Johnson Controls Metasys MS-FEU1610-0U Installation Instructions Manual

Type
Installation Instructions Manual
FEU16x0 Field Equipment Controller Installation Instructions
1
Applications
The FEU16x0 Controller is a member of the Metasys® system Field Equipment Controller (FEC) family. The
controller is designed exclusively for use in a Metasys Release 8.1 smoke control application that is UL 864 UUKL/
UUKLC 10th Edition Smoke Control Listed. For Metasys system smoke control applications, you must refer to the
Metasys® System UL 864 10th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System (LIT-12012487) for
detailed requirements and procedures for installing, commissioning, and operating UL 864 UUKL/UUKLC Listed
Metasys system devices. For example, the MS-FEU1610-0U can only be used with the Firefighters Smoke Control
Station (FSCS) panel manufactured by Automation Displays, Inc. (ADI). The UL 864 UUKL/UUKLC listing for
Smoke Control Equipment is voided if (1) you do not use the required software tools at the required versions; or (2)
you do not meet the requirements or do not follow the procedures as documented in the Metasys® System UL 864
10th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12012487).
North American Emissions Compliance
Canada
United States
Installation
Observe these guidelines when installing the FEU controller:
Transport the controller in the original container to minimize vibration and shock damage to the controller.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical shock.
Parts Included
one MS-FEU1610-0U Controller with removable Terminal Plugs
one Installation Instructions sheet
Materials and Special Tools Needed
three fasteners appropriate for the mounting surface (#8 screws or M4 screws)
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference, in which case the user will be required to correct the interference at his/her
own expense.
FEU16x0 Field Equipment Controller
Installation Instructions
MS-FEU1610-0U
Part No. 24-10143-535, Rev. B
Release 8.1
Issued March 2018
FEU16x0 Field Equipment Controller Installation Instructions
2
one 15.2 cm (6 in.) or longer piece of DIN rail and appropriate hardware for mounting the DIN rail
small straight blade screwdriver for securing communication wires in the terminal blocks
one phone jack splitter (optional)
Figure 1: FEU16 Controller Physical Features and Wiring Terminals
S
t
a
t
u
s
L
E
D
s
D
e
v
i
c
e
A
d
d
r
e
s
s
D
I
P
S
w
i
t
c
h
B
l
o
c
k
F
C
B
u
s
E
n
d
-
o
f
-
L
i
n
e
T
e
r
m
i
n
a
t
i
o
n
S
w
i
t
c
h
B
i
n
a
r
y
O
u
t
p
u
t
s
T
y
p
i
c
a
l
l
y
2
4
V
A
C
T
r
i
a
c
o
u
t
p
u
t
s
C
o
n
f
i
g
u
r
a
b
l
e
O
u
t
p
u
t
s
V
o
l
t
a
g
e
A
n
a
l
o
g
O
u
t
p
u
t
B
i
n
a
r
y
O
u
t
p
u
t
c
a
n
b
e
d
e
f
i
n
e
d
a
s
:
(
0
-
1
0
V
D
C
)
(
2
4
V
A
C
T
r
i
a
c
)
2
4
V
A
C
,
C
l
a
s
s
2
S
u
p
p
l
y
P
o
w
e
r
T
e
r
m
i
n
a
l
B
l
o
c
k
U
n
i
v
e
r
s
a
l
I
n
p
u
t
s
V
o
l
t
a
g
e
A
n
a
l
o
g
I
n
p
u
t
C
u
r
r
e
n
t
A
n
a
l
o
g
I
n
p
u
t
R
e
s
i
s
t
i
v
e
A
n
a
l
o
g
I
n
p
u
t
s
:
D
r
y
C
o
n
t
a
c
t
B
i
n
a
r
y
I
n
p
u
t
c
a
n
b
e
d
e
f
i
n
e
d
a
s
:
(
0
-
1
0
V
D
C
)
(
4
-
2
0
m
A
)
0
-
2
k
o
h
m
R
T
D
:
1
k
N
i
c
k
e
l
,
1
k
P
l
a
t
i
n
u
m
,
o
r
A
9
9
B
S
I
N
T
C
:
1
0
k
T
y
p
e
L
o
r
2
.
2
2
5
k
T
y
p
e
2
B
i
n
a
r
y
I
n
p
u
t
s
D
r
y
C
o
n
t
a
c
t
M
a
i
n
t
a
i
n
e
d
P
u
l
s
e
C
o
u
n
t
e
r
M
o
d
e
c
a
n
b
e
d
e
f
i
n
e
d
a
s
:
(
1
0
0
H
z
h
i
g
h
-
s
p
e
e
d
)
C
o
v
e
r
S
c
r
e
w
S
e
n
s
o
r
P
o
r
t
(
R
J
-
1
2
6
-
P
i
n
M
o
d
u
l
a
r
J
a
c
k
)
F
I
G
:
F
E
C
1
6
1
0
_
t
e
r
m
O
N
A
D
D
R
E
S
S
A
D
D
R
E
S
S
Ø
=
A
L
L
O
F
F
C
O
M
H
O
T
C
O
M
+
S
H
L
D
S
A
B
U
S
S
E
N
S
O
R
C
O
M
+
S
A
P
W
R
O
U
T
4
O
C
O
M
4
O
U
T
5
O
C
O
M
5
O
U
T
6
O
C
O
M
6
O
U
T
7
O
C
O
M
7
O
U
T
2
O
C
O
M
2
O
U
T
1
O
C
O
M
1
O
U
T
3
O
C
O
M
3
B
I
N
A
R
Y
I
N
3
I
C
O
M
3
U
N
I
V
E
R
S
A
L
+
1
5
V
I
N
1
I
C
O
M
1
I
N
2
I
C
O
M
2
F
C
E
O
L
O
N
S
A
B
U
S
F
A
U
L
T
P
O
W
E
R
T
h
e
B
i
n
a
r
y
O
u
t
p
u
t
s
I
N
T
/
E
X
T
p
o
w
e
r
s
o
u
r
c
e
j
u
m
p
e
r
s
a
r
e
l
o
c
a
t
e
d
u
n
d
e
r
t
h
e
F
E
C
c
o
v
e
r
o
n
t
h
e
t
e
r
m
i
n
a
t
i
o
n
b
o
a
r
d
.
N
o
t
e
:
F
C
B
u
s
T
e
r
m
i
n
a
l
s
a
n
d
T
e
r
m
i
n
a
l
B
l
o
c
k
S
A
B
u
s
T
e
r
m
i
n
a
l
s
a
n
d
T
e
r
m
i
n
a
l
B
l
o
c
k
FEU16x0 Field Equipment Controller Installation Instructions
3
Mounting
Observe these guidelines when mounting a field controller:
Ensure the mounting surface can support the controller, DIN rail,
and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail whenever possible.
Mount the controller in the proper orientation. If wall mount applications are not allowed for the FEU1610-0U,
then proper mounting position will only be as shown in Figure 2.
Mount the controller on a hard, even surface whenever possible in wall mount applications.
Use shims or washers to mount the unit securely and evenly on the mounting surface.
Mount the controller
in an area free of corrosive vapors and observe the Ambient Conditions requirements
listed in the Technical Specifications
section.
Provide for sufficient space around the controller for calbe and wire connections for easy cover removal and
good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
Do not mount the controller
on surfaces prone to vibration, such as duct work.
Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can
interfere with controller
communication.
Observe these additional guidelines when mounting a controller in a panel or enclosure:
Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the
controller.
Mount the controller so that the power transformer and other devices do not radiate excessive heat to the
controller.
Do not install the controller
in an airtight enclosure.
Wall Mount Applications
The FEU16 controller must be installed inside an FSCS panel; therefore, a wall mount application is not
acceptable.
DIN Rail Mount Applications
To mount the controller on a DIN rail inside the FSCS panel:
1. Securely mount a 20.3 cm (8 in.) or longer section of DIN rail horizontally and centered in the desired space so
that the controller mounts in the horizontal position shown in Figure 2.
2. Ensure that the bottom two mounting clips are pulled outward and snapped firmly into the extended position.
Figure 2: Required Orientation for DIN Rail Mount Applications
FIG:DINril
ON
ADDR ESS
ADDR ESS Ø = ALL OFF
COM
HOT
C
OM
+
SHLD
SA BUS
SENS OR
CO M
+
SA
PWR
OUT 4
OCOM 4
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 7
OCOM 7
OUT 2
OCOM 2
OUT 1
OCOM 1
OUT 3
OCOM 3
BI NA RY
IN3
ICOM
3
UNI VERSA L
+1 5V
IN1
ICOM
1
IN2
ICOM
2
FC
EOL
O
N
SAB
FLT
PWR
R
ET SY
esc
FEU16x0 Field Equipment Controller Installation Instructions
4
3. Hand the controller by the hooks at the top of the DIN rail channel on the back of the controller, and position the
controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure the controller
on the DIN rail tracks.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and carefully
lift the controller
off the DIN rail.
Wiring
For detailed information on configuring and wiring an MS/TP Bus, FC Bus, and SA Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034).
Hard-Wired Installation
To install an FEU16 for hard-wired operation, perform the steps that follow. See Figure 1 for jack and terminal block
locations.
Input/Output Terminals
Terminate input/output point wiring at the controller per engineering drawings.
SA Bus Terminal Block and Sensor Port
Wire Network Sensors and other devices to the Sensor Actuator (SA) Bus terminal block (Figure 3) or Sensor port
(RJ-12 modular jack) for sensors.
Note: The FEU16 controller should be at one end of the SA Bus daisy chain. If multiple Input/Output Modules
(IOMs) are used, set the End-of-Line (EOL) switch on the last IOM.
Risk of Electric Shock: Disconnect the power supply before making electrical connections to avoid electric
shock.
Mise En Garde: Risque de décharge électrique: Débrancher l'alimentation avant de réaliser tout raccordement
électrique afin d'éviter tout risque de décharge électrique.
Risk of Property Damage: Do not apply power to the system before checking all wiring connections. Short
circuited or improperly connected wires may result in permanent damage to the equipment.
Mise En Garde: Risque de dégâts matériels: Ne pas mettre le système sous tension avant d'avoir vérifié tous
les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent
d'endommager irrémédiablement l'équipement.
IMPORTANT: Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result
in permanent damage to the controller and void any warranty.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional
regulations.
IMPORTANT: Electrostatic discharge can damage controller components. Use proper electrostatic discharge
precautions during installation, setup, and servicing to avoid damaging the controller.
FEU16x0 Field Equipment Controller Installation Instructions
5
FC Bus Terminal Block
Wire the Field Controller (FC) Bus in a daisy chain to other devices on the FC Bus and the supervisory controller
(Figure 4).
Note: The Shield terminal (SHLD) on the FC Bus terminal block is isolated and can be used as a convenient
terminal for connecting the bus cable shield (Figure 4).
Sensor Port
The Sensor Bus port on the bottom-right of the IOM is an RJ-12, 6-position modular jack that provides a connection
for an NS sensor. See Table 1 for more information. The Sensors Port pin assignment is shown in (Figure 5).
Device Address DIP Switches
Ensure the device address DIP switches are set to the appropriate address (in the range of 4-127). Ensure that DIP
switch 128 is set to Off, which disables wireless mode. For more details on setting the DIP switches, see the
Setting the FC Bus Address
on page 11.
Figure 3: SA Bus Terminal Block Wiring
Figure 4: FC Bus Terminal Block Wiring
FEU16x0 Field Equipment Controller Installation Instructions
6
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board-mounted jack
on the top right of the controller. Connect the 24 VAC supply power wires from the transformer to the HOT and
COM terminals on the plug as shown in Figure 6. The middle terminal on the supply power block is not used..
IMPORTANT: The 24 VAC power should be connected to all network devices so transformer phasing is
uniform across the devices. Powering devices with uniform 24 VAC supply power phasing reduces noise,
interference, and ground loop problems. The FEC does not require an earth ground connection.
Figure 5: Pin Number Assignments for Sensor, SA Bus, and FC Bus Ports on FEC,
IOM, and VMA16
Power
(15 VDC)
SA or FC Bus +
SA or FC Bus
-
Bus and Power Common
Power
(15 VDC)
Sensor, SA Bus, or FC Bus Port
(RJ-12 Modular Jack)
Bus and Power Common
FIG:RJ_pinout
2
3
4
5
6
1
Figure 6: 24 VAC Supply Power Terminal Block Wiring
FEC
Supply Power
Terminal Block
Brown Wire
Orange Wire
FEU16x0 Field Equipment Controller Installation Instructions
7
Wire Gauges and Lengths
See Table 1 for the field controller platform wiring list and Table 2 for alternative wire gauges and lengths.
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 1 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements Recommended Cable Type
and Length
1
Universal IN +15 V Provides 15 VDC power for active devices connected to
the Universal IN terminal blocks (3-wire connection).
35 mA total current
0.6 mm (22 AWG) stranded, 3-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Same as IN. See IN n cable type.
IN n Analog Input, Voltage Mode
Accepts a 0-10 VDC input signal.
10 VDC Maximum Input Voltage
Internal 75k ohm Pulldown
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
Table 2.)
Analog Input, Current Mode
Accepts a 4-20 mA input signal.
Note: For current sensing applications, the FEU16x0
does not provide a jumper to close the current loop when
the controller is powered off. This option is available on
FEC26x0 controllers only.
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable
(See Row B in
Table 2.)
Analog Input, Resistive Mode
Accepts 0-600k ohm input signal.
Internal 12 V, 15k ohm Pullup
RTD (1k Nickel [Johnson Controls], 1k Platinum, A99B
Silicon Temperature Sensor)
Negative Temperature Coefficient (NTC) Sensor
(10k Type L, 2.252k Type 2)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
Table 2.)
Binary Input, Dry Contact Maintained Mode
1 second minimum pulse width (0.5 Hz at 50% duty cycle)
Internal 12 V, 15k ohm Pullup
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
Table 2.)
ICOM n The signal common for all Universal IN terminals;
isolated from all other terminal commons
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Same as IN. See IN n cable type.
Note: Use 3-wire cable for active
devices that connect to the +15 V
terminal also.
Binary IN IN n Binary Input, Dry Contact Maintained Mode
0.01 second min. pulse width (50 Hz at 50% duty cycle)
Internal 8 V, 3.3k ohm Pullup
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
Table 2.)
Binary Input, Pulse Counter Mode
0.01 second min. pulse width (50 Hz at 50% duty cycle)
Internal 8 V, 3.3k ohm Pullup
ICOM n The signal common for Binary IN terminals; isolated from
all other terminal commons, excluding Configurable
Output (CO) terminal commons that are configured as
Analog Outputs (AOs).
FEU16x0 Field Equipment Controller Installation Instructions
8
Binary OUT
(Jumper set
to External)
OUT n Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row C in
Table 2.)
OCOM n The signal common for Binary OUT terminals; isolated
from all other terminal commons, including Binary Output
terminal commons
Binary OUT
(Jumper Set
to Internal)
OUT n Sources 24 VAC Power (Hot) 0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row C in
Table 2.)
OCOM n Binary Output, 24 VAC Triac
Connects OCOM to 24 VAC Power (Com) when activated
(low side switching).
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current
Configurable
OUT
OUT n Analog Output, Voltage Mode
Sources 0-10 VDC
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row A in
Table 2.)
Binary Output, 24 VAC Triac mode
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(See Row C in
Table 2.)
OCOM n Analog Output: The signal common for all analog CO
terminals; isolated from all other terminal commons,
excluding BI terminal commons
Binary Output: The signal common for binary-configured
CO terminals; isolated from all other terminal commons,
including other CO terminal commons
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Same as OUT. See OUT cable
type.)
Sensor
2,3
Sensor Provides SA Bus communication network.
RJ-12 6-position modular connector
24 AWG 3-pair CAT 3 Cable
<30.5 m (100 ft)
SA Bus
2
,
3
+
-
Provides SA Bus communication network. 0.6 mm (22 AWG) stranded, 4-wire
twisted, shielded cable
recommended
COM Provides reference for network communication bus and
15 VDC source power.
SA PWR Sources 15 VDC power for devices on the SA Bus
FC Bus
Terminal
Block
3
+
-
COM
Provides FC Bus communication network. 0.6 mm (22 AWG) stranded, 3-wire
twisted, shielded cable
recommended
SHLD Provides an optional shield connection.
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements Recommended Cable Type
and Length
1
FEU16x0 Field Equipment Controller Installation Instructions
9
24~ Power Hot AC Supply Input
Supply 20-30 VAC (Nominal 24 VAC)
0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire
SHLD Provides an optional shield connection.
1. See
Table 2 for alternative wire gauges and lengths.
2. The SA Bus terminals and the RJ-style modular Sensor Port are connected internally.
3. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Table 2: Wire Gauge and Length Guidelines
Guideline Cable Size Maximum
Length
Assumptions
A 1.0 mm (18 AWG) 457.2 m (1,500 ft) 100 mV maximum voltage drop
0.8 mm
(20 AWG)
297.2 m (975 ft)
0.6 mm
(22 AWG)
182.9 m (600 ft)
0.5 mm (24 AWG) 106.7 m (350 ft)
B 1.0 mm (18 AWG) 228.6 m (750 ft) 100 mV maximum voltage drop
0.8 mm
(20 AWG)
137.1 m (450 ft)
0.6 mm
(22 AWG)
91.4 m (300 ft)
0.5 mm (24 AWG) 61 m (200 ft)
C
See
Figure 7.See Figure 7.
N/A
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 3 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements Recommended Cable Type
and Length
1
FEU16x0 Field Equipment Controller Installation Instructions
10
Wiring Requirements
Use Figure 7 to determine the maximum wire length allowable when alternative wire gauges are required.
Setup and Adjustments
Determining the FC Bus Address
The FC Bus address switch sets a unique address for this controller on the FC Bus. You must set the FEC’s device
address for your field bus application.
Set consecutive device addresses 4 through 127 for Field Equipment Controllers and other master devices on the
FC Bus. Use sequential addressing with no gaps in the device address range to ensure best FC Bus performance.
Note: Switch 128 on the device address DIP switch block should be set to Off.
Table 3 shows and describes the valid FC Bus and SA Bus devices addresses for FECs and IOMs on Johnson
Controls® MS/TP communications bus applications.
Table 3: FC Bus Device Address Descriptions
Device
Address
Description
0 Reserved for FC Bus supervisory controller.
1-3 Reserved for peripheral devices.
4-127 Available for FECs on the FC bus and IOMs
on the SA or FC Bus.
128 Unused and should be set to Off.
129-255 Are not valid addresses for FEC or IOM
controllers on the SA or FC Bus.
Figure 7: Maximum Wire Length by Current and Wire Size
450
500
400
350
300
250
200150
100
50
0
0 m (0 ft)
15.2 m (50 ft)
30.5 m (100 ft)
45.7 m (150 ft)
61 m (200 ft)
76.2 m (250 ft)
91.4 m (300 ft)
106.7 m (350 ft)
121.9 m (400 ft)
137.2 m (450 ft)
Load Current (mA)
Length
FIG:wir_lngth
1.0 mm (18 AWG)
0.8 mm (20 AWG)
0.6 mm(22 AWG)
0.5 mm (24 AWG )
FEU16x0 Field Equipment Controller Installation Instructions
11
Setting the FC Bus Address
Set the address of the FEU16 using the DIP switches on the face of the FEU16. The address equals the sum of the
numbers set to ON. For example, if the first (1), the third (4), and the fifth (16) DIP switches are set to ON, the
device address is 21 (1 + 4 + 16 = 21). See Figure 8.
FC Bus End-of-Line Switch
The FC Bus End-of-Line termination switch allows you to designate the FEU16 as the end of the FC Bus. The
default position is OFF. If the FEU16 is at the end of a daisy chain of devices on the FC Bus, set the EOL switch to
the ON position. See Figure 9.
Setting the Binary Output INT/EXT Jumpers
The Binary Output jumpers (OUT1 through OUT3) are located on the circuit board in the mounting base near the
binary outputs. These jumpers select whether the output provides internal power to the load (INT) or requires
external power (EXT). See Figure 10.
When set to the INT position, the FEU16
is the power source for the Binary Output and both sides of the load can
be wired directly to the OUTx and COMx terminals.
Setting the jumper to the EXT position isolates the Binary Outputs, and power must come from one or more
external sources. Do not wire the load directly to the OUTx and COMx terminals. Wire one side of the load to the
source and the other side of the load to the OUTx terminal. Wire the other side of the external power source to the
COMx terminal.
IMPORTANT: Do not set the Binary Output jumpers to INT when an external transformer is wired to the Binary
Output terminals. Failure to follow this precaution may cause damage to the controller.
Figure 8: Device Address Switches Set to 21
FIG:fec_dip_swtch
128
64
32
16
8
4
2
1
ON
Note:
Switch 128 is
used to enable or
disable an FEC for
wireless operation.
Figure 9: EOL Switch Positions
FIG:E
OL_Swtch
EOL ON Position EOL Off Position
O
N
O
N
Figure 10: Binary Output (BO) Jumper Positions
Jumper
Pins
Jumper positioned
on top two pins
Jumper positioned
on bottom two pins
INT
EXT (Default)
FIG:Bin_Jmpr
FEU16x0 Field Equipment Controller Installation Instructions
12
Commissioning
Commission the controller with the Controller Configuration Tool (CCT), either through the BTCVT or in
passthrough mode when connected via a Network Application Engine (NAE) or Network Control Engine (NCE).
Refer to CCT Help.
Troubleshooting
Use Table 4 to troubleshoot the controller.
Replacing the Fuse
If you connect power to the controller but it does not function, the fuse may need to be replaced. Use the following
procedure to replace the fuse.
1. Remove power from the controller.
2. Loosen the cover screw and remove the cover.
3. Remove the fuse. See Figure 11.
4. Install a new replacement fuse (MS-FUSE01-1).
5. Replace the cover.
6. Reconnect power to the controller.
Table 4: Status LEDs
Name Color Normal Descriptions
Power/PWR Green On Steady Off Steady = No Power
On Steady = Power is supplied by Primary Voltage.
Fault/FLT Red Off Steady Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download required, if
controller is in Boot mode.
SA Bus/SAB Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
FC Bus/FCB Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring
Figure 11: Location of Removable Fuse
Location
of
Removable
Fuse
FIG:fse_rmv
F1
Controller Mounting Base
FEU16x0 Field Equipment Controller Installation Instructions
13
Repair Information
If you need to replace the MS-FEU1611-0U controller, contact the Johnson Controls Repair Center in Louisville,
Kentucky, at 1-502-671-7312. This model has special restrictions because it is UL 864 10th Edition UUKL/ORD-
C100-13 UUKLC listed for smoke control.
Accessories
Use Table 5 to order accessories.
Technical Specifications
Table 5: FEU16 Accessories Ordering Information
Product Code Number Description
PAN-PWRSP-U Transformer, 120/24 VAC, 96 VA, with circuit breaker and 120 VAC outlet, approved for Smoke
Control
MS-FUSE01-1 Replacement fuse (Bulk Pack of 10)
FEU1610 Controller
Product Code Numbers MS-FEU1610-0U Field Equipment Controller
Supply Voltage 20 - 30 VAC at 50 or 60 Hz, Class 2
Power Consumption 10 VA typical, 14 VA maximum, plus all BO and CO loads
Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 70°C (-40 to 158°F); 10 to 90% RH noncondensing
Terminations Screw Terminals and Screw Terminal Pluggable Blocks
Controller Addressing DIP switch set (4-127). Addresses 0-3, 128-255 are reserved.
Communications Bus BACnet® MS/TP; 3-wire FC Bus between the NAE and other devices. 4-wire SA Bus
between network sensors and other devices.
Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail
Housing Plastic housing
Plastic material: ABS and polycarbonate UL94 5VB
Analog Input/Analog
Output Resolution and
Accuracy
Analog Input Points: 15-bit resolution
Analog Output Points: 16-bit resolution, +
200 mV accuracy
Dimensions
(Height x Width x Depth)
144 x 127 x 58 mm (5.68 x 5 x 2.25 in.)
Minimum space for mounting:
174 x 350 x 110 mm (6.8 x 13.8 x 4.3 in.)
Weight 0.5 kg (1.10 lb)
Compliance United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A
UL Listed, File S4977, UL 864 UUKL/UUKLC 10th Edition Listed, Smoke Control Units and
Accessories for Fire Alarm Systems Equipment
Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal
Equipment; Industry Canada Compliant, ICES-003
UL Listed, File S4977, UL 864 UUKL/ORD-C100-13 10th Edition Listed, Smoke Control Units
and Accessories for Fire Alarm Systems
Europe: CE Mark, EMC Directive, in accordance with EN 61000-6-3 and EN 61000-6-2, and
the Low Voltage Directive in accordance with EN 60730.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant.
BACnet International: BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet
Application Specific Controller (B-ASC)
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
Published in U.S.A.
www.johnsoncontrols.com
FEU16x0 Field Equipment Controller Installation Instructions 14
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2018 Johnson Controls.
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Johnson Controls Metasys MS-FEU1610-0U Installation Instructions Manual

Type
Installation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI