Samsung AG015KSVAFH/AA Installation guide

Category
Split-system air conditioners
Type
Installation guide

This manual is also suitable for

DVM CHILLER
Installation manual
AG010KSV✴✴✴ / AG015KSV✴✴✴ Series
Å· Thank you for purchasing this Samsung Product.
Å· Before operating this unit, please read this Installation manual carefully and retain it for future
reference.
2
English
Contents
INSTALLATION
Safety information 3
Preparing for installation 8
Specications 8
DVM CHILLER Classication 10
Moving the product 10
Center of Gravity Location 11
Accessories (Basic specication) 11
Field Supply 11
Selecting installation location 12
Installation Guide at the seashore 12
Required space for installation 14
Base construction and installation 16
Supporting base construction 16
Product installation 17
Base mount and anchor bolt position 17
Examples of draining work 17
Installation precautions 18
Installing the wind/snow prevention duct 20
Installing the discharge duct around obstacles 20
Installing the discharge duct in cold regions 20
Installing the discharge duct in regions with strong wind 21
Water pipe installation 22
Water pipe diagram 22
Water pipe installation 23
Securing water storage 26
Water pipe installation 26
ELECTRICAL WORK
Electrical wiring work 27
Specication of the circuit breaker and power cable 27
Power and communication cable conguration 28
Connecting the power cable 29
Connecting the communication cable 30
External contact wiring work 30
Selecting solderless ring terminal 36
Connecting the power terminal 37
Fixing the power cable 39
Fixing the ground cable 39
Withdrawing the power cable 40
Installing the Solution device 40
Grounding work 40
Setting key function 42
Setting hydro controller option 42
How to set hydro controller option 45
Setting inverter controller option 51
BEFORE OPERATION
Check points after installation 57
Trial operation 58
Trial operation for each CHILLER unit 59
MAINTENANCE
Maintenance 61
Name of the parts 61
Water pipe installation 62
Water maintenance standard 64
Maintaining plate type heat exchanger 66
Stopping during winter time 67
Stopping for a long time 67
Inspection for normal operation 68
Chilled/Heating water ow rate range 68
Chilled water management 69
Water temperature range 69
Freeze prevention 70
Error display 73
Error history display 76
Air tightness test and vacuuming 76
Troubleshooting 78
Periodic maintenance 80
Quick Smart Features 83
INSTALLATION
3
English
California Proposition 65 Warning (US)
WARNING :
Cancer and Reproductive Harm - www.P65Warnings.ca.gov.
This DVM Chiller must be installed by qualied personnel and in accordance with all national, state, provincial and
local building, electrical, mechanical, plumbing and other applicable codes.
Please follow the following safety information for safety of the installer and the user.
Safety information
DVM Chiller uses R-410A refrigerant.
ŷ When moisture or foreign substances enter into the
refrigerant pipe using R-410A, it may affect the
performance and reliability of the product. Safety
precautions must be obeyed when installing the
refrigerant pipe.
ŷ Since R-410A is an azeotrope refrigerant, it must be
charged in liquid phase. (A blend of the refrigerant
may change if you charge in vapor phase which
could cause product malfunction.)
The manufacturer is not responsible for any installation
or performance problem of the load side indoor unit
and water pipes.
ŷ Product for low temperature (below 41°F) must use
anti-freeze to manage freezing point (concentration
of anti-freeze) according to usage range.
ŷ Freezing point of anti-freeze should be checked
periodically after installation during usage. (once a
year or more)
ŷ Maintain the temperature of chilled/heating water to
recommended range for stable operation.
The manufacturer is not responsible for freezing
and bursting of heat exchanger caused by incorrect
installation or conguration.
After completing the installation and test operation,
explain to the user how to use and maintain the
product. Also, hand over this installation manual so that
it can be stored by the user.
The manufacturer of DVM Chiller is not responsible
for the incidents occurred by improper installation.
Installer is responsible for any installation related
claims from the user occurred by neglecting warnings
and cautions stated in this manual.
Generally, DVM Chiller should not be relocated after
installation. But when it has to be relocated for
inevitable reasons, please contact Samsung's qualied
dealers for DVM Chiller.
WARNING
Hazards or unsafe practices that may result in severe
personal injury or death.
CAUTION
Hazards or unsafe practices that may result in minor
personal injury or property damage.
Follow directions.
Do NOT attempt.
Make sure the machine is grounded to prevent
electric shock.
Unplug the power plug from the wall socket.
Do NOT disassemble.
For operation
WARNING
Do not use water containing chemicals such as
chlorine for chilled/heating water as it can cause
corrosion on stainless steel or copper.
ŷ This may result in product malfunction.
Do not block air inlet or outlet of the product.
ŷ It may cause performance decrease or
malfunction of the product.
Do not attempt to disassemble, modify, or repair
the product.
ŷ Failure to do so may result in water leakage,
electric shock or re. Contact the service center.
Do not use the product where oil particles such as
cooking oil and machine oil exist.
ŷ There are potential risks of electric shock or re.
Do not use the product where smokes consisted
by oil particles, such as kitchen, ammable gas,
corrosive gas, or metallic dust exist.
ŷ Failure to do so may result in re or phenomenon.
INSTALLATION
Safety information
4
English
Do not operate the product with power switch or
circuit breaker.
ŷ Potential risk of electric shock or re.
ŷ If automatic blackout restore is set, fan may spin
suddenly and it may cause injury.
If fuse load switch is used, do not use incorrect
fuse capacity/size.
ŷ Usage of incorrect wire may result in product
malfunction or re.
Do not use ammable gas (such as hair spray or
insecticide) near the product.
ŷ There are potential risks of electric shock or re.
If there is any problem (such as burning smell),
stop operation and shut off the circuit breaker.
ŷ Otherwise, it may cause product malfunction,
electric shock, or re. Contact the service center.
Use chilled/heating water which is appropriate
according to water maintenance standard.
ŷ Deterioration of water may cause water leakage.
Contact the merchandise or service center to clean
inside of the product.
ŷ Error on selecting cleaner and cleaning the
product may harm rubber part and cause water
leakage.
ŷ If the cleaner reaches to electric parts or motor,
it may cause product malfunction, smoke, or re.
CAUTION
Do not use the product for preservation purposes.
ŷ If you use this product for unintended purposes,
such as preservation of machinery, food, art
work or breeding animals or plants, it may cause
damage to their performance, quality or life.
Do not use the holder which is worn out for
longtime usage.
ŷ It may cause injury due to falling down of the
product.
Do not step onto the product or place any objects
on the product.
ŷ It may cause injury due to falling down of the
product.
Do not operate the product with the cover of
exterior or electric box opened.
ŷ It may cause electric shock or re.
Do not place any objects that are not allowed to be
wet.
ŷ It may get wet by dripping water caused
by product or refrigerant pipe freezing,
contaminated air lter, blocked drain valve.
Do not change settings for protection device.
ŷ It may cause re.
Do not use chilled/heating water for drinking.
ŷ It is harmful for humans.
ŷ For hot water supply, use indirect heat exchange.
Do not wash the product with water.
ŷ It may cause electric shock.
Do not operate protection devices forcibly.
ŷ This may result in re or explosion.
Do not touch high temperature part such as
compressor and refrigerant pipe.
ŷ It may cause burns.
Do not touch inlet or aluminum plate.
ŷ It may cause injury.
INSTALLATION
5
English
When outdoor temperature drops below 32°F, take
appropriate countermeasures to prevent freezing
of water.
ŷ Freeze protection such as using brine, heater,
pump operation, etc. is necessary.
ŷ Drain all water and cut-off the power supply
when the product is not operated during winter
time.
Use appropriate refrigerant and refrigerant oil.
ŷ This may result in re or explosion.
Stop the operation and close the circuit breaker
while repair service.
ŷ Otherwise, it may cause electric shock or injury.
Be aware of step board while working on high
place.
ŷ This may result in injury by falling down if the
step board is not stable.
Use chilled/heating water which is appropriate
according to water maintenance standard.
(Refer to page 64 for water maintenance standard.)
ŷ Deterioration of water may cause water leakage.
Follow regulations for disposing brine, cleaner, and
refrigerant.
ŷ It is against the law to dispose of improperly.
For installation
WARNING
Do not install the product by users.
ŷ It may result in water leakage, electric shock,
or re if installation is not precise. Contact the
merchandise or service center.
Consult qualied installer or dealer for installation.
ŷ When the installation is done by unqualied
people, it may cause water leakage, electric
shock or re.
Installation should be done by following the
installation manual accurately.
ŷ When installation is not done properly, it may
cause water leakage, electric shock or re.
Do not install the eld supply parts by users.
ŷ Do not use any other product other than the
manufacturer recommended. It may result in
water leakage, electric shock, or re if installation
is not precise. Contact the merchandise or
service center.
Do not move or reinstall the product by users.
ŷ It may result in water leakage, electric shock,
or re if installation is not precise. Contact the
merchandise or service center.
Do not close the circuit breaker for protect devices.
ŷ Otherwise, a re may occur.
Do not install power cables between the products.
ŷ It may cause re.
Make sure to install the product in a place strong
enough to withstand its weight.
ŷ Otherwise, it may result in falling down,
vibration, noise of the product.
Install the product securely to resist strong wind or
earthquake.
ŷ Otherwise, it may result in falling down,
vibration, noise of the product.
Fix the product securely to resist natural
phenomenon such as earthquake.
ŷ If the product is not properly xed, it may fall
down and cause an accident.
ŷ When installing the unit in a small area, take
measure to keep the refrigerant concentration
from exceeding allowable safety limits in case
of refrigerant leakage. Consult the dealer for
precautionary measure before the installation.
ŷ When refrigerant leaks and exceed dangerous
concentration level, it may cause suffocation
accidents.
INSTALLATION
Safety information
6
English
Check the followings before installation and repair/
maintenance service.
ŷ Before brazing, remove dangerous and/or
ammable things around workplace that may
cause an explosion and re.
ŷ Before brazing, remove the refrigerant within
the pipe or the product.
ŷ If you perform welding while refrigerant is in
the pipe, it may increase the pressure of the
refrigerant and cause the pipe to burst. If the
pipe bursts or explodes, it may cause severe
injury to the installer.
ŷ Use the nitrogen gas to eliminate oxide inside
the pipe during brazing.
Electric work must be done by qualied people,
complying the national wiring regulations and
installed according to the instruction stated in the
installation manual and must comply regulated
electrical specication.
ŷ Capacity shortage on the power circuit or
improper installation may cause electric shock or
re.
Wiring must be connected with the designated
wires and it must be xed securely so that it does
not apply any external force to the connection part
of the terminals.
ŷ If connection or xation is not properly done, it
may cause heat generation or re.
Neatly arrange the wires in the electrical parts to
make sure that electrical cover is closed securely
without any gaps.
ŷ If the cover is not properly closed, heat may
generate on the terminal and cause electric
shock or re.
Exclusive circuit breaker (MCCB, ELB) must be
installed to the power supply.
ŷ Use ELCB that has harmonic wave prevent
function since the product uses inverter
compressor.
ŷ If the auxiliary circuit breaker is not installed,
power will not be cutoff in case of overcurrent
or current leakage and cause electric shock or
re.
ŷ Do not use damaged parts. Otherwise, a re or
electric shock may occur.
You must cut-off the power before you work
on, or adjust any power supply part for product
installation, maintenance, repair or any other
services.
ŷ This may result in electric shock.
ŷ Even when the power is off, it is very dangerous
to touch the inverter PCB and the fan PCB since
high pressure DC voltage is charged for those
parts.
ŷ When replacing/repairing the PCB, cut-off
the power and wait until the DC voltage is
discharged before replacing/repairing them.
(Wait for more than 15 minutes to allow those
parts to be fully discharged.)
You must ventilate the room if the refrigerant gas
leaks during the installation.
ŷ Toxic gas can be generated when the refrigerant
gas gets in contact with ammable substance.
Use chilled/heating water which is appropriate
according to water maintenance standard.
(Refer to page 64 for water maintenance standard.)
ŷ Deterioration of water may cause water leakage.
Contact the merchandise or service center for
measures against the situation where leaked
refrigerent is accumulated.
ŷ When refrigerant leaks and exceed dangerous
concentration level, it may cause suffocation
accidents. When installing the unit in a small
area, take measure to keep the refrigerant
concentration from exceeding allowable safety
limits in case of refrigerant leakage.
Follow regulations for disposing brine, cleaner, and
refrigerant.
ŷ It is against the law to dispose illegally, and also
harmful for humans and environment.
INSTALLATION
7
English
Wiring must be connected with the designated
wires and it must be xed securely so that it does
not apply any external force to the connection part
of the terminals.
ŷ If connection or xation is not properly done, it
may cause heat generation or re.
Please connect ground wire.
ŷ If the ground wire is not properly xed, there is
potential risk of electric shock or re.
ŷ Do not connect the grounding cable to a gas
pipe, water pipe, lightening conductor or the
grounding cable of the telephone.
CAUTION
Drain system must be constructed according to this
installation manual so that condensation water
drains properly, and drain system should be kept
warm to prevent dew condensation.
ŷ When water management is not done properly,
water leakage may occur and cause property
damage.
Install the power cable and communication cable
of the product at least 5 ft away from the electric
appliances and install it at least 6.6 ft away from
the lightning conductor.
ŷ Even if the cables are installed more than 6.6 ft
away from electronics, noise can be generated
from them depending on the status of the
electric wave.
Do not leave any obstacles around the inlet and
outlet of the product.
ŷ It may cause product failure or other accidents.
Do not install the product in following places.
ŷ A place where noise and warm air of the product
may disturb neighbors
- It may cause property loss.
ŷ A place full of mineral oil, place where oil
scatters or with oil vapors such as a kitchen
- Plastic parts may get damaged and cause
water leakage, or maybe even cause product
to fall down.
- The performance of the heat exchanger may
decrease or cause product failure.
ŷ A place near exhaust pipes or ventilation outlet
where corrosive gas such as ammonia gas or
sulfurous acid gas are being generated
- Copper pipe and connection parts may corrode
causing refrigerant leakage.
ŷ A place with a machine that generates
electromagnetic waves
- Electromagnetic waves may cause problems in
control system and product may not operate
normally.
ŷ A place where there is a danger of combustible
gas leakage or the place where thinner or
gasoline is handled
- There is a risk of re or explosion.
ŷ A place with airborne carbon ber or ammable
dust
ŷ A place near seashore or hot spring where there
is risk of product corrosion
Install MCCB for each product.
ŷ Use ELCB that has harmonic wave prevent
function since the product uses inverter
compressor.
ŷ It may cause electric shock or re if more than
two products are installed on one MCCB.
Make sure to install drain pipe for draining
performed correctly.
ŷ If the installation is not done properly,
water leakage may occur and cause product
malfunction.
Wear protective equipment (such as safety gloves, goggles,
and headgear) during installation and maintenance works.
Installation/repair technicians may be injured if protective
equipment is not properly equipped.
INSTALLATION
8
English
Preparing for installation
Specications
Model Name AG010KSVAFH AG015KSVAFH
Power Supply
Ä­
, #, V, Hz 3, 3, 208~230, 60 3, 3, 208~230, 60
Capacity
Ton (Nominal) usRT 10 15
Cooling *1) kBtu/h 120.0 168.0
Heating *2) kBtu/h 120.0 171.0
Power
Power Input
Cooling *1)
kW
10.71 16.63
Heating *2) 11.54 17.45
Current Input
Cooling *1)
A
29.59 47.24
Heating *2) 31.88 48.20
MCA A 52.00 70.00
MOP A 70.00 90.00
COP
Normal Cooling *1) (Btu/h)/W 11.20 10.10
Normal Heating *2) (Btu/h)/W 10.40 9.80
Efciency IPLV (Btu/h)/W 20.5 18.8
Compressor
Type - Scroll Inverter Scroll Inverter
Output kW × n 6.45 x 2 6.45 x 2
Model Name - DS4GJ5066EVA DS4GJ5066EVA
Oil Type - PVE PVE
Fan
Type - Propeller Propeller
Output x n W 630 x 2 630 x 2
Air Flow Rate
CMM
(CFM)
364 (12,855) 364 (12,855)
External Static
Pressure
MAx.
mmAq
(inAq)
8.0 (0.315) 8.0 (0.315)
Pa 78.5 78.5
Water Side Heat
Exchanger
Type - Brazing Plate Brazing Plate
Water Flow (Cooling/Heating)
LPM (GPM)
90.8 (24.0) 127.2 (33.6)
Pressure Drop kPa (psi) 37 (5.37) 70 (10.15)
Max Operationg Pressure Mpa (psi) 1.0 (145) 1.0 (145)
Connection Type - 50A Cut Groove 50A Cut Groove
Quantity EA 2 2
Minimum water quantity
L 272.5 381.6
gal 72.0 100.8
Refrigerant
Type - R410A R410A
Factory Charging lbs 40 40
Sound Sound Pressure dB(A) 60 62
External
Dimension
Net Weight kg (lbs) 435 (959) 435 (959)
Shipping Weight kg (lbs) 457 (1008) 457 (1008)
Net Dimensions (WxHxD) mm (inch)
1,795 x 1,695 x 765
(70.67 x 66.73 x 30.12)
1,795 x 1,695 x 765
(70.67 x 66.73 x 30.12)
Shipping Dimensions (WxHxD) mm (inch)
1,900 x 1,887 x 919
(74.80 x 74.29 x 36.18)
1,900 x 1,887 x 919
(74.80 x 74.29 x 36.18)
Operating Water
Temp. Range
Cooling °C (°F)
5 ~ 25 (41~77)
[Brine, -10~25 (14~77)]
5 ~ 25 (41~77)
[Brine, -10~25 (14~77)]
Heating °C (°F) 25 ~ 55 (77~131) 25 ~ 55 (77~131)
Operating Amb.
Temp. Range
Cooling °C (°F) -15 ~ 48 (5~118) -15 ~ 48 (5~118)
Heating °C (°F) -25 ~ 43 (-13~109) -25 ~ 43 (-13~109)
* Certied efciency data in accordance with AHRI Standard 550/590
* Specication may be changed without further notication
*1) Ambient 95°F, Water Inlet/Water Outlet Temp. 54/44°F
*2) Dry/Wet Bulb 47/43°F, Water Outlet Temp. 120°F
INSTALLATION
9
English
Model Name AG010KSVAJH AG015KSVAJH
Power Supply
Ä­
, #, V, Hz 3, 3, 460, 60 3, 3, 460, 60
Capacity
Ton (Nominal) usRT 10 15
Cooling *1) kBtu/h 120.0 168.0
Heating *2) kBtu/h 120.0 171.0
Power
Power Input
Cooling *1)
kW
10.71 16.63
Heating *2) 11.54 17.45
Current Input
Cooling *1)
A
15.81 25.25
Heating *2) 17.04 25.77
MCA A 24.00 40.00
MOP A 30.00 50.00
COP
Normal Cooling *1) (Btu/h)/W 11.20 10.10
Normal Heating *2) (Btu/h)/W 10.40 9.80
Efciency IPLV (Btu/h)/W 20.5 18.8
Compressor
Type - Scroll Inverter Scroll Inverter
Output kW × n 6.76 x 2 6.76 x 2
Model Name - DS-GB070FAVA DS-GB070FAVA
Oil Type - PVE PVE
Fan
Type - Propeller Propeller
Output x n W 630 x 2 630 x 2
Air Flow Rate
CMM
(CFM)
364 (12,855) 364 (12,855)
External Static
Pressure
MAx.
mmAq
(inAq)
8.0 (0.315) 8.0 (0.315)
Pa 78.5 78.5
Water Side Heat
Exchanger
Type - Brazing Plate Brazing Plate
Water Flow (Cooling/Heating)
LPM (GPM)
90.8 (24.0) 127.2 (33.6)
Pressure Drop kPa (psi) 37 (5.37) 70 (10.15)
Max Operationg Pressure Mpa (psi) 1.0 (145) 1.0 (145)
Connection Type - 50A Cut Groove 50A Cut Groove
Quantity EA 2 2
Minimum water quantity
L 272.5 381.6
gal 72.0 100.8
Refrigerant
Type - R410A R410A
Factory Charging lbs 40 40
Sound Sound Pressure dB(A) 60 62
External
Dimension
Net Weight kg (lbs) 435 (959) 435 (959)
Shipping Weight kg (lbs) 457 (1008) 457 (1008)
Net Dimensions (WxHxD) mm (inch)
1,795 x 1,695 x 765
(70.67 x 66.73 x 30.12)
1,795 x 1,695 x 765
(70.67 x 66.73 x 30.12)
Shipping Dimensions (WxHxD) mm (inch)
1,900 x 1,887 x 919
(74.80 x 74.29 x 36.18)
1,900 x 1,887 x 919
(74.80 x 74.29 x 36.18)
Operating Water
Temp. Range
Cooling °C (°F)
5 ~ 25 (41~77)
[Brine, -10~25 (14~77)]
5 ~ 25 (41~77)
[Brine, -10~25 (14~77)]
Heating °C (°F) 25 ~ 55 (77~131) 25 ~ 55 (77~131)
Operating Amb.
Temp. Range
Cooling °C (°F) -15 ~ 48 (5~118) -15 ~ 48 (5~118)
Heating °C (°F) -25 ~ 43 (-13~109) -25 ~ 43 (-13~109)
* Certied efciency data in accordance with AHRI Standard 550/590
* Specication may be changed without further notication
*1) Ambient 95°F, Water Inlet/Water Outlet Temp. 54/44°F
*2) Dry/Wet Bulb 47/43°F, Water Outlet Temp. 120°F
INSTALLATION
Preparing for installation
10
English
DVM CHILLER Classication
Classication DVM CHILLER
Appearance
Applied model
AG010/015KSV Series
CAUTION
ŷSafely store or dispose the packaging materials.
- Sharp metals such as nails or wooden material
packaging that may break into pieces become a
cause for personal injury.
- Make sure to store or dispose the vinyl type
packaging material to keep it out of reach of
children. Children may put them over their face,
which is very dangerous since it may lead them
to suffocation.
Moving the product
f
Select the moving path in advance.
f
Be sure that moving path can support weight of the
product.
f
Do not slant the product more than 30Ëš when
carrying it.
(Do not lay the product down in sideways.)
f
Surface of the heat exchanger is sharp. Be careful not
to get injured while moving the product.
CAUTION
ŷYou must use square holes in the base of the
product when moving the product.
1 When moving with a crane
f
Fasten the wire rope using square holes of the
product as shown in the gure.
- To protect damage or scratches, insert a piece of
cloth between the product and the wire rope.
- Insert hanging softening material to prevent load
from the rope on top of the product.
INSTALLATION
11
English
CAUTION
ŷDo not hang the rope on side of the water pipe.
The rope may force the water pipe to deformed or
damaged.
2 When moving with a forklift
f
Carefully insert the forklift forks into the forklift
holes at the palette.
f
Be careful with the forklift from damaging the
product.
Center of Gravity Location
A
B
A
C
B
C
Unit: mm (inch)
Model name A B C
AG010/
015KSVA Series
1020
(40 3/16)
380
(14 15/16)
590
(23 1/4)
Accessories (Basic specication)
f
You must keep following accessories not to be lost
during installation.
f
Hand over the installation manual to the customer
after nishing the installation.
Installation manual Installation check card
Field Supply
f
Strainer
Maximum operating
pressure
Water pipe connection
part
1.0 MPa (145 psi) 50A (2")
INSTALLATION
12
English
Selecting installation location
Decide the installation location, with the consideration
of the following conditions, under user's approval.
f
Place where hot discharge air or noise from the DVM
CHILLER may not disturb the neighbor (Especially in
residential areas, keep the operation hours in mind.)
f
Place where structure can bear the weight and
vibration of the DVM CHILLER
f
Place with at surface where rainwater does not
settle or leak
f
Place where it is not exposed to strong wind
f
Well ventilated place with sufcient service place
for repairs and maintenance (Discharge duct can be
purchased separately)
f
Place where it allows easy waterproong and
draining work for the condensation water generated
from the DVM CHILLER during heating operation
f
Place where there is no risk of inammable gas leakage
f
Place where there is no direct inuence of snow or rain
f
Place where a large amount of water generated by
external environment does not directly affect the top
of the outdoor unit.
Installation Guide at the seashore
Make sure to follow below guides when installing at
the seashore.
f
Do not install the product in a place where it is
directly exposed to sea water and sea breeze.
- Make sure to install the product behind a structure
(such as building) that can block see breeze.
- Even when it is inevitable to install the product
in seashore, make sure that product is not
directly exposed to sea breeze by installing a
protection wall.
f
Consider that the salinity particles clinging to the
external panels should be sufciently washed out.
f
Because the residual water at the bottom of the
outdoor unit signicantly promotes corrosion,
make sure that the slope does not disturb drainage.
- Keep the oor level so that rain does not
accumulate.
- Be careful not to block the drain hole due to
foreign substance
f
When product is installed in seashore, periodically
clean it with water to remove attached salinity.
f
Make sure to install the product in a place that
provides smooth water drainage. Especially, ensure
that the base part has good drainage.
f
If the product is damaged during the installation or
maintenance, make sure to repair it.
f
Check the condition of the product periodically.
- Check the installation site every 3 months and
perform anti-corrosion treatment such as R-Pro
supplied by SAMSUNG (Code : MOK-220SA) or
commercial water repellent grease and wax, etc.,
based on the product condition.
- When the product is to be shut down for a long
period of time, such as off-peak hours, take
appropriate measures like covering the product.
f
If the product installed within 500 m (1640.4 ft) of
seashore, special anti-corrosion treatment is required.
࢜ Please contact your local SAMSUNG
representative for further details.
Sea
Sea breeze
DVM
CHILLER
DVM
CHILLER
Sea
Sea breeze
DVM
CHILLER
INSTALLATION
13
English
f
Protection wall should be constructed with a solid
material that can block the sea breeze and the height
and width of the wall should be 1.5times larger
than the size of the DVMCHILLER. (You must secure
more than 700 mm (27.6 inch) of space between
the protection wall and the DVMCHILLER for air
circulation.)
Sea
Sea breeze
DVM
CHILLER
Protection wall
DVM
CHILLER
CAUTION
ŷIn regions with heavy snowfall, make sure to install
the DVM CHILLER where there are no concerns of
direct snowfall on the DVM CHILLER. Also, build
higher base support so that accumulated snow does
not block the air inlet or the heat exchanger.
ŷR-410A refrigerant is a safe, nontoxic and
nonammable refrigerant. However, if the place
holds any concerns for exceeding dangerous level
of refrigerant concentration in case of refrigerant
leakage, extra ventilation system is required.
ŷWhen you install the product on a high location
such as roof, install fence or guardrail around it.
When there is no fence or guardrail, the service
person could fall.
ŷDo not install the product in places where corrosive
gases such as sulfur oxides, ammonia, and sulfurous
gases are produced. (e.g. Toilet outlet, ventilation
opening, sewage works, dyeing complex, cattle
shed, sulfuric hot spring, nuclear power plant, ship
etc.) When installing the product in those places,
contact an installation specialty store as the copper
pipe and brazing part will need additional corrosion
proof or anti-rust additive to prevent corrosion.
ŷMake sure to keep any inammable materials (such
as wooden materials, oil etc.) around the DVM
CHILLER. When there's re, those inammable
material will easily catch the re and may pass it on
to the product.
ŷDepending on the condition of power supply,
unstable power or voltage may cause malfunction
of the parts or control system.
(At the ship or places using power supply from
electric generator, etc.)
INSTALLATION
14
English
Required space for installation
f
Space requirement is based on the following
conditions; Cooling mode, outdoor temperature of
35°C (95°F). Larger space is required if the outdoor
temperature is higher than 35°C (95°F) or if the place
is heated easily by extreme solar radiation.
f
When you secure installation space, consider path for
people and the direction of the wind.
f
Secure installation space as shown in the gure,
considering ventilation and the service space.
f
If the installation space is narrow, installer or other
worker may get injured during work and may also
cause a problem with the product.
f
If you install multiple number of DVM CHILLERs in
one space, make sure to secure enough ventilation
space if there's any walls around the product that
may disturb the air ow. If enough ventilation space
is not secured, the product may malfunction.
f
DVM CHILLERs can be installed with 4 inches
between each unit, but performance may decrease
depending on the installation environment. More
than 4 inches is recommended.
1 Single installation
Unit: mm (inch)
Front side
100 (4) or more
100 (4) or
more
500 (20) or
more (S1)
100 (4) or
more (S2)
<Case 1>
Front side
100 (4) or
more
300 (12) or
more
Height of
the wall is
unlimited
<Case 2>
INSTALLATION
15
English
2 Module installation
Unit: mm (inch)
Front side
100 (4) or
more
200 (8) or more
100 (4) or
more
100 (4) or
more
300 (12) or
more (S2)
500 (20) or
more (S1)
<Case 1>
<Case 2>
400 (16) or
more
400 (16) or
more
200 (8) or
more
Front side
300 (12) or
more
Height of the wall is unlimited
Front side
Front side
100 (4) or
more
100 (4) or
more
100 (4) or
more
100 (4) or
more
100 (4) or
more
100 (4) or
more
100 (4) or
more
100 (4) or
more
500 (20)
or more
500 (20)
or more
600 (24)
or more
<Case 3>
f
Installing by <Case 1> or <Case 3>
- Height of the wall on the front side should not
be higher than 1500mm (59 inch).
- Height of the wall on the air inlet side should not
be higher than 500mm (20 inch).
- Height of the wall on the side is not limited.
- If the height of the wall exceeds by certain value
(h1, h2), additional clearance [(h1)/2, (h2)/2 : Half
of the exceeded distance] should be added to the
service space (S1, S2).
Unit: mm (inch)
1500 (59) h1
500 (20) h2
Front side
Air inlet side
S1+h1/2 S2+h2/2
INSTALLATION
16
English
WARNING
ŷMake sure to remove the wooden pallet before
installing the DVM CHILLER. If you do not remove
the wooden pallet, there is risk of re during
welding the pipes. If the DVMCHILLER is installed
with wooden pallet on, and it was used for long
period time, wooden palette may break and cause
electrical hazard or high pressure may damage the
pipes.
ŷFix DVMCHILLER rmly on the base ground with
anchor bolts.
CAUTION
ŷManufacturer is not responsible for the damage
occurred by not following the installation standards.
1 Make sure that the height of the base ground is 20
mm (8 inch) or higher to protect the product from
rain water or other external conditions. Also, install
a drainage hole around the supporting base and
connect the drain pipe to the drainage pit.
2 Considering the vibration and weight of the product,
strength of the base ground must be strong to
prevent noise and the top surface of it should be at.
3 Area of the base ground should be 1.5 times larger
than the bottom of the product.
4 Product must be xed rmly so that it can withstand
the wind speed of 30 m/s (100 ft/s). If you cannot x
the DVMCHILLER on the supporting base, x it by
side or use extra structure.
5 In heating operation, defrost water may form so
you must pay close attention to the drainage and
waterproong of the oor. To prevent defrost water
from stagnating or freezing, construct a drainage pit
with over 1/50 slant to prevent ice formation on the
oor in the winter time.
6 It is necessary to add wire mesh or steel bar during
concrete construction for the base ground to prevent
damage or cracks.
7 When installing multiple DVM CHILLERs at the same
place, construct an H beam or a vibration-isolation
frame on the base ground to install the product.
8 After installing an H beam or a vibration-isolation
frame, apply corrosion protection and other
necessary coating.
9 When concrete construction for product installation
is complete, install an isolation pad (t = 20 mm (0.78
inch) or more) or a vibration-isolation frame to
prevent vibration of the product from transferring to
the supporting base.
10 Place the product on an H beam or a vibration
isolation frame and x it with the anchor bolt, nut
and washer. (The bearing capacity of the anchor bolt
has to be over 3.5 kN (787 lbf))
Supporting base construction
Unit: mm (inch)
When installing on the ground
Draining pit
200 (8) or more
When installing on the roof
Bottom surface of
the supporting base
must be horizontally
leveled
200 (8) or more
200 (8) or more
Base construction and installation
INSTALLATION
17
English
Product installation
Unit: mm (inch)
200 (8) or
more
200 (8) or
more
50 (2) or
more
H beam or vibration-isolation frame
Supporting base
Base mount and anchor bolt
position
Unit: mm (inch)
A
B
54 (2 1/8)
761 (29 15/16)
803 (31 5/8)
54 (2 1/8)
Product - vibration-isolation
frame (4 - Ø12 (Ø1/2))
Supporting base (H beam or vibration-isolation frame)
Unit: mm (inch)
Applied model
Net dimension
AB
AG010/015
✴✴✴
1795
(70 11/16)
1655
(65 3/16)
ŷWhen applying vibration-isolation frame additionally
on supporting base, specication of xed holes with
the base should be referred to specication of the
frame.
Examples of draining work
f
Use concrete or steel bar for draining work to
prevent any damage or cracks.
f
For smooth draining of defrost water, make sure to
apply 1/50 slant.
f
Construct a drainage ditch/channel around the
product to prevent the defrost water (from the
product) from stagnating, overowing or freezing
near the installation space.
f
When the product is installed on the roof, check the
strength and waterproof status of the roof.
Unit: mm (inch)
960 (37 13/16)
760 (29 15/16)
100
(4)
80 (3 1/8)
80
(3 1/8)
80
(3 1/8)
60°
100
(4)
X
X’
Direction of the
drainage
(1/50 slant)
B
A
50 (2)
100 (4)
150
(6)
100
(4)
X-X’ SECTION
60°
60°
200
(8)
BB
2
00
(8)
Direction of
the drainage
(1/50 slant)
80 (3 1/8)
80 (3 1/8)
80 (3 1/8)
80
(3 1/8)
80
(3 1/8)
80
(3 1/8)
80
(3 1/8)
80
(3 1/8)
Unit: mm (inch)
Applied model
Net dimension
AB
AG010/015
✴✴✴
1855
(73 1/16)
1655
(65 3/16)
INSTALLATION
Base construction and installation
18
English
Installation precautions
Connecting the anchor bolt
CAUTION
Plastic (rubber)
washer
ŷTighten the rubber washer to
prevent the bolt connection
part of the DVM CHILLER from
corroding.
Anchor specication
a
b
c
m
ŷUse the anchor bolts and nuts
that is zinc plated or made
of STS material. Regular
anchor bolts or nuts may get
damaged by corrosion.
Unit: mm (inch)
Size
Diameter of
drill bit (a)
Anchor
length (b)
Sleeve
length (c)
Insertion
depth
Fastening
torque
ø10
(ø3/8)
14 (1/2) 75 (3) 40 (1 1/2) 50 (2)
30 N·m
(22.1 lbf·ft)
Connecting the pipe
Water inlet pipe
Water outlet pipe
f
If you install the DVMCHILLER on the rooftop,
check the strength and make sure to waterproof the
rooftop.
f
Construct draining pit around the supporting base
and pay attention to the drainage around the
product. (Condensation or defrost water may form
during product operation.)
f
If there's any possibility of small animals entering
into the product through pipe outlet, block the outlet.
INSTALLATION
19
English
Installing vibration-isolation frame
f
During installation, make sure there is no gap
between the supporting base and the extra structures
such as vibration-isolation frame or H beam.
f
Supporting base must be constructed strongly to
support the bottom part of the vibration-isolation
mount.
f
After installing the vibration-isolation frame, unscrew
the xing part on the top and bottom part of the
frame.
Installing discharge duct
f
Static pressure of the discharge duct should be within
the standard specication 78.5 Pa (0.315 W.G) when
installing the duct.
f
If you remove the fan guard to install the discharge
duct, make sure to install a fan guard on the duct
outlet.
Foreign substance may enter into the product and
there could be a risk of personal injury.
f
Wear protection equipment at all times when making
galvanized sheet metal duct, since the worker may
get injured by the sharp parts.
f
When installing the product under the tree or near
forest, leaves and other debris may get into the
product and cause problems. Therefore, install
a discharge duct to prevent foreign substance
inltration.
INSTALLATION
20
English
Installing the wind/snow prevention duct
Installing the discharge duct
around obstacles
Ex.) Balcony
Upper oor
Discharged air
Ex.) Mechanical room
Discharged
air
Grille/
louver
Suction air
f
It is necessary to install a wind/snow prevention
duct (eld supply) to direct exhaust from the fan
horizontally, when it is difcult to provide a minimum
space of 2 m (6.56 ft) between the air outlet and a
nearby obstacle above.
Installing the discharge duct in
cold regions
h
f
In cold regions with lots of snowfall, install a snow
prevention duct, as a sufcient countermeasure, to
prevent snow from accumulating on the product.
When the snow prevention duct is not installed
properly, frost may accumulate on the heat exchanger
and heating operation may not work normally.
f
Air outlet of the duct should not be directed to the
enclosed space.
CAUTION
Cautions regarding on installing the frame and selecting
the base ground
ŷHeight (h) of the frame and the base ground should
be higher than the "heaviest expected snowfall".
ŷArea of the frame and the supporting base should
not be larger than the area of the product. Snow
may accumulate if the area of the frame or the base
ground is larger.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86

Samsung AG015KSVAFH/AA Installation guide

Category
Split-system air conditioners
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI