Samsung AC018MXQFEC/ID Installation guide

Type
Installation guide
Air conditioner
Installation manual
A०००đǹůkAࢥA०००đǹůA
Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this manual carefully and retain it for future reference.
DB68-07310A-01
2
English
Contents
PREPARATION
Safety precautions ..........................................................................................................3
Preparation for outdoor unit installation.....................................................................................5
Deciding on where to install the outdoor unit ...............................................................................7
Outdoor unit installation ..................................................................................................11
INSTALLATION
Connecting the cable .....................................................................................................13
Wiring Work...............................................................................................................19
Connecting the refrigerant pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Adding refrigerant (R-410A)...............................................................................................22
Connecting up and removing air in the circuit .............................................................................23
Cutting/Flaring the pipes..................................................................................................25
Performing leak tests......................................................................................................26
Connecting the drain hose to the outdoor unit ............................................................................26
Refrigerant pipe work .....................................................................................................27
Using service valve ........................................................................................................28
Pump down Procedure....................................................................................................29
OTHERS
Checking correct grounding...............................................................................................30
Testing operations ........................................................................................................31
Troubleshooting ..........................................................................................................33
Packing and unpacking guide .............................................................................................35
Product specication......................................................................................................36
01 PREPARATION
3
English
Safety precautions
Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.
WARNING
Always disconnect the air conditioner from the power supply before servicing it or
accessing its internal components.
Verify that installation and testing operations are performed by qualied personnel.
Verify that the air conditioner is not installed in an easily accessible area.
General information
f Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order
to be able to use it as reference after installation.
f For maximum safety, installers should always carefully read the following warnings.
f Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air
conditioner is sold or transferred.
f This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types
of units with dierent control systems may damage the units and invalidate the warranty. The manufacturer shall not be
responsible for damages arising from the use of non compliant units.
f The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper
connection of electric and requirements set forth in the “Operating limits” table, included in the manual, shall
immediately invalidate the warranty.
f The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable
to be installed in areas used for laundry.
f Do not use the units if damaged. If problems occur, switch the unit o and disconnect it from the power supply.
f In order to prevent electric shocks, res or injuries, always stop the unit, disable the protection switch and contact
SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
f Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations
should be performed by qualied personnel only.
f The unit contains moving parts, which should always be kept out of the reach of children.
f Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may
cause electric shocks or res.
f Do not place containers with liquids or other objects on the unit.
f All the materials used for the manufacture and packaging of the air conditioner are recyclable.
f The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with
current laws.
f The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air
conditioner must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly
and safely.
f This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use
of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play
with the appliance.
4
English
Safety precautions
Installing the unit
IMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the electrical lines.
Always disassemble the electric lines before the refrigerant tubes.
f Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears
damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the
authorized technician has collected the material from the retailer.)
f After completing the installation, always carry out a functional test and provide the instructions on how to operate the air
conditioner to the user.
f Do not use the air conditioner in environments with hazardous substances or close to equipment that release free ames
to avoid the occurrence of res, explosions or injuries.
f Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from
both sides and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible
and easy to disassemble without endangering people and objects.
f For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair
the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaolding or any other
elevation system will NOT be considered part of the warranty and will be charged to the end customer.
Power supply line, fuse or circuit breaker
f Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in
compliance with current local safety standards.
f Always verify that a suitable grounding connection is available.
f Verify that the voltage and frequency of the power supply comply with the specications and that the installed power is
sucient to ensure the operation of any other domestic appliance connected to the same electric lines.
f Always verify that the cut-o and protection switches are suitably dimensioned.
f Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the
wiring diagram included in the manual.
f Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric
specications and with the instructions provided in the wiring scheme. Always verify that all connections comply with
the standards applicable to the installation of air conditioners.
f Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
f Be sure not to perform power cable modication, extension wiring, and multiple wire connection.
- It may cause electric shock or re due to poor connection, poor insulation, or current limit override.
- When extension wiring is required due to power line damage, refer to "How to connect your extended power cables" in
the installation manual.
01 PREPARATION
5
English
Preparation for outdoor unit installation
The air conditioner uses R-410A refrigerant.
A Type:
AC048MXQFGC/AC060MXQFGC
620
330
360
384
940
1395
1420
567
1095
558
(Unit : mm)
B Type:
AC036MXQFEC/AC042MXQFEC
C Type:
AC030MXQFEC
620
940
977
998
528
537
675
330
360
384
6
English
Preparation for outdoor unit installation
D Type:
AC018MXQFEC
364
310
638
880
54
660
12
23
E Type:
AC024MXQFEC
310
793
364
660
12
18
880
53
F Type:
AC012MXQFEC
543
319
343
131
285
548
790
50
54
29
01 PREPARATION
7
English
Moving the Outdoor Unit by Wire Rope
Fasten the outdoor unit by two 8m or longer wire ropes as shown at the gure.
To prevent from damage or scratches, insert a piece of cloth between the
outdoor unit and rope, then move the unit.
The appearance of the unit may be dierent from the picture depending on the
model.
Plate protection
cloth
Wire rope
Outdoor Unit
f The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling
circuit and seriously damage the unit.
f Choose a location that is dry and sunny, but not exposed to direct sunlight or strong winds.
f Do not block any passageways or thoroughfares.
f Choose a location where the noise of the air conditioner when running and the discharged air do not disturb any
neighbours.
f Choose a position that enables the pipes and cables to be easily connected to the indoor unit.
f Install the outdoor unit on a at, stable surface that can support its weight and does not generate any unnecessary noise
and vibration.
f Position the outdoor unit so that the air ow is directed towards the open area.
f Maintain sucient clearance around the outdoor unit, especially from a radio, computer, stereo system, etc.
Fuse
Outdoor
Unit
Stereo
1.5m or more
Indoor Unit
Control
Air Guide Duct
(This product is not
provided by Samsung)
1m or more
1m or more
1.5m or more
1.5m or more
1.5m or more
Fuse
200mm
300mm
f If the outdoor unit is installed at a height, ensure that its base is rmly xed in position.
f Make sure that the water dripping from the drain hose runs away correctly and safely.
f When you install the outdoor unit at wayside, you should install it above 2m height or make sure that the heat from the
outdoor unit shouldn't be in direct contact with passersby. (The ground for application :The revision of regulation for
facility in building by the law of the Ministry of Construction and Transportation.
Deciding on where to install the outdoor unit
8
English
Deciding on where to install the outdoor unit
You have just purchased a system air conditioner and it has been installed by your installation specialist.
This device must be installed according to the national electrical rules.
With an outdoor unit having net weight upper than 60kg, we suggest do not install it suspended on wall,
but considering oor standing one.
CAUTION
When installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze. If you can not nd a
adequate place without direct see breeze, protection wall should be constructed.
- Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which
can damage the outdoor unit.
Outdoor unit
Outdoor unit
Sea breeze Sea breeze
Sea
Sea
- If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the
sea breeze.
Protection wall
Outdoor unit
Sea breeze
Sea
Protection wall should be constructed with a solid material
such as concrete to block the sea breeze and the height
and the width of the wall should be 1.5 times larger than
the size of the outdoor unit. Also, secure over 700mm
between the protection wall and the outdoor unit for
exhausted air to ventilate.
- Install the outdoor unit in a place where water can drain smoothly.
If you cannot nd a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea
water and the dust on the outdoor unit heat exchanger and spread corrosion inhibitor on heat exchanger. (At
least one time per one year.)
Depending on the condition of power supply, unstable power or voltage may cause malfunction of the parts or
control system. (At the ship or places using power supply from electric generator, etc).
CAUTION
01 PREPARATION
9
English
Space Requirements for Outdoor Unit
When installing 1 outdoor unit
300 or more
1500 or more
When the air outlet is opposite the wall When the air outlet is towards the wall
300 or more
300 or more
600 or more
1500 or more
2000 or more
When 3 sides of the outdoor unit are blocked by the wall The upper part of the outdoor unit and the air outlet is
towards the wall
600 or more
300 or more
1500 or more 300 or more
The upper part of the outdoor unit and the air outlet is
opposite the wall
When front and rear side of the outdoor unit is towards
the wall
When installing more than 1 outdoor unit
1500 or more
600 or more
600 or more
(Unit : mm)
When the air outlet is towards the wall
10
English
Deciding on where to install the outdoor unit
600 or more 600 or more 600 or more
300 or more
300 or more
When 3 sides of the outdoor unit are blocked by the wall
300 or more
1500 or more
600 or more 600 or more
500 or more500 or more
300 or more
300 or more
When front and rear side of the outdoor unit is towards the wall The upper part of the outdoor unit and
the air outlet is towards the wall
1500 or more 600 or more 3000 or more 3000 or more 300 or more
When front and rear side of the outdoor unit is towards the wall
The units must be installed according to distances declared, in order to permit accessibility from each side, either to
guarantee correct operation of maintenance or repairing products.
The unit’s parts must be reachable and removable completely under safety condition (for people or things).
CAUTION
Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver]
[Rain resistance louver]
• Louver specications.
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%
WARNING
01 PREPARATION
11
English
Outdoor unit installation
The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration,
particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be xed to
an appropriate support(wall or ground).
Fix the outdoor unit with anchor bolts.
NOTE
The anchor bolt must be 20mm or higher from the base surface.
(Unit : mm)
620
940
330
360
384
Anchor bolt hole
660
880
310
340
364
Anchor bolt hole
Type A,B,C: AC030MXQFEC / AC036MXQFEC
AC042MXQFEC / AC048MXQFGC
AC060MXQFGC
Type D,E : AC018MXQFEC / AC024MXQFEC
543
790
285
319
343
Anchor bolt hole
Type F : AC012MXQFEC
CAUTION
Make a drain outlet around the base for outdoor unit drainage.
If the outdoor unit is installed on the roof, you have to check the ceiling strength and waterproof the unit.
Location of the compressor
Make sure that product is level during installation. Especially, product shouldn’t be tilted towards the
compressor.
CAUTION
12
English
Outdoor unit installation
Outdoor Unit Support
NN
Anchor bolt
Outdoor
Unit
Base Surface
Outdoor Unit
Support
Soft rubber designed to cut o
vibration from rack to wall.
(not supplied with product)
Designed to
cut o residual
vibration from
outdoor unit to
rack.
(not supplied with
product)
OUTDOOR UNIT INSTALLED ON THE WALL BY RACK
f Ensure the wall will be able to suspend the weight of rack and outdoor unit ;
f Install the rack close to the column as much as possible ;
f Install proper grommet in order to reduce noise and residual vibration
transferred by outdoor unit towards wall.
When installing air guide duct
Check and make sure that screws do not damage the copper pipe.
Secure air guide duct on guard fan.
CAUTION
02 INSTALLATION
13
English
Connecting the cable
Two electronic cables must be connected to the outdoor unit.
f The connection cord between indoor unit and outdoor unit.
f The power cable between outdoor unit and auxiliary circuit breaker.
f Specially for Russian and European market, before installation, the supply authority should be consulted to determine the
supply system impendance to ensure compliance.
During the unit installation make rst refrigerant connections and then electrical connections. If unit is
uninstalled rst disconnect electrical cables, then refrigerant connections.
Connect the air conditioner to grounding system before performing the electrical connection.
When installing the unit, you shouldn't use inter connection wire.
CAUTION
Example of Air Conditioner System
When using ELCB for 1 phase
Indoor Unit
Power cable
Outdoor Unit
Communication cable
Grounding
OR
Power cable
Communication cable
When using ELCB for 3 phase 4 wires
Indoor Unit
Power cable
OR
Outdoor Unit
Communication cable
Grounding
Power cable
Communication cable
If an outdoor unit is installed in a place in danger of an electric leak or submergence, you must install the ELCB.
14
English
Connecting the cable
Power Cable Specications
f The power cable is not supplied with air conditioner.
- Select the power supply cable in accordance with relevant local and national regulations.
- Wire size must comply with the applicable local and national code.
- Specications for local wiring power cord and branch wiring are in compliance with local cord.
Single Phase
Model Outdoor Units Input Current (Amperes) Power Supply
Outdoor Unit
Indoor Unit
Rated Voltage Range Outdoor Unit
Indoor
Unit
Total MCA (A) MFA (A)
Hz Volts Min. Max. Cooling Heating
AC012MXQFEC
AC012MNMFEC
50 220-240 198 264 9.0 - 2.5 11.5 11.5 12.7
AC018MXQFEC
AC018MNMFEC
50 220-240 198 264 18.0 - 2.5 20.5 20.5 22.6
AC024MXQFEC
AC024MNMFEC
50 220-240 198 264 18.0 - 2.5 20.5 20.5 22.6
AC030MXQFEC
AC030MNMFEC
50 220-240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC036MXQFEC
AC036MNMFEC
50 220-240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC042MXQFEC
AC042MNMFEC
50 220-240 198 264 32.0 - 2.5 34.5 34.5 40.0
3 Phase
Model Outdoor Units Input Current (Amperes) Power Supply
Outdoor Unit
Indoor Unit
Rated Voltage Range Outdoor Unit
Indoor
Unit
Total MCA (A) MFA (A)
Hz Volts Min. Max. Cooling Heating
AC048MXQFGC AC048MNMFEC
50 380-415 342 457 16.1 - 2.5 18.6 18.6 18.6
AC060MXQFGC AC060MNMFEC
50 380-415 342 457 16.1 - 2.5 18.6 18.6 18.6
NOTE
1. Voltage range
- Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits
2. Maximum allowable voltage variation between phases is 2%.
3. Wire size & type must comply with the applicable local and national code.
- Wire size : Based on the value of MCA.
- Wire type : Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene
sheathed exible cord (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66
/ CENELEC H07RN-F)
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5. MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)
02 INSTALLATION
15
English
Between Indoor unit and Outdoor unit Connection Cable Specications(Common in use)
Power supply
Communation Cable
Power supply Max/Min(V) Indoor Power Cable
, 220 - 240V, 50Hz ±10%
2.5mm² , 3wires 0.75mm² , 2wires
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord (Code
designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66 / CENELEC H07RN-F)
When installing the indoor unit in a computer room or net work room, use the double
shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type.
1-phase terminal block specications
AC power : M5 screw AC power : M4 screw Communication : M4 screw
1(L) 2(N)
N
L
15 12
1(L) 2(N)
N
L
9.95 11.55
10.1
11.4
Communication : M3 screw
6.7
9.7
3-phase terminal block specications
AC power : M4 screw Communication : M4 screw
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
9.95 11.55
10.1
11.4
16
English
Connecting the cable
Wiring Diagram of Power Cable
When using ELB for 1 phase and 3 phase
ELB
MCCB
MCCB
1(L) 2(N)
N
L
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
Power Supply
Electrical
component box
Indoor Unit
f 3 phase
Indoor Power
Communication cable
Main power cable
The appearance of the unit may be
dierent from the picture depending on
the model.
Cable tie
Cable tie
Communication
cable
3 Phase 4 Wires power
cable (AC 380V)
Indoor Power
f 1 phase
You should connect the power cable into the power cable terminal and fasten it with a clamp.
The unbalanced power must be maintained within 2% of supply rating.
- If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over 4% of supply rating,
the indoor unit is protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the power cable and the connection cord of the indoor and
outdoor units within ducts. (with appropriate IP rating and material selection for your application)
Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least 3 mm.
Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.
Keep distances of 50mm or more between power cable and communication cable.
CAUTION
02 INSTALLATION
17
English
Silence mode controller wiring diagram
ASSY Control out
Silence Mode Controller
Outdoor unit
Silence Mode is a function that reduces noise at night. For more information how to set mode, refer to page 32.
1 phase (Duct Type)
1(L) 2(N)
2
1
1(L) 2(N)
N
L
F4
F3
F1 F2
V2
V1
Indoor Unit Outdoor Unit
Main power cable
Indoor Power
Communication cable
Cable tie
3 phase (Duct Type)
1(L) 2(N)
2
1
F4
F3
F1 F2
V2
V1
N
L3(T)
L2(S)
L1(R)
1(L) 2(N)
Indoor Unit Outdoor Unit
3 Phase 4 Wires power cable (AC 380V)
Indoor Power
Communication cable
Cable
tie
The appearance of the unit may be dierent from the picture depending on the model.
Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely.
Ground wire for the indoor unit and outdoor unit connection cable must be clamped to a soft copper tin-plated eyelet terminal with M4
screw hole(NOT SUPPLIED WITH UNIT ACCESSORIES).
NOTE
18
English
Connecting the cable
Connecting the Power Terminal
f Connect the cables to the terminal board using the compressed ring terminal.
f Cover a solderless ring terminal and a connector part of the power cable and then connect it.
Silver solder
Nominal
dimensions
for cable
[mm
2
(inch
2
)]
Nominal
dimensions
for screw
[mm(inch)]
BDd1EFLd2t
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Min.
[mm
(inch)]
Min.
[mm
(inch)]
Max.
[mm
(inch)]
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Min.
[mm
(inch)]
4/6
(0.006/
0.009)
4(3/8) 9.5(3/8)
±0.2
(±0.007)
5.6(1/4)
+0.3(+0.011)
-0.2(-0.007)
3.4(1/8)
±0.2
(±0.007)
6
(1/4)
5
(3/16)
20
(3/4)
4.3
(3/16)
+ 0.2(+0.007)
0(0)
0.9
(0.03)
8(3/16) 15(9/16)
9
(3/8)
28.5
(1-1/8)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
10(0.01) 8(3/16) 15(9/16)
±0.2
(±0.007)
7.1(1/4)
+0.3(+0.011)
-0.2(-0.007)
4.5(3/16)
±0.2
(±0.007)
7.9
(5/16)
9
(3/8)
30
(1-3/16)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.15
(0.04)
16(0.02) 8(3/16) 16(10/16)
±0.2
(±0.007)
9(3/8)
+0.3(+0.011)
-0.2(-0.007)
5.8(1/4)
±0.2
(±0.007)
9.5
(5/16)
13
(1/2)
33
(1-5/16)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.45
(0.05)
25(0.03)
8(3/16) 12(1/2)
±0.3
(±0.011)
11.5(7/16)
+0.5(+0.019)
-0.2(-0.007)
7.7(5/16)
±0.2
(±0.007)
11
(3/8)
15
(5/8)
34
(1-3/8)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.7
(0.06)
8(3/16) 16.5(10/16)
13
(1/2)
8.4
(1-3/16)
35(0.05)
8(3/16) 16(10/16)
±0.3
(±0.011)
13.3(1/2)
+0.5(+0.019)
-0.2(-0.007)
9.4(3/8)
±0.2
(±0.007)
12.5
(1/2)
13
(1/2)
38
(1-1/2)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.8
(0.07)
8(3/16) 22(7/8)
13
(1/2)
43
(1-
11/16)
8.4
(1-3/16)
50(0.07) 8(3/16) 22(7/8)
±0.3
(±0.011)
13.5(1/2)
+0.5(+0.019)
-0.2(-0.007)
11.4(7/16)
±0.3
(±0.011)
17.5
(11/16)
14
(9/16)
50
(2)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.8
(0.07)
70(0.10) 8(3/16) 24(1)
±0.4
(±0.015)
17.5(11/16)
+0.5(+0.019)
-0.4(-0.015)
13.3(1/2)
±0.4
(±0.015)
18.5
(3/4)
20
(3/4)
51
(2)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
2.0
(0.078)
f Connect the rated cables only.
f Connect using a driver which is able to apply the rated torque to the screws.
f If the terminal is loose, re may occur caused by arc. If the terminal is connected too rmly, the terminal may be damaged.
Tightening Torque (kgf • cm) Model
M4 12.0~18.0
Communication : F1, F2 All model
1 phase AC power : 1(L), 2(N), L, N
AC018MXQFEC
AC024MXQFEC
3phase AC power : 1(L), 2(N), L1R, L2(S), L3(T), N AC048MXQFGC
M5 20.0~30.0 1 phase AC power : 1(L), 2(N), L, N
AC030MXQFEC
AC036MXQFEC
When connecting cables, you can connect the cables to the electrical part or connect them through the holes
below depending on the spot.
Run transmission wiring between the indoor and outdoor units through a conduit to protect against
external forces, and feed the conduit through the wall together with rergerant piping.
Remove all burrs at the edge of the knock-out hole and secure the cable to the outdoor knock-out using lining
and bushing with an electrical insulation such as rubber and so on.
Must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and communication cable.
When the cables are connected through the hole, remove the Plate bottom.
CAUTION
02 INSTALLATION
19
English
Wiring Work
How to connect your extended power cables
1. Prepare the following tools.
Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm)
Spec MH-14 20xØ6.5(HxOD) Width 19mm 70xØ8.0(LxOD)
Shape
2. As shown in the gure, peel o the shields from the rubber and wire of the
power cable.
- Peel o 20 mm of cable shields from the pre-installed tube.
For information about the power cable specications for indoor and
outdoor units, refer to the installation manual.
After peeling o cable wires from the pre-installed tube, insert a
contraction tube.
CAUTION
(Unit: mm)
Power cable
Pre-installed tube for the power cable
3. Insert both sides of core wire of the power cable into the connection sleeve.
f Method 1
Push the core wire into the sleeve from both sides.
Connection sleeve
f Method 2
Twist the wire cores together and push it into the sleeve.
Connection sleeve
4. Using a crimping tool, compress the two points and ip it over and compress another two points in the same location.
- The compression dimension should be 8.0.
- After compressing it, pull both sides of the wire to make sure it is rmly pressed.
Compression
dimension
f Method 1
Compress it 4 times.
5 mm
f Method 2
Compress it 4 times.
5 mm
20
English
Wiring Work
5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.
Three or more layers of insulation are required.
f Method 1
40 mm
Insulation tape
f Method 2
Insulation tape
35 mm
6. Apply heat to the contraction tube to contract it.
Contraction tube
7. After tube contraction work is completed, wrap it with the insulation tape to nish.
Insulation tape
Make sure that the connection parts are not exposed to outside.
Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have
the same level of withstand voltage with the power cable. (Comply with the local regulations on extensions.)
CAUTION
In case of extending the electric wire, please DO NOT use a round-shaped Pressing socket.
- Incomplete wire connections can cause electric shock or a re.
WARNING
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38