Johnson Controls FX-PCX2721 Installation Instructions Manual

Type
Installation Instructions Manual

This manual is also suitable for

Application
The FX-PCX2721 controller is part of the Facility Explorer
FX-PC Series Programmable Controller family. FX-PCXs
expand the number of input/output points connected to
either an FX-PCA, FX-PCG, FX-PCV programmable
controller or to a supervisory controller to monitor and
control a wide variety of HVAC equipment.
FX-PCX operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus as BACnet
Application Specific Controllers (B-ASCs) and integrate
into Johnson Controls® and third-party BACnet systems.
Note: At FX-PCT Release 10.1, a new capability was
introduced allowing FX-PCVs, FX-PCGs, and
FX-PCAs to communicate by using either the
BACnet or the N2 field bus networking protocol.
The operation of the FX-PCX Input/Output Module
is not affected by the selection of the BACnet or
the N2 protocol in the host controller.
North American Emissions
Compliance
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur
du Canada.
United States
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction
manual, may cause harmful interference to radio
communications. Operation of this equipment in a
residential area may cause harmful interference, in which
case the users will be required to correct the interference
at their own expense.
Installation
Observe these guidelines when installing a controller:
Transport the controller in the original container to
minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical
shock.
Parts Included
one controller with removable terminal blocks (Power
and SA/FC bus are removable)
one installation instructions sheet
Materials and Special Tools Needed
three fasteners appropriate for the mounting surface
(M4 screws or #8 screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
small straight-blade screwdriver for securing wires in
the terminal blocks
Mounting
Observe these guidelines when mounting an FX-PCX
controller:
Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail
whenever possible.
Mount the controller in the proper mounting position.
Mount the controller on a hard, even surface
whenever possible in wall-mount applications.
Use shims or washers to mount the controller securely
and evenly on the mounting surface.
Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in Table 10.
Provide for sufficient space around the controller for
cable and wire connections for easy cover removal
and good ventilation through the controller (50 mm
[2 in.] minimum on the top, bottom, and front of the
controller).
1FX-PCX2721 Expansion Input/Output Module Installation Instructions
FX-PCX2721 Expansion Input/Output Module Installation
Instructions
FX-PCX2721-0
Part No. 24-10144-173, Rev. F
Issued August 2018
Refer to
the QuickLIT website for the most up-to-date version of this document.
Do not mount the controller on surfaces prone to
vibration, such as duct work.
Do not mount the controller in areas where
electromagnetic emissions from other devices or
wiring can interfere with controller communication.
Observe these additional guidelines when mounting a
controller in a panel or enclosure:
Mount the controller so that the enclosure walls do
not obstruct cover removal or ventilation through the
controller.
Mount the controller so that the power transformer
and other devices do not radiate excessive heat to
the controller.
Do not install the controller in an airtight enclosure.
Figure 1: Controller Mounting Positions
DIN Rail Mount Applications
Mounting the FX-PCX controller horizontal on 35 mm DIN
rail is the preferred mounting method.
To mount a controller on 35 mm DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of
35 mm DIN rail horizontal and centered in the desired
space so that the controller mounts in the horizontal
position shown in Figure 1.
2. Pull the two bottom mounting clips outward from the
controller to the extended position (Figure 2).
3. Hang the controller on the DIN rail by the hooks at
the top of the (DIN rail) channel on the back of the
controller (Figure 2), and position the controller snugly
against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure
the controller on the DIN rail.
To remove the controller from the DIN rail, pull the
bottom mounting clips out to the extended position
and carefully lift the controller off the DIN rail.
2FX-PCX2721 Expansion Input/Output Module Installation Instructions
Wall Mount Applications
To mount an FX-PCX controller directly on a wall or other
flat vertical surface:
1. Pull the two bottom mounting clips outward and
ensure they are locked in the extended position, as
shown in Figure 2.
2. Mark the mounting hole locations on the wall using
the dimensions in Figure 2 and one of the mount
positions shown in Figure 1. Or hold the controller up
to the wall or surface in a proper mount position and
mark the hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked
locations, and insert appropriate wall anchors in the
holes (if necessary).
4. Hold the controller in place, and insert the screws
through the mounting clips and into the holes (or
anchors). Carefully tighten all of the screws.
Important: Do not overtighten the mounting screws.
Overtightening the screws may damage
the mounting clips.
Figure 2: Back of Controller Showing Extended
Mounting Clips, DIN Rail Channel, and Mounting
Dimensions, mm (in.)
3FX-PCX2721 Expansion Input/Output Module Installation Instructions
Figure 3: FX-PCX2721 Physical Features
Table 1: FX-PCX2721 Physical Features Callouts and Descriptions
Physical Feature: Description and ReferencesCallout
Analog Outputs (AOs) Terminal Block. (See Table 3)
1
Mounting Clip (Three Total)2
Device Address DIP Switch Block (See Setting the Device Addresses)
3
24 VAC, Class 2 Supply Power Terminal Block (See Supply Power Terminal Block)
4
Cover Lift Tab (One of Two) (See Removing the Controller Cover)
5
Sensor Actuator (SA) Bus / Field Controller (FC) Bus Terminal Block (See SA/FC Bus Terminal Block)
6
Universal Inputs (UIs) Terminal Block (See Table 3)
7
LED Status Indicators (See Table 8)
8
Sensor Actuator (SA) Bus or Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack) (See SA/FC Bus Port)
9
4FX-PCX2721 Expansion Input/Output Module Installation Instructions
Wiring
Risk of Electric Shock: Disconnect or isolate all power
supplies before making electrical connections. More than
one disconnect or isolation may be required to
completely de-energize equipment. Contact with
components carrying hazardous voltage can cause
electric shock and may result in severe personal injury
or death.
Avertissement: Risque de décharge électrique:
Débrancher ou isoler toute alimentation avant de réaliser
un branchement électrique. Plusieurs isolations et
débranchements sont peut-être nécessaires pour
-couper entièrement l'alimentation de l'équipement. Tout
contact avec des composants conducteurs de tensions
dangereuses risque d'entraîner une décharge électrique
et de provoquer des blessures graves, voire mortelles.
Risk of Property Damage: Do not apply power to the
system before checking all wiring connections. Short
circuited or improperly connected wires may result in
permanent damage to the equipment.
Mise En Garde: Risque de dégâts matériels: Ne pas
mettre le système sous tension avant d'avoir vérifié tous
les raccords de câblage. Des fils formant un court-circuit
ou connectés de façon incorrecte risquent
d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical
ratings. Exceeding controller electrical
ratings can result in permanent damage to
the controller and void any warranty.
Important: Use copper conductors only. Make all wiring
in accordance with local, national, and
regional regulations.
Important: Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
For detailed information on configuring and wiring an
MS/TP Bus, FC bus, and SA bus, refer to the FX-PC
Series Controllers MS/TP Communications Bus Technical
Bulletin (LIT-12011670) or MS/TP Communications Bus
for BCM System Technical Bulletin (LIT-12011908).
Terminal Blocks and Bus Ports
See Figure 3 for terminal block and bus port locations on
the controller. Observe the following guidelines when
wiring a controller.
Input and Output Terminal Blocks
All of the input terminal blocks are mounted on the bottom
of the controller and the output terminal blocks are
mounted on the top of the controller. See Table 3 for more
information about I/O terminal functions, requirements,
and ratings.
SA/FC Bus Terminal Block
An FX-PCX controller can be connected to a
Sensor/Actuator (SA) bus or a Field Controller (FC) bus,
but not to both buses simultaneously. The SA/FC bus
terminal block is a removable, 4-terminal plug that fits
into a board-mounted jack.
When connecting the FX-PCX to an FC bus, wire the bus
terminal block plugs on the controller, and the other
controllers in a daisy-chain configuration using 3-wire
twisted, shielded cable as shown in Figure 4. See Table
5 for more information.
Figure 4: FC Bus Terminal Block Wiring
When connecting the FX-PCX to an SA bus, wire the bus
terminal block plugs on the controller and other SA bus
devices in a daisy-chain configuration using 4-wire
twisted, shielded cable as shown in Figure 5. See Table
3 for more information.
5FX-PCX2721 Expansion Input/Output Module Installation Instructions
Figure 5: SA Bus Terminal Block Wiring
Note: The SA PWR/SHLD terminal does not supply 15
VDC. The SA PWR/SHLD terminal is isolated and
can be used to connect (daisy chain) the 15 VDC
power leads on the SA bus (Figure 5) or the cable
shields on the FC bus (Figure 4). The SA bus
supervisor supplies 15 VDC to devices on the SA
bus requiring power.
SA/FC Bus Port
The SA/FC bus port on the front of the controller is an
RJ-12, 6-position modular jack that provides a connection
for devices on the SA bus, a Bluetooth® Commissioning
Converter, Zigbee® wireless dongle, or an FX-ZFR1811
Wireless Router (depending on which bus the FX-PCX
is operating on).
The SA/FC bus port is connected internally to the SA/FC
bus terminal block. See Table 5 for more information.
The SA/FC bus Port pin assignment is shown in Figure
6.
Figure 6: Pin Number Assignments for Sensor, SA
Bus and FC Bus Ports on Controllers
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a board-mounted
jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer
to the HOT and COM terminals on the terminal plug as
shown in Figure 7. The middle terminal on the supply
power terminal block is not used. See Table 5 for more
information about the Supply Terminal Block.
Figure 7: 24 VAC Supply Power Terminal Block Wiring
Note: The supply power wire colors may be different on
transformers from other manufacturers. Refer to
the transformer manufacturer’s instructions and
the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to the
controller and all other network devices so
that transformer phasing is uniform across
the network devices. Powering network
devices with uniform 24 VAC supply power
phasing reduces noise, interference, and
ground loop problems. The controller does
not require an earth ground connection.
Wireless Network Applications
The controller can also be installed in a wireless
application using an FX-ZFR1811 Wireless Field Bus
Router.
To configure a controller for use with the FX-ZFR Series
Wireless Field Bus system:
Note: FX-PCXs can talk wirelessly on the FC bus only.
6FX-PCX2721 Expansion Input/Output Module Installation Instructions
1. Connect the FX-ZFR1811 Wireless Field Bus Router
to the FC bus port (RJ-12 modular jack) on the front
of the controller.
2. Ensure that the controller's device address DIP
switches are set to the correct device address. See
Setting the Device Addresses.
3. Set DIP switch 128 to ON, which enables wireless
operation on the controller.
For more information on installing a controller in a
wireless configuration, refer to the FX-ZFR Wireless
Field Bus Router Installation Instructions (Part No.
24-10325-29).
Termination Details
A set of Johnson Controls® termination diagrams provides details for wiring inputs and outputs to the controllers.
See the figures in this section for the applicable termination diagrams.
Table 2: Termination Details
Termination DiagramsType of
Input/Output
Type of Field
Device
UITemperature Sensor
UIVoltage Input -
External Source
UIVoltage Input -
Internal Source
UIVoltage Input
(Self-Powered)
UICurrent Input -
External Source
(Isolated)
7FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 2: Termination Details
Termination DiagramsType of
Input/Output
Type of Field
Device
UICurrent Input -
Internal Source (2
wire)
UICurrent Input -
Internal Source (3
wire)
UICurrent Input -
External Source (in
Loop)
UIFeedback from
EPP-1000
UIDry Contact (Binary
Input)
AO0–20 VDC Output to
Actuator (External
Source)
8FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 2: Termination Details
Termination DiagramsType of
Input/Output
Type of Field
Device
AO0–10 VDC Output to
Actuator (Internal
Source)
AOAnalog Output
(Current)
AO4–20 mA Output to
Actuator
AOVoltage (Analog
Output)
AO4–20 mA Output to
Actuator
9FX-PCX2721 Expansion Input/Output Module Installation Instructions
Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements
Input and Output Wiring Guidelines
Table 3 provides information and guidelines about the
functions, ratings, and requirements for the controller
input and output terminals; and references guidelines for
determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in Table 3, observe
these guidelines when wiring controller inputs and
outputs:
Run all low-voltage wiring and cables separate from
high-voltage wiring.
All input and output cables, regardless of wire size or
number of wires, should consist of stranded, insulated,
and twisted copper wires.
Shielded cable is not required for input or output
cables.
Shielded cable is recommended for input and output
cables that are exposed to high electromagnetic or
radio frequency noise.
Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup.
Cable-runs over 30 m (100 ft) may require an offset
in the input/output software setup.
Table 3: Controller Terminal Blocks, Functions, Ratings, Requirements, and Cables
Determine Wire Size and
Maximum Cable Length
1
Function, Ratings, RequirementsTerminal
Label
Terminal Block
Label
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power from
the +15V terminal.
15 VDC Power Source for active (3-wire) input devices
connected to the Universal INn terminals.
Provides 100 mA total current
+15 VUNIVERSAL
(Inputs)
See Guideline A in Table 4.
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage
Internal 75k ohm Pull-down
INn
See Guideline B in Table 4.
Analog Input - Current Mode (4–20 mA)
Internal 100 ohm load impedance
Note: A current loop fail-safe jumper can be positioned to
maintain a closed 4 to 20 mA current loop, even when the
power to the controller is interrupted or off. See UI Current
Loop Jumpers.
See Guideline A in Table 4.
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls® sensor], 1k Platinum, and A99B Silicon
Temperature Sensor) Negative Temperature Coefficient
(NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type
II)
See Guideline A in Table 4.
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V. 15k ohm pull up
Same as (Universal) INn
Universal Input Common for all Universal Input terminals
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
ICOMn
10FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 3: Controller Terminal Blocks, Functions, Ratings, Requirements, and Cables
Determine Wire Size and
Maximum Cable Length
1
Function, Ratings, RequirementsTerminal
Label
Terminal Block
Label
See Guideline C in Table 4.
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Note: The Analog Output (AO) operates in the Voltage
Mode when connected to devices with impedances greater
than 1,000 ohm. Devices that drop below 1,000 ohm may
not operate as intended for Voltage Mode applications.
OUTn
ANALOG
(Outputs)
Analog Output - Current Mode (4–20 mA)
Requires an external load between 0 and 300 ohm.
Note: The Analog Output (AO) operates in the Current
Mode when connected to devices with impedances less
than 300 ohm. Devices that exceed 300 ohm may not
operate as intended for Current Mode applications.
Analog Output Signal Common for all Analog OUT
terminals.
Note: All Analog Output Common terminals (OCOMn) share
a common, which is isolated from all other commons.
OCOMn
1
See Table 4 to determine wire size and cable lengths for cables.
Cable and Wire Length
Guidelines
Table 4 defines cable length guidelines for the various
wire sizes that may be used for wiring low-voltage (<30V)
input and outputs.
Table 4: Cable Length Guidelines for Recommended Wire Sizes for Low-Voltage (<30V) Inputs and Outputs
AssumptionsMaximum Cable
Length and Type
Wire Size/Gauge and TypeGuideline
100 mV maximum voltage drop
Depending on cable and the connected input
or output device, you may have to define an
offset in the setup software for the input or
output point.
457 m (1,500 ft) twisted
wire
1.5 mm
2
(18 AWG) stranded copper
A
297 m (975 ft) twisted wire0.8 mm (20 AWG) stranded copper
183 m (600 ft) twisted wire0.6 mm (22 AWG) stranded copper
107 m (350 ft) twisted wireN/A (24 AWG) stranded copper
100 mV maximum voltage drop
Depending on cable and the connected input
or output device, you may have to define an
offset in the setup software for the input or
output point.
229 m (750 ft) twisted wire
1.5 mm
2
(18 AWG) stranded copper
B
137 m (450 ft) twisted wire0.8 mm (20 AWG) stranded copper
91 m (300 ft) twisted wire0.6 mm (22 AWG) stranded copper
61 m (200 ft) twisted wireN/A (24 AWG) stranded copper
N/A
See Figure 8 to determine
cable length. Use twisted
wire cable.
See Figure 8 to select wire size/gauge.
Use stranded copper wire.
C
11FX-PCX2721 Expansion Input/Output Module Installation Instructions
Maximum Cable Length versus
Load Current
Use Figure 8 to estimate the maximum cable length
relative to the wire size and the load current (in mA) when
wiring inputs and outputs.
Note: Figure 8 applies to low-voltage (<30V) inputs and
outputs only.
Figure 8: Maximum Wire Length for Low-Voltage (<30V) Inputs and Outputs by Current and Wire Size
SA/FC Bus and Supply Power
Wiring Guidelines
Table 5 provides information about the functions, ratings,
and requirements for the communication bus and supply
power terminals; and guidelines for wire sizes, cable
types, and cable lengths when wiring the controller's
communication buses and supply power.
In addition to the guidelines in Table 5, observe these
guidelines when wiring an SA or FC bus and the 24 VAC
supply power:
Run all low-voltage wiring and cables separate from
high-voltage wiring.
All SA and FC bus cables, regardless of wire size,
should be twisted, insulated, stranded copper wire.
Shielded cable is strongly recommended for all SA
and FC bus cables.
Refer to the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin
(LIT-12011670) or MS/TP Communications Bus for
BCM System Technical Bulletin (LIT-12011908) for
detailed information regarding wire size and cable
length requirements for the SA and FC buses.
12FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and Cables
Recommended Cable Type
1
Function, Electrical Ratings/RequirementsTerminal
Labels
Terminal
Block/Port
Label
FC Bus: 0.6 mm (22 AWG) stranded, 3-wire
twisted, shielded cable recommended.
SA Bus: 0.6 mm (22 AWG) stranded, 4-wire
(2 twisted-pairs), shielded cable
recommended.
Note: On the SA Bus, the + and - wire are
one twisted pair, and the COM and SA PWR
are the second twisted pair of wires.
FC or SA Bus Communications+
-
FCBUS
2
or
SABUS
2
Signal Reference (Common) for FC or SA Bus
communications
COM
SHLD on FC Bus: Isolated terminal (optional shield drain
connection
SAP WR on SA Bus: 15 VDC power lead connection
Note: The SA PWR terminal on an FX-PCX37 controller
does not supply 15 VDC. The SA bus supervisor supplies
15 VDC to devices on the SA bus requiring power.
SHLD
or
SAPWR
Bluetooth Commissioning Converter
retractable cable or 24 AWG 3-pair CAT 3
Cable <30.5 m (100 ft)
RJ-12 6-Position Modular Connector provides:
FC or SA Bus Communications
FC or SA Bus Signal Reference and 15 VDC Common
Commissioning Converter or FX-ZFR1811 Wireless Router
(Maximum total current draw for SA Bus is 240 mA.)
SA/FC BUS
2
(Port)
0.8 mm to 1.5 mm
2
(18 AWG) 2-wire
24 VAC Power Supply - Hot
Supplies 20-30 VAC (Nominal 24 VAC)
HOT24~
24 VAC Power Supply - Common
(Isolated from all other Common terminals on controller.)
COM
1
See Table 4 to determine wire size and cable lengths for cables.
2 The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38,400 baud. For more
information, refer to the FX-PC Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670) or MS/TP
Communications Bus for BCM System Technical Bulletin (LIT-12011908).
Setup and Adjustments
Setting the Device Addresses
FX-PCX controllers are master devices on MS/TP (SA
or FC) buses. Before operating controllers on a bus, you
must set a valid and unique device address for each
controller on the bus. You set a controller's device
address by setting the positions of the switches on the
DIP switch block at the top of the controller (Figure 3).
Device addresses 4 through 127 are the valid addresses
for these controllers.
The DIP switch block has eight switches numbered 128,
64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1 are
device address switches. Switch 128 is a mode switch
that enables a controller to operate on an FX-ZFR Series
Wireless Field Bus. Switch 128 must be set to off for all
hard-wired SA and FC bus applications. Set switch 128
to ON for wireless FC bus applications only.
Figure 9: Device Address DIP Switch Block Set to
Address 21
Note: Controllers ship with switch 128 ON and the
remaining address switches off rendering the
controllers wired slave devices, which do not
operate on MS/TP buses, but will not interfere
with bus operation. Set a valid and unique device
address on the controller before applying power
to the controller on the bus.
To set the device addresses on FX-PCX controllers:
13FX-PCX2721 Expansion Input/Output Module Installation Instructions
1. Set all of the switches on the address DIP switch
block (128 through 1) to off.
2. Set one or more of the seven address switches (64
though 1) to ON, so that the sum of the switch
numbers set to ON equals the intended device
address. See Table 6 for valid device addresses.
Set the highest number switch that is less than or
equal to the intended device address to ON. Then
continue setting lower numbered switches until the
total equals the intended address. For example, if the
intended device address is 21, set switch 16 to ON
first, then set switch 4 ON, followed by switch 1
(16+4+1= 21).
3. Set switch 128 to ON only for controllers on an
FX-ZFR Series Wireless Field Bus application. For
all hard-wired SA and FC bus applications, ensure
that switch 128 is set to Off.
Note: Do not connect a controller with switch 128
set to ON to an active (hard-wired) SA or FC
bus. When a controller with switch 128 is set
to ON and a device address from 4 to 127 is
connected to a wired field bus, the entire field
bus is rendered inoperable until the controller
is disconnected or switch 128 is set to Off.
Refer to the FX-ZFR Series Wireless Field Bus
System Technical Bulletin (LIT-12011660) for more
information on device addresses in wireless
applications.
4. Set a unique and sequential device address for each
of the controllers connected on the SA or FC bus
starting with device address 4.
To ensure the best bus performance, set sequential
device addresses with no gaps in the device address
range (4, 5, 6, 7, 8, 9, and so on). The controllers do
not need to be physically connected on the bus in
their numerical device address order.
5. Write the controller's device address on the white
label below the DIP switch block on the controller's
cover.
Table 6 describes the FC bus and SA bus device
addresses for Johnson Controls® MS/TP
communications bus applications.
Refer to the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin
(LIT-12011670) or MS/TP Communications Bus for
BCM System Technical Bulletin (LIT-12011908) for
more information on controller device addresses and
how to set them on MS/TP buses.
Table 6: SA/FC Bus Device Address Descriptions
Use on DescriptionDevice
Address
Reserved for FC Bus Supervisory Controller
(not for use on controllers).
0
(Switch
128 Off)
Reserved for peripheral devices (not for use
on controllers).
1 to 3
(Switch
128 Off)
Used for MS/TP master devices (controllers)
that are hardwired to an SA Bus or FC Bus.
4 to 127
(Switch
128 Off)
Reserved addresses for wired slave devices
(not for use on controllers).
Note: FX-PCX controllers ship with switch 128
ON and the remaining address switches OFF,
rendering the controllers wired slave devices,
which do not operate on MS/TP buses.
0 to 3
(Switch
128 ON)
Valid for MS/TP Master controllers on wireless
FC Buses only.
Note: Do not connect a controller with switch
128 ON to an active (hard-wired) SA or FC
Bus. When a controller with switch 128 ON
and a device address from 4 to 127 is
connected to a wired field bus, the entire field
bus is rendered inoperable until the controller
is disconnected or switch 128 is set to OFF.
4 to 127
(Switch
128 ON)
Removing the Controller Cover
Important: Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
Important: Disconnect all power sources to the
controller before removing cover and
changing the position of any jumper or the
EOL switch on the controller. Failure to
disconnect power before changing a jumper
or EOL switch position can result in damage
to the controller and void any warranties.
The controller cover is held in place by four plastic latches
that extend from the base and snap into slots on the
inside of the housing cover.
To remove the controller cover:
1. Place your fingernails under the two cover lift tabs
(Figure 3) on the sides of the housing cover and
14FX-PCX2721 Expansion Input/Output Module Installation Instructions
gently pry the top of the cover away from the base to
release the cover from the two upper latches.
2. Pivot the top of the cover further to release it from the
lower two latches.
3. Replace the cover by placing it squarely over the
base, and then gently and evenly push the cover on
to the latches until they snap into the latched position.
Figure 10: Controller with Cover Removed Showing
EOL Switch and Jumper Positions
Setting the End-of-Line (EOL) Switch
Each controller has an EOL switch, which, when set to
ON, sets the controller as a terminating device on the
bus. See Figure 10 for the EOL switch location. The
default EOL switch position is Off.
Figure 11: End-of-Line Switch Positions
To set the EOL switch on a controller:
1. Determine the physical location of the controller on
the SA or FC bus.
2. Determine if the controller must be set as a
terminating device on the bus.
Note: The EOL termination rules for SA buses and
FC buses are different. Refer to the FX-PC
Series Controllers MS/TP Communications
Bus Technical Bulletin (LIT-12011670) or
MS/TP Communications Bus for BCM System
Technical Bulletin (LIT-12011908) for detailed
information regarding EOL termination rules
and EOL switch settings on SA and FC buses.
3. If the controller is a terminating device on the FC bus,
set the EOL switch to ON. If the controller is not a
terminating device on the bus, set the EOL switch to
Off.
When a controller is connected to power with its EOL
switch set to ON, the amber EOL LED on the
controller cover is lit.
UI Current Loop Jumpers
The Universal Input (UI) current loop fail-safe jumpers
are on the circuit board under the controller cover near
the UI terminals (Figure 10). When a UI is defined (in the
system software) as a 4 to 20 mA Analog Input and the
UI’s current loop jumper is in the Disabled (default)
position (Figure 12), the 4 to20 mA current loop circuit
opens whenever power to the controller is interrupted or
off.
Figure 12: Current Loop Jumper Positions
Setting the current loop jumper to the Enabled position
(Figure 12) connects an internal 100 ohm resistor across
the UI terminals, which maintains the 4 to 20 mA current
loop circuit even when power to the controller is
interrupted or off.
Important: Current Loop jumpers must be in the
Disabled (default) position for all UIs that
are not set up to operate as 4 to20 mA
analog inputs.
Table 7 identifies the current loop jumpers associated
with each UI on the FX-PCX2721 controller.
Table 7: FX-PCX2721 UI Inputs and Jumper Labels
Jumper Label on Circuit BoardUniversal Input
Label
J20IN1
J21IN2
J22IN3
J23IN4
J24IN5
J25IN6
15FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 7: FX-PCX2721 UI Inputs and Jumper Labels
Jumper Label on Circuit BoardUniversal Input
Label
J26IN7
J27IN8
Commissioning the Controllers
You commission controllers with the FX-PCT software,
either via a Bluetooth Commissioning Converter, a ZigBee
wireless dongle, or in BACnet® router mode when
connected to an FX supervisory controllers. Refer to the
Controller Tool Help (LIT-12011147) for detailed
information on commissioning controllers.
Troubleshooting the Controllers
Observe the Status LEDs on the front of the controller
and see Table 8 to troubleshoot the controller.
Table 8: Status LEDs and Descriptions of LED States
Description of LED StatesNormal LED
State
LED ColorLED Label
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse
is open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
On SteadyGreenPOWER
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download
required, if controller is in Boot mode, or a firmware mismatch exists between
the FX-PCX and the FX-ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Off SteadyRedFAULT
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
Blink - 2 HzGreenSA/FC BUS
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position
Off (Except on
terminating
devices)
AmberEOL
Repair Information
If a controller fails to operate within its specifications,
replace the controller. For a replacement controller,
contact your Johnson Controls representative.
Accessories
See Table 9 for controller accessories ordering
information.
Table 9: Accessories Ordering Information
DescriptionProduct Code Number
Bluetooth Commissioning ConverterFX-BTCVT-1
Wireless Field Bus RouterFX-ZFR1811-0
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA,
Wall Plug
TP-2420
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary,
40 VA, Foot Mount, 8 in. Primary Leads and Secondary Screw
Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available.
Refer to the Series Y63, Y64, Y65, Y66, and Y69 Transformers
Product Bulletin (LIT-125755) for more information.
Y65T31-0
Power transformer (Class 2, 24 VAC, 50 VA maximum output),
no enclosure
AS-XFR050-0
16FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 9: Accessories Ordering Information
DescriptionProduct Code Number
Replacement SA/FC Bus Terminal Blocks, 4-Position, Gray, Bulk
Pack of 10
Note: This is the standard terminal block that is provided with the
controller.
MS-TBK4BUS-0
Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk
Pack of 10
Note: These terminal blocks can be used as replacement parts
if keeping consistent terminal block colors is important.
AP-TBK4SA-0
Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk
Pack of 10
Note: These terminal blocks can be used as replacement parts
if keeping consistent terminal block colors is important.
AP-TBK4FC-0
Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack
of 10
AP-TBK3PW-0
USB Dongle with ZigBee Driver provides a wireless connection
through FX-PCT to allow wireless commissioning of the wirelessly
enabled FX-PCG, FX-PCA, FX-PCX, and FX-PCV field controllers.
Also allows use of the FX-ZFR Checkout Tool (FX-ZCT) in
FX-PCT.
Note: The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400
ZigBee USB dongle. For additional information on the
ZFR-USBHA-0 ZigBee dongle, refer to the FX-ZFR Series
Wireless Field Bus System Technical Bulletin (LIT-12011660) or
FX-ZFR Series Wireless Field Bus System Quick Reference
Guide (LIT-12011696).
ZFR-USBHA-0
Technical Specifications
Table 10: FX-PCX2721 Technical Specifications
FX-PCX2721-0 Expansion Input/Output ModuleProduct Code Number
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply
Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
Supply Voltage
14 VA maximum for FX-PCX2721 onlyPower Consumption
Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing
Ambient Conditions
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and
128–255 are reserved and not valid controller addresses.)
Addressing
BACnet® MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and other controllers
4-wire SA Bus between controller, network sensors and other sensor/actuator devices,
includes a lead to source 15 VDC supply power (from controller) to bus devices.
Communications Bus
H8SX/166xR Renesas® 32-bit microcontrollerProcessor
640 KB Flash Memory and 128 KB Random Access Memory (RAM)Memory
8 - Universal Inputs: Defined as 0–10 VDC, 4-20 mA, 0-600k ohm, or Binary Dry
Contact
2 - Analog Outputs: Defined as 0–10 VDC or 4-20 mA
Input and Output Capabilities
17FX-PCX2721 Expansion Input/Output Module Installation Instructions
Table 10: FX-PCX2721 Technical Specifications
Output: 16-bit resolution, +/-200 mV accuracy in 0-10 VDC applicationsAnalog Output Resolution and Accuracy
Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal
Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Terminations
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface
with three integral mounting clips on controller
Mounting
Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum
Rated
Protection Class: IP20 (IEC529)
Housing
150 x 164 x 53 mm (5-7/8 x 6-1/2 x 2-1/8 in.) including terminals and mounting clips
Note: Mounting space requires an additional 50 mm (2 in.) on top, bottom and front
face of controller for easy cover removal, ventilation, and wire terminations.
Dimensions(Height x Width x Depth)
0.5 kg (1.1 lb)Weight
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Compliance
Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal
Equipment
Industry Canada Compliant, ICES-003
Europe: Johnson Controls, Inc. declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet International: BACnet Testing Laboratories (BTL) Protocol Revision 4
Listed BACnet Application Specific Controller (B-ASC)
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable
for damages resulting from misapplication or misuse of its products.
APAC Single Point of Contact:NA/SA Single Point of Contact:European Single Point of Contact:
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls® is a registered trademark of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners.© 2018 Johnson Controls, Inc.
www.johnsoncontrols.comPublished in U.S.A.
18FX-PCX2721 Expansion Input/Output Module Installation Instructions
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13