
4
N
O
O
C
O
M
4
O
U
T
4
N
C
O
U
T
3
N
O
O
C
O
M
3
O
U
T
3
N
C
O
U
T
2
N
O
O
C
O
M
2
O
U
T
2
N
C
O
U
T
1
N
O
O
C
O
M
1
O
U
T
1
N
C
ADDRE SS Ø = AL L OFF
EOL
O
N
R
E
T
S
Y
F
A
U
L
T
P
O
W
E
R
A
D
D
R
E
S
S
O
N
+
1
5
V
+
5
V
I
N
1
I
C
O
M
1
I
N
2
I
C
O
M
2
+
1
5
V
+
5
V
I
N
3
I
C
O
M
3
I
N
4
I
C
O
M
4
U
N
I
V
E
R
S
A
L
C
O
M
+
+
C
O
M
S
A
P
W
R
C
O
M
H
O
T
O
U
T
7
O
C
O
M
7
O
U
T
8
O
C
O
M
8
O
U
T
5
O
C
O
M
5
O
U
T
6
O
C
O
M
6
O
U
T
4
N
O
O
C
O
M
4
O
U
T
4
N
C
O
U
T
3
N
O
O
C
O
M
3
O
U
T
3
N
C
O
U
T
2
N
O
O
C
O
M
2
O
U
T
2
N
C
O
U
T
1
N
O
O
C
O
M
1
O
U
T
1
N
C
A
D
D
R
E
S
S
Ø
=
A
L
L
O
F
F
E
O
L
O
N
F
I
G
:
I
O
M
2
7
3
7
1
0
_
w
l
l
Figure 3: Required Orientation for Wall Mount
Applications
IOM2710 and IOM3710 Input/Output Modules Installation Instructions 3
3. Drill holes in the wall at the locations marked in
Step 2 and insert wall anchors (if necessary).
4. Position the IOM controller and insert the screws
through the holes in the mounting clips, and
carefully tighten all the screws.
DIN Rail Mount Applications
To mount the IOM controller on a DIN rail:
1. Securely mount the section of DIN rail horizontally
and centered in the required space.
2. Carefully pull down (outward) the bottom mounting
clips until they lock in place (Figure 4).
Note: The top mounting clip is not used on DIN
rail applications. You may remove the clip.
3. Hang the IOM controller on the DIN rails using the
DIN rail hooks on the back of the IOM controller.
4. Secure the IOM controller on the DIN rail by
pressing the bottom mounting clips up until they
snap into place.
To remove the IOM controller from the DIN rail, snap
the bottom DIN clips to the outboard position and
carefully lift the IOM controller off the DIN rail.
Wiring
Refer to the MS/TP Communications Bus Technical
Bulletin (LIT-12011034) for more information on
Master-Slave/Token-Passing (MS/TP) devices.
To wire the IOM controller:
1. Terminate wiring per engineering drawings.
2. If the IOM is connected to the FC Bus of a Network
Automation Engine (NAE) or Network Control
Engine (NCE), wire the FC Bus in a daisy chain.
IMPORTANT: Do not overtighten the mounting
screws. Overtightening the screws may damage the
mounting clips or IOM housing.
48
1-7/8()
90
3-1/2()
90
3-1/2()
143
5-5/8()
127
5()
DIN Rail
Channel
DIN Rail
Hooks
95
3-3/4()
F
I
G
:
I
O
M
2
7
1
0
_
3
7
1
0
_
m
n
t
_
d
i
m
Mounting Clips
(in Extended Positions)
48
1-7/8()
48
1-7/8
()
Figure 2: IOM2710 and 3710 Controller Mounting
Features, mm (in.)
IMPORTANT: Do not connect 24 VAC supply
power to the IOM controller before finishing wiring
and checking all wiring connections. Short circuits or
improperly connected wires may result in permanent
damage to the equipment.
IMPORTANT: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations. The IOM controller is a
low-voltage (<30 VAC) device. Do not exceed the
IOM controller electrical ratings.
IMPORTANT: Prevent any static electric discharge
to the IOM controller. Static electric discharge can
damage the IOM controller and void any warranties.
Figure 4: Required Orientation for DIN Rail
Mount Applications
FAULT
POWER
ADDRESS
ON
+15V
+5V
IN 1
ICOM 1
IN 2
ICOM 2
+15V
+5V
IN 3
ICOM 3
IN 4
ICOM 4
UNIVERSAL
COM
+
+
COM
SA
PWR
COM
HOT
OUT 7
OCOM 7
OUT 8
OCOM 8
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 4 NO
OCOM 4
OUT 4 NC
OUT 3 NO
OCOM 3
OUT 3 NC
OUT 2 NO
OCOM 2
OUT 2 NC
OUT 1 NO
OCOM 1
OUT 1 NC
ADDRESS Ø = ALL OFF
EOL
O
N
FIG:IOM273
710_DIN
IOM2710 and IOM3710 Input/Output Modules Installation Instructions4
3. If the IOM is connected to the SA Bus of an NCE or
FEC, wire the SA Bus in a daisy chain (Figure 6).
Note: The SA/FC Bus Port (RJ-12 6-position
modular connector) provides 15 VDC on one of its
pins, which is used to power the MS-BTCVT.
Note: If the IOM controller is at one end of the SA
Bus daisy chain, set the End-of-Line (EOL) switch
to ON.
4. Connect power to the IOM controller.
5. Download and commission the IOM controller. See
the Commissioning
section.
SA/FC Bus Port
The SA/FC Bus port on the front of the IOM is an
RJ-12, 6-position modular jack that provides a
connection for the Wireless Commissioning Converter.
See Table 1 for more information. The SA/FC Bus Port
pin assignment is shown in (Figure 7).
Figure 5: FC Bus Terminal Block Wiring
Stranded 3-Wire Twisted Shielded Cable
+
_
COM
SHLD
To Next
Device on
Block Plugs
s
Stranded, 4-Wire (2 Twisted Pair) Shielded Cable
(One twisted pair is the and leads.
The second pair is COM and SA PWR.)
+ -
Cable Shield
Connection
To Next
Device on
the SA Bus
FIG:sa_bus_terms
SA Bus
Terminal
Block Plugs
Terminating Device
on SA Bus
Daisy Chained Device
on SA Bus
To Next
Device on
the SA Bus
+
COM
SA PWR
+
CO
M
SA
PWR
Figure 6: SA Bus Terminal Block Wiring
Figure 7: Pin Number Assignments for
Sensor, SA Bus, and FC Bus Ports on
FEC, IOM, and VMA16
Power
(15 VDC)
SA or FC Bus +
SA or FC Bus
-
Bus and Power Common
Power
(15 VDC)
Sensor, SA Bus, or FC Bus Port
(RJ-12 Modular Jack)
Bus and Power Common
FIG:RJ_pinout
2
3
4
5
6
1
IOM2710 and IOM3710 Input/Output Modules Installation Instructions 5
Table 1: IOM2710 and IOM3710 Controller Wiring List (Part 1 of 2)
Terminal
Block
1
Terminal
Labels
Function and Electrical Ratings/Requirements Wiring Requirements
(See Table 2 for A, B, or C.)
Universal IN +5 V Sources 5 VDC power for active devices
60 mA total current
Same as IN
+15 V Sources 15 VDC power for active devices
35 mA total current
Same as IN
IN n Analog Input, Voltage Mode
Accepts a 0-10 VDC input signal.
10 VDC Maximum Input Voltage
Internal 75k ohm Pulldown
A
Analog Input, Current Mode
Accepts a 4-20 mA input signal.
Note: For current sensing applications, the IOM2710
and IOM3710 Controllers do not provide a jumper to
close the current loop when the controller is powered off.
This option is available on IOM4710 Controllers only.
B
Analog Input, Resistive Mode
Accepts 0-600k ohm input signal.
Internal 12 V, 15k ohm Pullup
A
Binary Input, Dry Contact Maintained Mode
1 s minimum pulse width (0.5 Hz at 50% duty cycle)
Internal 12 V, 15k ohm Pullup
A
Binary Input, Dry Contact Pulse Counter Mode
1 s minimum pulse width (0.5 Hz at 50% duty cycle)
Internal 12 V, 15k ohm Pullup
A
ICOM n The input signal common for Universal IN terminals;
isolated from all other terminal commons.
Same as IN
Universal
OUT
OUT n Analog Output, Voltage Mode
Sources 0-10 VDC output voltage
1k ohm minimum load
10 VDC maximum output voltage
10 mA maximum output current
A
Binary Output Mode
24 V AC/DC FET
Connects OUT to OCOM when activated.
30 V AC/DC maximum output voltage
0.5 A maximum output current
40 mA minimum load current (hold current)
B
Analog Output, Current Mode
Sources 4-20 mA output current
External 300 ohm maximum load required
B
OCOM n The output signal common; isolated from all other
terminal commons, including UO terminal commons.
Same as OUT
IOM2710 and IOM3710 Input/Output Modules Installation Instructions6
Relay
Output
Control
OUT NO n Normally Open Contact
Connects OCOM to OUT NO when activated.
240 VAC maximum voltage
1/3 hp 125 VAC, 1/2 hp 250 VAC
400 VA Pilot Duty @ 240 VAC
200 VA Pilot Duty @ 120 VAC
3 A Noninductive 24-240 VAC
OCOM n The relay signal common; isolated from other terminal
commons, including Relay Output terminal commons.
OUT NC n Normally Closed Contact
Connects OCOM to OUT NC when activated.
240 VAC maximum voltage
1/3 hp 125 VAC, 1/2 hp 250 VAC
400 VA Pilot Duty @ 240 VAC
200 VA Pilot Duty @ 120 VAC
3 A Non-inductive 24-240 VAC
SA/FC Bus
Port
2,3
SA/FC Bus Provides SA Bus communication network
RJ-12 6-position modular connector
30.5 m (100 ft) maximum length
phone cord
SA Bus
3
+
-
COM
Provides SA Bus communication network. Daisy-chained
366 m (1,200 ft) maximum length
0.6 to 1.5 mm
2
(18 to 24 AWG)
[22 AWG Recommended]
FC Bus
1
+
-
COM
Provides FC Bus communication network. Daisy-chained
1,524 m (5,000 ft) maximum length
0.6 to 1.5 mm
2
(18 to 24 AWG)
[22 AWG Recommended]
SHLD Provides an optional shield connection.
24~ Power Hot AC Supply Input
Supply 20-30 VAC (Nominal 24 VAC)
16 AWG
COM The 24~ Power common; isolated from all other terminal
commons.
1. The terminal block column displays all the points for the IOM3710 model.
2. The SA Bus and the SA/FC Bus are daisy-chained internally.
3. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Table 1: IOM2710 and IOM3710 Controller Wiring List (Part 2 of 2)
Terminal
Block
1
Terminal
Labels
Function and Electrical Ratings/Requirements Wiring Requirements
(See Table 2 for A, B, or C.)
IOM2710 and IOM3710 Input/Output Modules Installation Instructions 7
Wiring Requirements
Setup and Adjustments
The IOM controller can reside on either the FC Bus or
the SA Bus. When you set the address, you are setting
the address for the specified bus. The IOM controller
can only be on one bus at a time.
Determining the FC Bus or SA Bus Address
The ADDRESS DIP switch sets a unique address for
the controller (or module) on the FC Bus or SA Bus.
Set the address to 4-127 for an IOM. For best
performance, all devices on the same Bus (FC Bus or
SA Bus) should have consecutive addresses. Do not
use Addresses 128 and above when connecting the
IOM to the FC Bus or SA Bus. For more information,
refer to the MS/TP Communications Bus Technical
Bulletin (LIT-12011034).
Table 3 shows and describes the valid FC Bus and
SA Bus devices addresses for FECs and IOMs on
Johnson Controls® MS/TP communications bus
applications.
Table 2: Wire Gauge and Length Guidelines
Guideline Cable Size Maximum Length Assumptions
A
1.5 mm
(18 AWG)
457.2 m (1,500 ft) 100 mV maximum voltage drop
0.8 mm
(20 AWG)
297.2 m (975 ft)
0.6 mm
(22 AWG)
182.9 m (600 ft)
N/A (24 AWG) 106.7 m (350 ft)
B
1.5 mm
(18 AWG)
228.6 m (750 ft) 100 mV maximum voltage drop
0.8 mm
(20 AWG)
137.1 m (450 ft)
0.6 mm
(22 AWG)
91.4 m (300 ft)
N/A
(24 AWG)
61 m (200 ft)
C See Figure 8. See Figure 8. N/A
Figure 8: Maximum Wire Length by Current and Wire Size
450 500400350300250200150100
500
0 m 0 ft()
15 m 50 ft()
31 m 100 ft()
46 m (150 ft)
61 m 200 ft()
76 m 250 ft()
91 m 300 ft()
107 m 350 ft()
122 m 400 ft()
137 m 450 ft()
Load Current (mA)
C
a
b
l
e
L
e
n
g
t
h
F
I
G
_
W
I
R
_
L
N
G
T
H
1.5 mm (18 AWG)
2
0.8 mm (20 AWG)
0.6 mm(22 AWG)
N/A (24 AWG )
Table 3: FC Bus Device Address Descriptions
Device
Address
Description
0 Reserved for FC Bus supervisory controller.
1-3 Reserved for peripheral devices.
4-127 Available for FECs on the FC bus and IOMs
on the SA or FC Bus.
128 Disables (Off) or Enables (ON) a controller for
wireless operation.
129-255 Are not valid addresses for FEC or IOM
controllers on the SA or FC Bus.
IOM2710 and IOM3710 Input/Output Modules Installation Instructions8
Setting the FC Bus or SA Bus Address
For most devices on an FC Bus or SA Bus, the
(non-supervisory) device address is set using the DIP
switches on the device’s ADDRESS DIP switch block.
The DIP switch blocks are binary switch blocks and
each switch represents a binary numerical value when
the switch is set to the ON position. For example,
positioning switches 16, 4, and 1 to ON, as shown in
Figure 9, sets the device address to 21.
FC Bus or SA Bus EOL Switch
The EOL switch applies power termination to the
device’s FC Bus or SA Bus. If the IOM is at the
End-of-Line (EOL) position on the Bus, set the EOL
switch to the ON position. Otherwise, set the EOL
switch to the OFF position (Figure 10). The controller
ships with the EOL switch set in the OFF position.
Commissioning
Commission the IOM controller through the Wireless
Commissioning Converter with Bluetooth® Technology
(BTCVT) and the Controller Configuration Tool (CCT)
software. Refer to the CCT Help.
Troubleshooting
Use Table 4 to troubleshoot the IOM controller.
Repair Information
If the IOM controller fails to operate within its
specifications, replace the unit. For a replacement IOM
controller, contact the nearest Johnson Controls®
representative.
Accessories
Use Table 5 to order accessories for the IOM controller.
Figure 9: Device Address Switches Set to 21
FIG:fec_dip_swtch
128
64
32
16
8
4
2
1
ON
Note:
Switch 128 is
used to enable or
disable an FEC for
wireless operation.
Figure 10: EOL Switch Positions
FIG:E
OL_Swtch
EOL ON Position EOL Off Position
O
N
O
N
Table 4: Status Light-Emitting Diodes (LEDs)
Name Color Normal Descriptions
Power Green On Steady Off Steady = No Power
On Steady = Power is supplied by primary voltage.
Fault Red Off Steady Blink - 2 Hz = Download or startup in progress, not ready for normal operation
Off Steady = No faults
On Steady = Device fault or no application loaded
SA/FC Bus Green Blink - 2 Hz Blink - 2 Hz = Data transmission (normal communication)
Off Steady = No data transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring
Table 5: FEC/IOM Accessories (Order Separately) (Part 1 of 2)
Product Code
Number
Description
Y64T15-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 30 in. Primary
Leads and 30 in. Secondary Leads, Class 2
Y65A13-0 Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount [Y65AS], 8 in. Primary
Leads and 30 in. Secondary Leads, Class 2
Y65T42-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount [Y65SP+], 8 in.
Primary Leads and Secondary Screw Terminals, Class 2
Y65T31-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount [Y65AR+],
8 in. Primary Leads and Secondary Screw Terminals, Class 2
AP-TBK1002-0 2-position Screw Terminal that Plugs onto VMA output point Spade Lugs
AP-TBK1003-0 3-position Screw Terminal that Plugs onto VMA output point Spade Lugs
IOM2710 and IOM3710 Input/Output Modules Installation Instructions 9
Technical Specifications
AP-TBK4SA-0 Replacement MS/TP SA Bus Terminal, 4 Position Connector, Brown, Bulk Pack
AP-TBK4FC-0 Replacement MS/TP FC Bus Terminal, 4 Position Connector, Blue, Bulk Pack
AP-TBK3PW-0 Replacement Power Terminal, 3 Position Connector, Gray, Bulk Pack
MS-BTCVT-1 Wireless Commissioning Converter, with Bluetooth technology
MS-BTCVTCBL-700 Cable replacement Set for the MS-BTCVT-1 or the NS-ATV7003-0; includes one 5-foot
retractable cable.
Table 5: FEC/IOM Accessories (Order Separately) (Part 2 of 2)
Product Code
Number
Description
IOM2710 and IOM3710 Input/Output Modules (Part 1 of 2)
Product Code Numbers MS-IOM2710-0
MS-IOM3710-0
Supply Voltage 20-30 VAC at 50 or 60 Hz, Class 2 or Safety Extra Low Voltage (SELV)
Power Consumption 10 VA typical, 14 VA maximum plus all BO and Configurable Output loads
Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 70°C (-40 to 158°F); 10 to 90% RH noncondensing
Terminations Screw terminals, 3-Position Screw Terminal Pluggable Blocks, 4-Position Screw Terminal
Pluggable Blocks
Controller Addressing DIP switch set (4-127). Addresses 1-3, 128-255 are reserved.
Communications Bus BACnet® MS/TP; 3-wire FC Bus between the NAE/NCE and other devices. 4-wire SA Bus
when used as expansion to FEC.
1
Analog Input/Analog Output
Resolution and Accuracy
Analog Input: 16-bit resolution
Analog Output: 16-bit resolution and ±200 mV in 0-10 VDC applications
Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail
Dimensions
(Height x Width x Depth)
IOM2710: 180 x 127 x 58 mm (7-1/16 x 5 x 2-1/4 in.)
IOM 3710: 180 x 127 x 58 mm (7-1/16 x 5 x 2-1/4 in.)
Housing Plastic housing
Plastic material: ABS + polycarbonate UL94 5VB
Protection: IP20 (IEC529)
Weight IOM2710: 0.48 kg (1.1 lb)
IOM 3710: 0.55 kg (1.2 lb)
Published in U.S.A. www.johnsoncontrols.com
IOM2710 and IOM3710 Input/Output Modules Installation Instructions10
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Compliance United States:
UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment;
UL Listed, File S4977, UUKL 864 - 9th Edition, Smoke Control Equipment (MS-IOMx710-0U
and MS-IOU4710-0U models only)
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada:
UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada Compliant, ICES-003
Europe:
CE Mark, EMC Directive 89/336/EEC, in accordance with EN 61000-6-3 (2001) Generic
Emission Standard for Residential and Light Industry and EN 61000-6-2 (2001) Generic
Immunity Standard for Heavy Industrial Environment and the Low Voltage Directive
73/23/EEC in accordance with EN 60730-1 (1999) Automatic electrical controls for
household and similar use.
Australia and New Zealand:
C-Tick Mark, Australia/NZ Emissions Compliant
BACnet International:
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Application Specific
Controller (B-ASC)
1. For more information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
IOM2710 and IOM3710 Input/Output Modules (Part 2 of 2)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Johnson Controls IOM3710 Installation Instructions Manual

Type
Installation Instructions Manual
This manual is also suitable for

Johnson Controls MS-IOM3710-0U is a powerful and versatile input/output module designed for use with the Metasys system. It provides increased capacity to larger Field Equipment Controller (FEC) applications when used on the Sensor-Actuator (SA) Bus. Additionally, it can be utilized on the Field Controller (FC) Bus to connect extra I/O points to the system. The MS-IOM3710-0U features universal outputs, relay outputs, universal inputs, and an SA/FC Bus port for connecting various devices such as the Wireless Commissioning Converter.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI