  • Hello! I am an AI chatbot trained to assist you with the meitav-tec MIGA 1-FC-Super Product information. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Date:
Title:MIGA1-FC-SUPER
20/09/2005
meitav tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com Rev.1 Original 20/09/2005
Print name: MIG1 Drawn: P.Rechtman
Checked: S.Lukin
Approved: E. Samocha
File: MIGA1-FANCOIL-SUPER.VSD
Software: MG1TFV4
Checksum: 55C3
Heat (1A)
Condensation pump (1A)
High
Medium
Low
Indoor fan
(3A)
J3
EF
HI
MED
LOW
000
J8
J7
J6
J4
J5 J11 J10
~
AUX
AUX1
COMPRESSOR
T1 0T2 0T3 0
0
T4
17
8/14
7
6
5/16
4
3
2
1/15
Panel
J9 J15 J12
Fuse
10A
+12V
Power
supply
Microcontroller
Outdoor
Coil
Sensor
(option)
Indoor
Sensor
(option)
Fault input (N.C)
15
16
17
ETN-MIGA-IR / FMH-MIGA-IR
JP3
JP2
JP1
Main
supply
230VAC
Swing
output
Cool
(1A)
00 0 ~
Green LED - ON
IR Receiver
Panel M101P
Yellow LED - TIMER
ON/OFF Button
ON/OFF
ON TIMER
Quick connector
Condensation pump
The condensation pump output, 230VAC,1A, will work together with the “Cool”
output.
Swing
The swing output, dry contact, can be activated using the remote control, and will
remain ON until turned OFF using the remote control.
When ON, the swing output will work only together with the fan, and will turn OFF
when the fan is OFF.
Jumper JP1 – Auto fan configuration
SHORT - In cool and heat modes – fan works on demand (auto fan)
- Suitable for No-valve systems (unit runs on fan without valves)
OPEN - In cool mode – fan works continuously.
- In heat mode – fan works on demand (auto fan)
Jumper JP2 – 2-Pipe / 4-Pipe
OPEN - 2-Pipe configuration (one valve).
- “Cool” output connected to the valve (cooling and heating).
- No Auto change-over mode
SHORT - 4-Pipe configuration (two valves)
- “Cool” output connected to cool valve.
- “Heat” output connected to heat valve.
T2 logic – Mode selection in 2-Pipe system
T2 Connected:
- System mode defined by T2 sensor as follows:
T2 < 20°C COOL
T2 > 20°C HEAT
- Mode is NOT selectable by occupant.
T2 NOT Connected:
- Mode selected by occupant.
T3 logic – Fan operation in heat mode
T3 < 27°C Fan OFF (preventing cold drafts)
T3 > 32°C Fan ON
T4 logic – Fault input
- Voltage free, normally close input.
- When open, the unit will turn OFF and LEDS in M101P will flash.
On/Off Mode Fan
(OR)
Rev.2 New rev.PCB 27/07/2010
Return
Air
sensor
Important!
The unit will not operate without the return air sensor.
/