ESAB Safety test User manual

Type
User manual
Maintenance and inspection procedure
1
FOREWORD
THI S P RO C ED UR E IS BA SED O N IE C 6 09 74 - 4 PERI OD IC IN SPE C TION A N D T ESTI NG
1 SCOPE
This document specifies test procedures for periodic inspection and, after repair, to ensure electrical safety.
These test procedures are also applicable for maintenance.
This document is applicable to power sources for arc welding and allied processes designed in accordance with
IEC 60974-1 or IEC 60974-6. Stand-alone ancillary equipment designed in accordance with other parts of IEC
60974 may be tested in accordance with relevant requirements of this part of IEC 60974.
NOTE 1 The welding power source can be tested with any ancillary equipment fitted that can affect the test results.
2 NORMATIVE REFERENCES
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments)
applies.
IEC 60050-151, International Electrotechnical Vocabulary Part 151: Electrical and magnetic devices
IEC 60050-195, International Electrotechnical Vocabulary Part 195: Earthing and protection against electric shock
IEC 60050-851, International Electrotechnical Vocabulary Part 851: Electric welding
IEC 60974-1:2012, Arc welding equipment Part 1: Welding power sources
IEC 60974-6, Arc welding equipment Part 6: Limited duty equipment
IEC 61557-4, Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500
V d.c. Equipment for testing, measuring or monitoring of protective measures Part 4: Resistance of earth connection and equipotential bonding
IEC 61140, Protection against electric shock Common aspects for installation and equipment
3 TERMS AND DEFINITIONS
For the purposes of this document, the terms and definitions given in the IEC 60050-151, the IEC 60050-195, the
IEC 60050-851, the IEC 60974-1, as well as the following, apply.
3.1
expert
competent person
skilled person
a person who can judge the work assigned and recognize possible hazards on the basis of professional training,
knowledge, experience and knowledge of the relevant equipment.
Note 1 to entry: Several years of practice in the relevant technical field may be taken into consideration in assessment of professional training.
[SOURCE: IEC 60974-1:2012, 3.3]
3.2
instructed person
person informed about the tasks assigned and about the possible hazards involved in neglectful behavior.
Note 1 to entry: If necessary, the person has undergone some training
[SOURCE: IEC 60974-1:2012, 3.4]
Maintenance and inspection procedure
2
3.3
periodic inspection and test
examination carried out at specified intervals to reduce the risk of hazard.
3.4
maintenance
service carried out at specified intervals to reduce the risk of hazard and failure.
3.5
repair
restore to a safe and intended operating condition
3.6
test personnel
instructed person or expert that has been trained and authorized to perform periodic inspection and testing
4 GENERAL REQUIREMENTS
4.1 Qualification of test personnel
Tests of welding equipment can be hazardous and shall be carried out by an instructed person or expert in the
field of electrical repair, preferably also familiar with welding, cutting and allied processes. Instructed persons
should be considered qualified for simple periodic testing and maintenance provided the equipment enclosure
does not have to be opened.
NOTE Hazardous voltages and currents inside the equipment enclosure can cause shock, burn or death. Only expert test
personnel can open the equipment.
4.2 Test conditions
Tests shall be carried out at an ambient air temperature between 10 °C and 40 °C on dry and cleaned welding
equipment.
Before the work station enters and the inspection begins the workplace should be checked and
controlled to be safe together with a local representative.
4.3 Measuring instruments
The accuracy of measuring instruments shall be class 2.5 as a minimum, except for the measurement of
insulation resistance, where the accuracy of the instruments is not specified but shall be taken into account for the
measurement. The voltmeter shall have an internal resistance of at least 1MΩ and indicate mean value.
4.4 Periodic inspection and test
The periodic inspection and test specified in Table 1 shall be carried out.
Tests shall be documented in a test report in accordance with 7.1.
During the tests, complementary instructions from the manufacturer shall be followed.
4.5 Maintenance
The manufacturer’s maintenance schedule and instructions shall be followed.
Tests shall be documented in a test report in accordance with 7.1.
Maintenance and inspection procedure
3
4.6 Repair
After repair or replacement of a component which restores a welding or cutting function, an expert shall select
appropriate tests to be carried out, as specified in Table 1.
NOTE After a minor repair such as replacement of a lamp, wheel or under carriage, the tests given in Table 1 may not be
necessary.
Tests shall be documented in a test report in accordance with 7.1.
During the tests, complementary instructions from the manufacturer shall be observed (for example, circuit
diagrams, spare part list, functional test of power source and ancillary equipment, etc.).
4.7 Test sequence
The test sequence is given in Table 1.
Table 1 Test sequence on used arc welding equipment
Periodic inspection and test
After repair
a) Visual inspection in accordance with 5.1
a) Visual inspection in accordance with 5.1
b) Electrical test:
protective conductor resistance in accordance with 5.2
insulation resistance in accordance with 5.3
no-load voltage in accordance with 5.7
b) Electrical test:
protective conductor resistance in accordance with 5.2
insulation resistance in accordance with 5.3
no-load voltage in accordance with 5.7
c) Functional test:
no requirement
c) Functional test:
function in accordance with 6.1
supply-circuit on/off switching device in accordance with
6.2
voltage-reducing device in accordance with 6.3
magnetic gas valve in accordance with 6.4
signal and control lamps in accordance with 6.5
d) Documentation in accordance with Clause 7
d) Documentation in accordance with Clause 7
a If the insulation resistance test cannot be carried out for without disconnection of any component of the
equipment to be tested (e.g. interference suppression networks, protection capacitors or surge protection
component), the insulation resistance test may be replaced by the optional tests specified in item b).
b Only if there are accessible conductive surfaces not connected to the protective circuit.
5 PROTECTION AGAINST ELECTRICAL SHOCK
5.1 Visual inspection
Visual inspection shall be carried out in accordance with the conditions of use of welding equipment and the
manufacturer’s instructions.
An example of items for a visual inspection is given in Annex A.
Maintenance and inspection procedure
4
5.2 Continuity of the protective circuit
For mains-powered welding equipment of protection class I, including ancillary equipment (for example, cooling
system) having mains connecting cables up to a length of 5,0 m, the maximum measured protective conductor
resistance shall not exceed 0,3 Ω.
For cables longer than 5,0 m, the permissible value of the protective conductor resistance is increased by 0,1 Ω
per additional 7,5 m cable. The maximum permissible value of the protective conductor resistance is 1 Ω.
Conformity shall be checked by measuring the resistance between the protective conductor
contact at the plug and exposed conductive parts with testing equipment according to
IEC 61557-4.
During the measurement, the cables shall be bent, flexed or twisted along the whole length, especially in the
vicinity of cable entries into the enclosure, in order to detect interruptions in the protective conductor.
5.3 Insulation resistance
The insulation resistance shall not be less than the values given in Table 2.
Table 2 Insulation resistance
Measurement
a
Resistance
Insulation
Supply circuit
welding circuit
5,0 MΩ
Double or reinforced
Welding circuit
protective circuit
2,5 MΩ
Basic
Supply circuit
protective circuit
2,5 MΩ
Basic
Supply circuit of Class II equipment
accessible surfaces
b
5,0 MΩ
Double or reinforced
a
Control circuits are tested together with the circuit to which they are galvanically connected. Accessible control circuits
separated from all other circuits are tested according to the manufacturer’s specification.
b
For measurement to accessible non-conductive surfaces, such surfaces shall be considered to be covered by metal foil.
c Interference suppression capacitors are not disconnected.
Conformity shall be checked by the stabilized measurement of the insulation resistance by application of a d.c.
voltage of 500 V at room temperature.
During the measurement, torches shall be disconnected, solid-state electronic components and their protective
devices may be short-circuited, and liquid cooling units shall be tested without liquid.
5.7 No-load voltage (U0)
The peak values of the maximum no-load voltage at all possible settings of the power source should not be higher
than ±15 % of no-load voltage U0 and shall not exceed the values given in Table 13 of IEC 60974-1 when the
power source is supplied at rated supply voltage and frequency.
Before testing, arc striking and stabilizing devices shall, if necessary, be removed or bypassed according to the
manufacturer’s instructions (see also instructions for use or manufacturer’s testing instructions).
The no-load voltage is measured between welding output terminals. If this is not possible for safety or control
reasons, the no-load voltage is measured between torch and welding return cable connection. This test is not
required for plasma cutting power sources.
If rated reduced no-load voltage (UR) or rated switched no-load voltage (US) are defined on the rating plate, UR
or US shall be measured instead of U0.
Conformity shall be checked by measurement of:
a) r.m.s. values
A true r.m.s. meter is used with a resistance of the external welding circuit of 5 kΩ.
b) peak values
To obtain reproducible measurements of peak values, omitting impulses which are not dangerous, a circuit as
shown in Figure 4 is used.
Maintenance and inspection procedure
5
Figure 4 Measurement of peak values
The voltmeter shall indicate mean values. The measurement range chosen shall be as near as possible to the
actual value of the no-load voltage. The voltmeter shall have an internal resistance of at least 1 MΩ.
The tolerance of the component values in the measurement circuit shall not exceed ±5 %. The minimum power
for the resistor of 0,2 kΩ is 65 W.
The rheostat shall withstand a current value of 0,6 A. The capacitors shall have a minimum voltage rating of 200
V.
6 FUNCTIONAL TEST
6.1 Function
Each safety-related function judged as relevant by the test personnel shall be checked for correct operation.
Conformity shall be checked by operating the device and by checking whether the welding power source operates
correctly.
6.2 Supply-circuit on/off switching device
Where an integral supply-circuit on/off switching device (for example, switch, contactor or circuit-breaker) is fitted,
this shall:
a) open or close all ungrounded mains conductors;
b) clearly indicate whether the circuit is open or closed.
Conformity shall be checked by visual inspection and measurement.
6.3 Voltage-reducing device
Where a voltage-reducing device is fitted, it shall be checked for correct operation.
Conformity shall be checked by measurement of reduced no-load voltage (see 5.7) and visual inspection of
indicator in load and no-load condition.
Circuit in figure 4 is in
ESAB test box TB1
Maintenance and inspection procedure
6
6.4 Magnetic gas valve
Each magnetic gas valve (for example, TIG, MIG/MAG, plasma power sources), shall be checked for correct
operation.
Conformity shall be checked by visual inspection and the following operations or by a test specified by the
manufacturer.
a) Function
Operate the trigger of the torch and check by means of the gas flow whether the magnetic gas valve operates.
b) Leakage
Pressurize the system and verify there is no leak, for example, there is no pressure drop.
NOTE Flexible gas tubes and their connections can be sources of leaks.
6.5 Signal and control lamps
Signal or control lamps shall be checked for correct operation if possible.
Conformity shall be checked by visual inspection.
7.1 Test report
The test report shall include
a) identification of tested arc welding equipment;
b) date of testing;
c) supply voltage;
d) test results;
e) signature, identification of the test personnel and his organization;
f) identification of testing equipment.
The test report, after repair, shall include all the tests given in Table 1 and an indication shall be made
if a particular test has not been carried out.
An example of a test report is given in Annex B.
7.2 Labelling
A label shall be attached to the equipment to indicate that it has passed the test.
The label shall state the date of testing or recommended date for next inspection depending on local
regulation.
Maintenance and inspection procedure
7
*ESAB recommended measuring/test equipment.
Multimeter according to 4.3
Insulation resistance meter, 500V
ESAB test box TB1 part nr. 0460 868 880
Maintenance and inspection procedure
8
Maintenance and inspection procedure for ESAB equipment
Following pages should be kept together with Test Report
5.1 Visual inspection
Turn off and disconnect the mains power supply to the power source.
Note each unit’s serial no. in the test report for identification.
During visual Inspection, each safety related function judged as relevant by the test
personnel, shall be checked for correct operation.
During visual inspection, the following listed items shall be checked:
5.1.1 Mains supply:
a) defective, damaged cable
b) deformed, faulty plug
c) broken or thermally damaged plug pins
d) ineffective cable anchorage
e) cables and plugs unsuitable for the intended use and performance
Passed Not passed (see remark in protocol)
5.1.2 Intermediate cables:
a) defective, damaged cable
b) deformed, faulty or thermally damaged plug/socket
c) deformed, faulty or thermally damaged sleeves/pins
d) ineffective, cable anchorage
e) cables and coupler unsuitable for the intended use and performance
Passed Not passed (see remark in protocol)
5.1.3 Enclosure:
a) missing or damaged parts
b) unauthorized modifications
c) cooling openings blocked or missing air filters
d) signs of overload and improper use
e) missing of defective protective covers
f) conductive objects put in the enclosure
g) distance between live parts and enclosure
Passed Not passed (see remark in protocol)
5.1.4 Return clamp:
a) missing or defective insulation
b) defective connections
c) defective, damaged switches
d) other damage
Passed Not passed (see remark in protocol)
Maintenance and inspection procedure
9
5.1.5 Welding gun/electrode holder:
a) Are all parts securely attached (torch, torch mount, cable assembly)?
b) Are all hoses connected correctly and protected from damage?
c) Is the Euro central connector or direct connector fastened tightly?
d) Is the cable assembly length correct and suitable for the installation?
e) The cable must not be bent sharply, any risk of the cable catching on another object
must be eliminated.
f) Is the wire liner clean and properly assembled?
Passed Not passed (see remark in protocol)
5.1.6 Welding circuit
a) _ defective damaged cable
b) _ deformed, faulty or thermally damaged connector/sockets
c) _ cables and connectors unsuitable for the intended use and performance
Passed Not passed (see remark in protocol)
5.1.7 General condition
a) _ cooling liquid circuit leakage or incorrect cooling liquid level
b) _ defective gas hoses and connections
c) _ poor legibility of markings and labelling
d) _ other damage or signs of improper use
e) _cooling fans
Passed Not passed (see remark in protocol)
5.1.8 Wire feeder/ wear parts:
a) inlet, intermediate and outlet nozzle
b) drive , gear and pressure rollers
c) defective, damaged switches
d) brake hub
e) other damage
Passed Not passed (see remark in protocol)
6.4 Magnetic gas valve
a) Function. Operate the trigger of the torch and check by means of the gas flow
whether the magnetic gas valve operates.
b) Leakage. Pressurize the system and verify there is no leak, for example, there is no
pressure drop.
NOTE Flexible gas tubes and their connections can be sources of leaks
Passed Not passed (see remark in protocol)
Maintenance and inspection procedure
10
6.5 Controls and indicators
a) _ defective switches, meters and lamps
b) _ incorrect fuses accessible from outside of the enclosure
Passed Not passed (see remark in protocol)
Cleaning the equipment.
After the visual inspection has been performed and before making the electrical test the
equipment shall be cleaned!
Note! The equipment shall be disconnected from the mains supply!
Welding equipment
Check that the welding equipment is not clogged with dirt.
Remove the side panels to be able to reach all necessary compartments.
Which cleaning methods apply depend on: the welding process, arc time, placement and the
surrounding environment.
It is preferable to use an industrial vacuum cleaner to remove dust and dirt.
Using compressed air can be used with reduced pressure but may collect dust in contactors,
transformers and terminals. This may also cause clogged or blocked air inlets/outlets and
result in overheating.
Replacing and cleaning the dust filter (if applicable)
- Remove the dust filters.
- Blow the filters clean with compressed air (reduced pressure).
- Ensure that the filter with the finest mesh is placed towards the grill.
- Reinstall the filter.
Passed Not passed (see remark in protocol)
Electrical test
Disconnect the welding power source from the mains supply.
Note the measured values in the test report!
9 Welding Circuit
7 Supply circuit
8 Protective circuit
Maintenance and inspection procedure
11
5.2 Continuity of the protective circuit.
Measure the resistance of the protective circuit from the screw (1) to the protective earth (8)
in the mains plug (2).
During the measurement the cable shall be bent, flexed and twisted along the whole length in
order to detect interruptions in the protective conductor.
- Required value for cables up to 5 m, max 0.3 Ω.
5.3 Check the insulation resistance
Use an insulation tester with the measurement voltage set to 500 VDC.
Connect all three phase in the mains plug (2) to one point (supply circuit (7)) and the welding
outlets (3,4) to one point (welding circuit (9))
As alternative, the test can be done without connecting the three phases and welding circuit
together and test each node against each other (total 11 tests)
For welding power sources with primary contactor:
Connect all three phase in the mains plug (2) to one point (supply circuit (7)) and the welding
outlets (3,4) to one point (welding circuit (9))
a. Open the small protective cover on top of primary contactor (6).
b. With an isolated tool (5) press down the mechanism of primary contactor (6).
c. Turn the mains switch of the welding power source to START/ON and hold it there.
d. Measure from the supply circuit (7) to the welding circuit (9).
- Required value not less than 5 MΩ.
e. Measure from the welding circuit (7) to the protective circuit (8).
- Required value not less than 2.5 MΩ.
f. Measure from the supply circuit (7) to the protective circuit (8).
- Required value not less than 2.5 MΩ.
g. Turn the mains switch of the welding power source to OFF and release primary contractor.
For welding power sources without primary contactor
a. Turn the mains switch of the welding power source to START/ON and hold it there.
b. Measure from the supply circuit (7) to the welding circuit (9).
- Required value not less than 5 MΩ.
c. Measure from the welding circuit (7) to the protective circuit (8).
- Required value not less than 2.5 MΩ.
Maintenance and inspection procedure
12
d. Measure from the supply circuit (7) to the protective circuit (8).
- Required value not less than 2.5 MΩ.
e. Turn the mains switch of the welding power source to OFF.
5.7 Check the no-load voltage.
Use the ESAB test box TB 1. If the welding power source has an activated VRD function
then proceed to step 6.3.
a. Connect the positive (3) and negative (4) welding outlets to the positive and negative
terminals (DCIN) of the TB 1.
b. Connect a voltmeter to VPEAK of the TB 1.
c. Connect the welding power source to the mains supply.
d. Turn the control knob of the TB 1 anti-clockwise to 0.2.
e. Turn the mains switch of the welding power source to ON.
f. Set welding power source to MMA or SAW.
g. For MMA, set the welding current control on the welding power source to maximum.
h. For MMA, slowly turn the control knob of the TB 1 clockwise from 0.2 to 5.2 while checking
the voltmeter for the highest value.
i. For SAW, set OCV/arc voltage on the PEK/PEH to maximum.
j. For SAW, release the wire and press start on PEK/PEH. Slowly turn the control knob of the
TB 1 clockwise from 0.2 to 5.2 while checking the voltmeter for the highest value.
-Measured value shall not exceed the allowable value 113 VPEAK
k. Turn the mains switch of the welding power source to OFF.
l. Disconnect the welding power source from the mains supply.
6.3 Check of no-load voltage with the VRD activated.
Use the ESAB test box TB 1. This test is only conducted when the VRD function is activated.
a. Connect the positive (3) and negative (4) welding outlets to the positive and negative
terminals (DCIN) of the TB 1.
b. Connect a voltmeter to VPEAK of the TB 1.
c. Connect the welding power source to the mains supply.
d. Turn the control knob of the TB 1 anti-clockwise to 0.2.
e. Turn the mains switch of the welding power source to ON.
f. Set welding power source to MMA.
g. Set the welding current control on the welding power source to maximum.
h. Check the voltage with the voltmeter. Measured value shall not exceed 35 V.
i. Check that the LED indicates active VRD function by a steady green light.
j. Turn the mains switch of the welding power source to OFF.
k. Disconnect the welding power source from the mains supply.
Maintenance and inspection procedure
13
Functional test
Each safety related function judged as relevant by the test personnel shall be checked
for correct operation.
Conformity shall be checked by operating the device and by checking whether the welding
power source operates correctly.
Check the supply circuits on/off switching devices (welding power source with
primary contactor)
a) Disconnect the welding power source from the mains supply.
b) Remove the cover.
c) Turn the mains switch of the welding power source to OFF.
d) Measure from the supply pins of the mains plug to the primary contactor.
- Measure L1 - L1 of primary contactor.
Required value, open circuit
- Measure L2 - L2 of primary contactor.
Required value, open circuit
- Measure L3 - L3 of primary contactor.
Required value, open circuit
e) Open the small protective cover on top of primary contactor.
f) With an isolated tool (5) press down the mechanism of primary contactor.
g) Measure from the supply pins in the mains plug to the primary contactor.
- Measure L1 - L1 of primary contactor.
Required value, less than 0.5 Ω.
- Measure L2 - L2 of primary contactor.
- Required value, less than 0.5 Ω.
- Measure L3 - L3 of primary contactor.
Required value, less than 0.5 Ω.
Maintenance and inspection procedure
14
h) Turn the mains switch of the welding power source to OFF.
- Measure contacts at mains switch (each contact pair separately).
Required value, open circuit.
i) Turn the mains switch of the welding power source to ON.
- Measure contacts at mains switch (each contact pair separately).
Required value, less than 0.5 Ω.
j) Turn the mains switch of the welding power source to OFF.
k) Reassemble the cover.
Check the supply circuits on/off switching devices (welding power source without
primary contactor)
l) Turn the mains switch of the welding power source to OFF.
- Measure contacts at mains switch (each contact pair separately).
Required value, open circuit.
m) Turn the mains switch of the welding power source to ON.
- Measure contacts at mains switch (each contact pair separately).
Required value, less than 0.5 Ω.
n) Turn the mains switch of the welding power source to OFF.
o) Reassemble the cover.
Testwelding etc.
3). Check signal and control lamps
Check the function of the display indicators by turning on the unit and visually check
the front panel.
4). Check the function of the welding power source by welding.
6). Write the test report.
7). If the equipment passes all the tests, attach appropriate label with signature and date of
the test and/or recommended date for next inspection.
Maintenance and inspection procedure
15
TEST REPORT
Company:
Location:
Equipment:
Serial number:
Manufacturer:
ESAB
Type:
Testing Equipment:
5.1 VISUAL INSPECTION
Passed Not passed (see remark in
protocol)
ELECTRICAL TEST
Limit
Measured values
5.2 Protective conductor
resistance
0.3 Ω
5.3 Insulation resistance
d. Supply circuit/
Welding circuit (500 VDC)
5 MΩ
e. Welding circuit/
Protective circuit (500 VDC)
2.5 MΩ
f. Supply circuit/
Protective circuit (500 VDC)
2.5 MΩ
No-load voltage
5.7 without VRD
Vpeak
113 VDC
6.3 with VRD activated
Vpeak
35 VDC
Passed Not passed (see remark in protocol)
6 FUNCTIONAL TEST
Passed Not passed (see remark in
protocol)
Remarks
Date
Inspected by
Signature
Date
Local representative
Signature
Testing company
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

ESAB Safety test User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI