AIRTAC DPS Series Quick start guide

Category
Measuring, testing & control
Type
Quick start guide

AIRTAC DPS Series is a digital display pressure switch with a wide range of capabilities for precise pressure monitoring and control in various applications. Here are some key features and possible use cases:

  • Accurate Pressure Measurement: With a measurement error of ±2% F.S. ±1 digit, the device provides reliable and accurate pressure readings.

  • Multi-Unit Pressure Range: The DPS Series offers multiple pressure range options, including -100kPa to 100kPa and -100kPa to 1000kPa, catering to diverse pressure monitoring needs.

  • Switchable Pressure Units: The device allows you to select from various pressure units such as kPa, MPa, kgf/cm2, bar, psi, mmHg, and cmHg, ensuring compatibility with different industry standards.

AIRTAC DPS Series is a digital display pressure switch with a wide range of capabilities for precise pressure monitoring and control in various applications. Here are some key features and possible use cases:

  • Accurate Pressure Measurement: With a measurement error of ±2% F.S. ±1 digit, the device provides reliable and accurate pressure readings.

  • Multi-Unit Pressure Range: The DPS Series offers multiple pressure range options, including -100kPa to 100kPa and -100kPa to 1000kPa, catering to diverse pressure monitoring needs.

  • Switchable Pressure Units: The device allows you to select from various pressure units such as kPa, MPa, kgf/cm2, bar, psi, mmHg, and cmHg, ensuring compatibility with different industry standards.

28.6
20
16
N
Made in Taiwan
12
A
B C
D
E
F
G
30
30
20
7
345 12
12 24V
~
12 24V
~
2-M3
MPa kPa kgf/cm bar
psi cmHgmmHg
IP64
2ms、20ms、50ms、100ms、250ms、500ms、1000ms、2500ms、5000ms
DPS Series
Precautions
Digital Display Pressure Switch
A.Value up button
B.Setting button
C.Value Down button
D.Pressure display area
E.Set pressure display area
F.Output 1 indicator light
G.Output 2 indicator light
Specifications Model Description
User Interface Instructions
Connection Example
2.Turn on the power
1.Install the connector
(Measurement mode)
(Basic mode)
(Measurement mode)(Basic mode) (Advanced mode)
Interface switch
Press the SET button
for two seconds
Press the SET button
for two seconds
Interface switch
Press the SET button
for four seconds
Press the SET button
for two seconds
Press the SET button to change menu
Press the value up and
down button to set the
pressure value
Press the value up and
down button to set the
pressure value
Press the value up and
down button to set the
pressure value
Rolling
display
Rolling
display
Rolling
display
Basic mode
Hysteresis /window comparator mode
Basic mode Hysteresis mode
Basic mode Hysteresis mode
Output1-N.O.
Output2-N.O.
Output1-N.C.
Output2-N.O.
Output1-N.O.
Output2-N.C.
Output1-N.C.
Output2-N.C.
Output:Red
No output:Red
Press the SET
button to change
menu
No output:Green
Output:Green
All-time
display red
All-time
display green
Press the value up and down
button setting the value
Load
Do not use it with corrosive and/or flammable gases or liquids.
Don't use in an environment with spattering liquid of oil or solvent.
Do not dropknock or apply excessive impact while handling.Otherwise
could cause damage and a malfunction.
The tensile strength of the cord is 60N.Applying a greater pulling
force on it can cause a malfunction.
Do not exceed the screw-in torque of 7N
m when installing piping.
Exceeding this value may cause malfunctioning of the sensor.
Please use it within rated pressure range.
Turn off the power before connecting the wires.
Separate power lines from high voltage lines,avoiding wiring in the
same conduit with these lines.
M5 with female
thread
Piping specifications:
PT 1/8 with M5 female thread
NPT 1/8 with 10-32UNF female thread
G 1/8 with M5 female thread
1.DC(+) input (Brown)
2.OUT1 (Black)
3.OUT2 (White)
4.Retention(Orange)
5.DC(-) input (Blue)
Maximum 100m/s , X, Y, Z directions 3 times each
0℃ to +50℃
-20℃ to +65℃
35% to 80% RH(No condensation)
Input power
Display
Switch output
Voltage
fluid type
Output
Color
Output group
Response time
12 to 24VDC ±10%,Ripple(p-p)≤10%
45 mA or less
Non-corrosive gas
DPSN1(P1)-01:-100kPa to 100kPa
DPSN1(P1)-10:-100kPa to 1000kPa
DPSN1(P1)-01:200kPa
DPSN1(P1)-10:1500kPa
±2% F.S. ±1 digit
±0.2% F.S.
100ms、250ms、500ms、1000ms
2-color LCD (Red/Green)
DPSN1:Built-in two sets of NPN output
DPSP1:Built-in two sets of PNP output
2ms、20ms、50ms、100ms、250ms、500ms、
1000ms、2500ms、5000ms
±3% F.S.(Base 25℃,Range 0 to 50℃ )
Model
DPSN1-01、DPSN1-10、DPSP1-01、DPSP1-10
Hysteresis
Output mode
Pressure Unit
Impact
resistance
NPN:Maximum applied voltage 30V/100mA,
Retained voltage <1.5V
Operating
Temp. range
Current
consumption
Measurement
range
Pressure
range
Withstand
pressure
Measurement
error
Repeative
accuracy
Temperature
error
Display
Type
Display
period
Transistor
output
Double row LCD display
PNP:Maximum applied voltage 30V/100mA,
Retained voltage <1.5V
Vibration
resistance
Stored
Temp. range
Humidity
range
Basic mode, Hysteresis mode, Window
comparator mode
10 to 500Hz with 10mm Amplitude in X, Y, Z directions
for 2hrs
2
4-digit measurement, 3.5-digit setting
DPSP1:PNP Output
DPSN1:NPN Output
Pressure Switch
Pressure Switch
DC(+)-Brown
Out1-Black
Out2-White
DC(-)-Blue
Load
DC(+)-Brown
Out1-Black
Out2-White
DC(-)-Blue
Load
Load
Interface of basic mode
Pressure unit
Output1
Output-
Output-
Response time
Output2
Normally open
or close
Output-
Color
selection
Output type
N1:NPN
P1:PNP
Piping specifications
NULL - PT 1/8 with M5 female thread
T - NPT 1/8 with 10-32UNF female thread
G - G 1/8 with M5 female thread
DPS -
020:Length 2m
030:Length 3m
Lead wire
length
Measurement range
01:-100 to 100kPa
10:-100 to 1000kPa
B:Rear End Cable
Connected mode
NULL:Plug-in
connector.
Press the SET button to change menu
Window comparator
mode
Window comparator
mode
050:Length 5m
DPSN1(P1)-01:kPa、kgf/cm 、bar、psi、mmHg、inHg
DPSN1(P1)-10:MPa、kPa、kgf/cm 、bar、psi、cmHg、inHg
DPSN1(P1)-01:0.1、0.2、0.30.8(kPa)
DPSN1(P1)-10:1、2、3
8(kPa)
2
2
2
0
0
0
(Advanced mode)
Dimensions/Assembly Instructions
Press the SET button to change menu
Advanced mode
Neither
100ms 250ms 500ms 1000ms
Backlight off Backlight on
Change backlight
Copy function:OFF
Change backlight Change backlight
Change backlight
Copy function:ON Copy function:ON
Slave device Master device
Display
pressure unit
Display
setting value
Display
pressure unit
Press the value up and down
button setting the value
Factory-fresh
state:OFF
Factory-fresh
state:ON
color when
output1 works
color when
output2 works
color when output1
and output2 work
color either output1
or output2 works
Power-saving mode
Copy function
Factory-fresh state
Hysteresis
setting
Bottom row
value
display
Display
period
setting
Color choice in
basic mode
Backlight
setting
Copy Function
2.Software:Set "CP-M" on master device. Set "CP-S" on slave device.
3.Icon of copy completed :
4.Turn off the power,disconnected devices and restart it after setting.
1.Hardware:Connect the second pin of master device with the third pin of slave
device,then power on after connecting.
Repeat step 1 and 2 if copy failed.
Power supply: DC24(+) (Brown)
Power supply: DC24(-) (Blue)
Output1(Black)
Output2(White)
Master device
Slave device
Zero-Clear Funtion Key lock Funtion
Press and simultaneously
Press any button will display "LCK" in lock on mode.
to reset the display value to
zero.
Press and
Lock:Press and the SET button simultaneously.
Release it when the display turns to "LoCK on".
Unlock:Press and the SET button simultaneously.
Release it when the display turns to "LoCK oFF".
Press and the SET
button simultaneously.
Press and the SET
button simultaneously.
simultaneously.
Bracket
Panel mount adapter + Front protective cover
DPS
Assembly type
EB:Panel mount
LB:Bracket
F -
Assembly code
29.6
45
20
20
14
20
9.6
19
14.7
t=1.6
31
0
-0.5
31
0
-0.5
4-3
5.2
5.2
Step1-Front cover assembly
Step2-Back cover assembly
Panel frame dimension
Unit:mm
Bracket dimension
Unit:mm
-High pressure(1000kPa) Unit:1kPa
-Low pressure(100kPa) Unit:0.1kPa
Hysteresis value
Pressure
Time
Set point value L
Time
Output:OFF
Output:ON
Set point value H
Mode setting- Pressure setting- Hysteresis value-
Window comparator mode:Set the pressure value H/L.When the applied pressure
value is greater than H + hysteresis value or less than L, the display will OFF.
When the applied pressure value is less than L + hysteresis value, the display
will ON.
Hysteresis value
Hysteresis value
Pressure
Time
Set point value L
Time
Output:OFF
Output:ON
Set point value H
Mode setting- Pressure setting-
Hysteresis mode:Set the pressure value H/L. When the applied pressure value is
greater than H, the display will ON. When the applied pressure is less than L,
the display will OFF.
Time
Set point value P
Time
Output:OFF
Output:ON
Pressure
Copy /Key lock /Zero-clear Function Output Mode Description
Mode setting-
Basic mode: Set the pressure value P. When the applied pressure value is
greater than P + hysteresis value, the display will ON. When the applied
pressure value is less than P + hysteresis value, the display will OFF.
Pressure setting- Hysteresis value-
Hysteresis value
Interface of advanced mode
  • Page 1 1
  • Page 2 2

AIRTAC DPS Series Quick start guide

Category
Measuring, testing & control
Type
Quick start guide

AIRTAC DPS Series is a digital display pressure switch with a wide range of capabilities for precise pressure monitoring and control in various applications. Here are some key features and possible use cases:

  • Accurate Pressure Measurement: With a measurement error of ±2% F.S. ±1 digit, the device provides reliable and accurate pressure readings.

  • Multi-Unit Pressure Range: The DPS Series offers multiple pressure range options, including -100kPa to 100kPa and -100kPa to 1000kPa, catering to diverse pressure monitoring needs.

  • Switchable Pressure Units: The device allows you to select from various pressure units such as kPa, MPa, kgf/cm2, bar, psi, mmHg, and cmHg, ensuring compatibility with different industry standards.