Fluidwell F030 Owner's manual

Category
Motor vehicle accessories & components
Type
Owner's manual
User Manual
F030-P
BATCH CONTROLLER
Signal input: pulse, NAMUR or coil flowmeter signal
Signal output: one control output for one stage batching
Options: intrinsically safe
backlight
F-Series - Field mounted indicators for safe and hazardous areas
More info: www.fluidwell.com/fseries
User Manual F030-P
Page 2 FW_F030-P_M_v0501-02_EN
TABLE OF CONTENTS
1 ABOUT THIS MANUAL............................................................................................................ 4
1.1 How to use this manual .................................................................................................. 4
1.2 Use of pictograms........................................................................................................... 4
1.3 Warranty and technical support ...................................................................................... 4
1.4 Model Reference ............................................................................................................ 4
2 SAFETY.................................................................................................................................... 5
2.1 Personal safety ............................................................................................................... 5
2.2 End-user responsibilities................................................................................................. 5
2.3 Potential equipment damage .......................................................................................... 5
2.4 Disposal of electronic waste ........................................................................................... 5
3 INTRODUCTION....................................................................................................................... 6
3.1 System description ......................................................................................................... 6
3.2 Product features ............................................................................................................. 6
3.2.1 General characteristics................................................................................................... 6
3.2.2 Input................................................................................................................................ 7
3.2.3 Output............................................................................................................................. 7
3.2.4 Options ........................................................................................................................... 7
3.3 Installation example ........................................................................................................ 7
4 OPERATION............................................................................................................................. 8
4.1 Introduction ..................................................................................................................... 8
4.1.1 Operating modes ............................................................................................................ 8
4.2 Control panel .................................................................................................................. 8
4.2.1 Display............................................................................................................................ 8
4.2.2 Backlight (Type ZB) ........................................................................................................ 9
4.3 Batching.......................................................................................................................... 9
4.4 Displayed information ..................................................................................................... 10
4.4.1 Totalized flow and accumulated total.............................................................................. 10
4.4.2 Clear total ....................................................................................................................... 10
4.5 Operator alarms.............................................................................................................. 10
4.5.1 Low battery ..................................................................................................................... 10
4.5.2 Internal error ................................................................................................................... 10
5 CONFIGURATION.................................................................................................................... 11
5.1 Introduction ..................................................................................................................... 11
5.2 Configuring using SETUP mode..................................................................................... 11
5.2.1 Entering SETUP mode ................................................................................................... 11
5.2.2 Navigating the SETUP menu.......................................................................................... 11
5.2.3 Changing configuration settings ..................................................................................... 12
5.2.4 Returning to Operator Mode........................................................................................... 12
5.3 SETUP menu overview................................................................................................... 13
5.4 SETUP menu explanations............................................................................................. 13
5.4.1 Menu 1: Preset .............................................................................................................. 13
5.4.2 Menu 2: Overrun ............................................................................................................ 14
5.4.3 Menu 3: Display ............................................................................................................. 14
5.4.4 Menu 4: Power management ......................................................................................... 15
5.4.5 Menu 5: Flowmeter ........................................................................................................ 15
5.4.6 Menu 6: Others .............................................................................................................. 15
6 INSTALLATION........................................................................................................................ 17
6.1 Installation / environmental conditions............................................................................ 17
6.2 Handling the F030-P enclosure ...................................................................................... 18
6.2.1 Identification.................................................................................................................... 18
6.2.2 Opening, assembling and closing the F-Series .............................................................. 19
6.3 Mechanical installation.................................................................................................... 21
6.3.1 Mechanical dimensions .................................................................................................. 21
6.3.2 Mounting the F-Series .................................................................................................... 23
6.4 Electrical installation ....................................................................................................... 24
6.4.1 Electrical safety............................................................................................................... 24
6.4.2 Protective earth (PE) connections .................................................................................. 24
6.4.3 Field wiring connections ................................................................................................. 25
6.4.4 Power supply .................................................................................................................. 26
6.4.5 Sensor supply................................................................................................................. 26
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 3
6.5 Terminal connectors safe area applications - Type PX, PD ........................................... 27
6.5.1 Terminals 1-3 (6): flowmeter input.................................................................................. 27
6.5.2 Terminals 4-5: Power supply - type PX and PD ............................................................. 30
6.5.3 Terminal 6: Sensor power supply - Type PD.................................................................. 30
6.5.4 Terminals 7-8: Control output - Type OT........................................................................ 30
6.5.5 Terminals 9-10: Backlight power supply - Type ZB ........................................................ 31
6.6 Terminal connectors safe area applications - Type PF, PM ........................................... 32
6.6.1 Terminals GND-1-2: Power supply................................................................................. 32
6.6.2 Terminals 3-4: Control output ......................................................................................... 32
6.6.3 Terminals 5-7: flowmeter input ....................................................................................... 33
7 INTRINSICALLY SAFE APPLICATIONS ................................................................................ 36
7.1 Identification.................................................................................................................... 36
7.2 Electrical installation in hazardous areas........................................................................ 37
7.2.1 Installations based on FM or CSA Certificate................................................................. 37
7.2.2 Electrical data - Control drawing..................................................................................... 38
7.2.3 Installations based on ATEX or IECEx Certificate.......................................................... 39
7.2.4 Electrical data - Annex 1................................................................................................. 40
7.2.5 Power supply .................................................................................................................. 41
7.2.6 Sensor supply................................................................................................................. 41
7.3 Terminal connectors hazardous area applications ......................................................... 41
7.4 Configuration examples Intrinsically Safe applications................................................... 42
7.4.1 F030-P-OT-PC-(PX)-XI-(ZB) - Ex ia IIC/IIIC................................................................... 42
7.4.2 F030-P-OT-PX-XI-(ZB) - Ex ia IIC/IIIC............................................................................ 42
7.4.3 F030-P-OT-PX-XI-ZB - Ex ia IIC/IIIC.............................................................................. 43
7.4.4 F030-P-OT-PD-XI-ZB - Ex ia IIC/IIIC.............................................................................. 43
8 MAINTENANCE........................................................................................................................ 44
8.1 General directions........................................................................................................... 44
8.2 Instructions for repair ...................................................................................................... 44
8.3 Battery replacement........................................................................................................ 45
8.3.1 Safety instructions .......................................................................................................... 45
8.3.2 Battery replacement procedure ...................................................................................... 46
8.3.3 Disposal of batteries ....................................................................................................... 46
APPENDIX A - TECHNICAL SPECIFICATION .............................................................................. 47
A.1 General ........................................................................................................................... 47
A.2 Input................................................................................................................................ 49
A.3 Output ............................................................................................................................. 49
A.4 Operational ..................................................................................................................... 49
APPENDIX B - TROUBLESHOOTING ........................................................................................... 50
APPENDIX C - LEGAL INFORMATION ......................................................................................... 51
C.1 Declarations of Conformity ............................................................................................. 51
User Manual F030-P
Page 4 FW_F030-P_M_v0501-02_EN
1 ABOUT THIS MANUAL
1.1 HOW TO USE THIS MANUAL
This operation manual is divided into two main parts:
The daily use of the F030-P is described in Section 4: Operation[»8]. These instructions are
meant for users / operators.
All subsequent sections and appendices are meant for electricians/technicians. These provide a
detailed description of all software settings and hardware installation guidance.
Always follow the instructions in this manual, especially the safety information. For additional
information, please contact your supplier.
1.2 USE OF PICTOGRAMS
A hazardous situation may occur if the unit is not used for the purpose it was designed for or is used
incorrectly. The following pictograms inform you of important information:
A warning indicates a hazardous situation that could cause injury or death.
A caution indicates a condition that could cause:
moderate/minor personal injury or equipment damage.
incorrect functioning of the unit or connected instruments.
A note informs you of important information.
1.3 WARRANTY AND TECHNICAL SUPPORT
For warranty and technical support on your Fluidwell products, visit our internet site
www.fluidwell.com or contact us at [email protected].
1.4 MODEL REFERENCE
Hardware version: 03.03.xx
Software version: 03.03.xx
Document version: FW_F030-P_M_v0501-02_EN
© Copyright 2023 Fluidwell B.V. - The Netherlands
Information in this document is subject to change without prior notice. The manufacturer is
not responsible for mistakes in this material or for incidental damage caused as a direct or
indirect result of the delivery, performance or use of this material.
© All rights reserved. No parts of this publication may be reproduced or used in any form or
by any means without written permission of your supplier.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 5
2 SAFETY
2.1 PERSONAL SAFETY
Explosion hazard: Never open the unit when explosive atmosphere is present, and the unit is
connected to a power supply or consuming device like the internal battery supply.
Risk of electric shock: Only open the unit if all leads are free of potential electrical energy.
Immediately inform the person responsible for the installation if you disagree with the safety
precautions or if you detect errors or danger.
Intrinsically Safe applications: follow the instructions as mentioned in Section 7: Intrinsically safe
applications[»36].
Certificates and related documents are available on our website or from your distributor.
2.2 END-USER RESPONSIBILITIES
Installation, use, and servicing of the unit must be done by authorized technicians.
This unit is not designed for use in life support appliances, devices, or systems where
malfunction of the product could result in personal injury. Customers using or selling these
products for use in such applications do so at their own risk and agree to fully indemnify the
manufacturer and supplier for any damages resulting from such improper use or sale.
Check all connections, settings and technical specifications of all peripheral devices supplied
with the unit.
The unit must be installed in accordance with the EMC (Electro Magnetic Compatibility)
guidelines.
Connect Protective Earth (PE) / proper grounding to the metal enclosure as indicated in
Section 6.4.2: Protective earth (PE) connections[»24].
If the unit is used on a ship, truck or somewhere else with no Protective Earth (PE) connection
available, connect an alternative grounding suitable for the application to the metal enclosure.
The Protective Earth (PE) wire (or alternative grounding) may never be disconnected or
removed.
The local labor and safety laws, and regulations must be adhered to.
Modifying the unit without prior written consent from the manufacturer will result in the
immediate termination of product liability and warranty period.
The manufacturer accepts no responsibility whatsoever if the safety information and instructions
in this manual are not observed.
2.3 POTENTIAL EQUIPMENT DAMAGE
Before installing the unit, check the mains voltage and information on the manufacturer's label
for product configuration.
Electro Static Discharge (ESD) causes irreparable damage to electronics. When installing or
opening the unit, the technician should first discharge him- or herself by touching a well-
grounded object.
Never touch the electronic components.
Never expose the unit to conditions that may exceed the enclosure classifications as indicated
by the manufacturer's label and Section 6.1: Installation / environmental conditions[»17].
2.4 DISPOSAL OF ELECTRONIC WASTE
At the end of its life this product should be disposed of according to the
(inter)national regulations regarding waste electronic equipment. If a
battery is installed in this product, it should be disposed of separately. The
separate collection and recycling of your waste equipment will help to
conserve natural resources and ensure that it is recycled in a manner that
protects the environment.
User Manual F030-P
Page 6 FW_F030-P_M_v0501-02_EN
3 INTRODUCTION
3.1 SYSTEM DESCRIPTION
The batch controller model F030-P is a microprocessor-driven instrument designed for batching and
filling of small batch sizes up to medium large quantities, as well as showing resettable total and a
non-resettable accumulated total.
Fig.1: The F030
This manual describes the daily use, configuration and installation of the F030-P with pulse input
from a flowmeter and its available options.
The following figure shows the F030-P used in a typical application.
Fig.2: Typical application
3.2 PRODUCT FEATURES
3.2.1 GENERAL CHARACTERISTICS
One control output for controlling a pump or valve
Ultra-low power consumption to allow for long battery life (Type PB/PC)
Various mounting possibilities
A choice of enclosure materials: GRP, aluminum or stainless steel (316L), suitable for every
industrial environment
Ability to process a broad range of sensor signals
Simple and standard configuration and operator interface.
Configuration
The F030 can be used for many types of application and has a SETUP mode to allow for configuring
it to your requirements. See Section 5: Configuration[»11] for further information.
All settings are stored in an EEPROM memory so they will not be lost if there is a power failure.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 7
3.2.2 INPUT
One flowmeter with a passive or active pulse, NAMUR or coil signal output
Several options are available for powering the sensor.
3.2.3 OUTPUT
One output is available on the F030-P to drive a pump or valve.
3.2.4 OPTIONS
Available options are:
Intrinsic safety (Type XI)
Power and sensor supply (Types PB, PC, PD, PF, PM, PX, in various combinations)
Output driving (Types OA, OR, OT)
Panel mount enclosure (Types HB, HC)
Flame-proof enclosure (Type XF)
Display backlight (Type ZB).
3.3 INSTALLATION EXAMPLE
Following parts can be recognized in below installation example.
13
24
56
Fig.3: Installation example F030-P
1. Front cover 3. Label 5. Keys
2. Display 4. Back cover 6. Cable entry (process mount)
User Manual F030-P
Page 8 FW_F030-P_M_v0501-02_EN
4 OPERATION
This unit may only be operated by authorized and trained personnel who have read and understood
this manual, particularly Section 2: Safety[»5].
4.1 INTRODUCTION
This chapter describes the daily use and operation of the F030-P. For this, the F-Series is equipped
with a control panel that provides the operator with various functions, information and operating
modes.
4.1.1 OPERATING MODES
The following operating mode are available:
OPERATOR-mode
This is the default mode of operation and mode indicator
RUN
is shown on the display. This
mode is available for all operators and gives access to the other modes. The available functions
and rights depend on the type of unit and configured settings. The unit will always return to this
mode when there is no user interaction for some time in any of the other modes.
SETUP-mode
This mode allows to review all configuration settings using a SETUP-menu. The mode indicator
SETUP
is shown on the display and access can be restricted via a password. After selecting a
configuration item, it can be changed using the PROGRAM-mode.
PROGRAM-mode
This mode is used to change settings in the SETUP-menu, enter values in OPERATOR-mode or
enter a password. When a setting is being changed, this is indicated by the mode indicator
PROGRAM
on the display.
The following paragraphs describe the modes of operation in more detail. SETUP-mode and
PROGRAM-mode are described in Section 5: Configuration[»11].
4.2 CONTROL PANEL
The control panel is located on the front side of the F-Series.
A Liquid Cristal Display (LCD) to show process values and various other information.
Three keys (PROG/ENTER, START, STOP) to control the F030 during operation.
An optional backlight to illuminate the display (Type ZB).
Functions of the keys in Operator Mode
PROG/ENTER-key
This key is used to program and save new values or settings.
The PROG-key is also used to gain access to SETUP mode, see Section 5:
Configuration[»11].
START-key
This key is used to START the batch process or continue the batch process after it has
been paused.
The START-key is also used to increase a digit after the PROG-key has been pressed
(see Section 5: Configuration[»11]).
STOP-key
This key is used to PAUSE the batch process (which can then be continued via the
START-key), and after that to STOP the batch process. When the batch process is
stopped, the STOP-key is used to select total and accumulated total.
The STOP-key is also used to select the next digit after the PROG-key has been pressed
(see Section 5: Configuration[»11]).
4.2.1 DISPLAY
In the F030-P, all inputs and outputs are continuously processed in the background. The relevant
process information is then displayed on a selection of screens when the product is in OPERATOR-
mode.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 9
The display contains one line with larger digits and one line with smaller characters below that. The
top line displays key process information, while the bottom line usually displays additional
information or system messages. Also, measurement unit and symbols to indicate operating mode,
function, and status may be displayed.
Normally, the display is updated depending on the refresh rate selected in the configuration settings.
By pressing any key, the display switches to refreshing the information 8 times per second. After 30
seconds of key inactivity, the display returns to the configured refresh rate.
4.2.2 BACKLIGHT (TYPE ZB)
The F030 with Type ZB is equipped with a backlight to illuminate the display for improved
readability. The backlight can be turned on or off, and its intensity can be set in the SETUP- menu.
4.3 BATCHING
Entering a batch quantity
To set the PRESET value:
1. When ACTUAL and PRESET are displayed, press PROG.
PROGRAM
will start flashing.
2. Use ► to select digits and ▲ to increase the selected value.
3. Set the new value by pressing ENTER.
When data is changed but ENTER has not been pressed yet, the changes can be cancelled by
waiting for 20 seconds or by pressing and holding ENTER for three seconds. The previous entered
value will be reinstated.
The programmed PRESET value will be used for each following batch, until a new value is set.
When trying to set a batch value which is too large the decrease sign ▼ will be shown while
programming. A value too high cannot be set!
SETUP
READY
RUN PAUSE PROGRAM
L
Fig.4: Example of display while programming preset value
Starting the batch process
Batching is started by pressing the START key. The batch process can only be started when
READY is displayed.
The arrows on the display indicate whether the ACTUAL value is (or was) counting up or down (see
SETUP
3.1: DISPLAY > FUNCTION).
PRESET
ACTUAL
RUN PAUSE PROGRAM
L
Fig.5: Example display information during batching process
Interrupting and aborting the batch process
When STOP is pressed once, the batch process will be temporarily interrupted; the running values
are not lost.
PAUSE
will be flashing. Batching can be resumed with the START-key.
The process can be ended entirely at all times by pressing STOP twice. Running values are lost and
the system returns to steady state. Batching cannot be resumed.
User Manual F030-P
Page 10 FW_F030-P_M_v0501-02_EN
PRESET
ACTUAL
RUN PAUSE PROGRAM
L
Fig.6: Example display information when paused
4.4 DISPLAYED INFORMATION
For displayed information during batching see Section 4.3: Batching[»9]. When no batch process is
running, the following functions/informations are available.
4.4.1 TOTALIZED FLOW AND ACCUMULATED TOTAL
When STOP is pressed, total and accumulated total are displayed. The unit is indicated on the top
line of the display, the resettable total is displayed on the second line with large digits and the non-
resettable accumulated total is shown on the bottom line. Accumulated total will count up to
99,999,999,999.
Unit and number of decimals are according to configuration settings
SETUP
1.1: PRESET > UNIT.
4.4.2 CLEAR TOTAL
The value for total can be re-initialized. To do so, select the Total display (press STOP while not
batching) and press PROG. Flashing text “PUSH STOP” is displayed. When STOP is pressed, the
total is reset to zero.
To avoid re-initialization, press another key than STOP or wait for 20 seconds.
Re-initialization of total DOES NOT influence the accumulated total.
4.5 OPERATOR ALARMS
4.5.1 LOW BATTERY
When the battery voltage drops, it must be replaced. To warn in time, an icon “LOW BATTERY” will
flash on the left side of the display. The F030 will continue to function correctly for several days up to
some weeks, but as soon as the warning stop flashing and is displayed continuously the battery
must be replaced shortly after, or it will run out.
See Section 8.3: Battery replacement[»45] for further information.
RUN
Fig.7: Example of low battery alarm
4.5.2 INTERNAL ERROR
When an internal error occurs, “ALARM” will be displayed. Press the SELECT key several times to
display the 4-digit error code. Consult Section B: Troubleshooting[»50] for more information.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 11
5 CONFIGURATION
5.1 INTRODUCTION
This chapter describes how technicians can use configuration settings to configure the F-Series for
optimal functionality. Configuration of the F030-P can be done in SETUP mode, using the front keys.
5.2 CONFIGURING USING SETUP MODE
For an overview of Operating modes, see Section 4.1.1: Operating modes[»8].
Changing settings may influence current operation
In SETUP mode the unit remains fully operational. Make sure the product is not being used for any
application when changing settings.
5.2.1 ENTERING SETUP MODE
1. Press the PROG-key for 7 seconds. During this, the symbols ▲▼ are displayed. You may be
prompted to enter a password.
2. The
SETUP
indicator is now activated on the display and the
RUN
indicator is deactivated.
5.2.2 NAVIGATING THE SETUP MENU
The SETUP menu contains several menu groups, which each contain various menu items. Each
menu item has a unique number which is displayed at the bottom of the display. Additionally, each
menu item is expressed with a keyword.
The menu number is a combination of two figures separated by a dot:
the first figure indicates the selected menu group (e.g. 1. TOTAL).
the second figure indicates the menu item (e.g. 1.1 UNIT).
The following image shows the layout of the menu structure:
Fig.8: SETUP menu layout and navigation
Navigate the SETUP menu with the following functions:
PROG-key
When a menu item is selected (e.g. 1.1), this key is used to start the programming
sequence.
When a menu group is selected (and no function), this key is used to scroll back a group
(e.g. 3. à 2. à 1. à 3. à 2. ...)
START-key
This key is used to select the next menu item in the list (e.g. 1. à 1.1 à 1.2 à 1.3 à
1. ...). When the top of the list is reached, it will wrap around and return to the menu group
selection.
STOP-key
This key is used to select the previous menu item in the list (e.g. 1.3 à 1.2 à 1.1 à 1. à
2. ...). When the bottom of the list is reached, it returns to the menu group selection.
When a menu group is selected (and no item), this key is used to scroll to the next group
(e.g. 1. à 2. à 3. à 1. à 2. ...)
User Manual F030-P
Page 12 FW_F030-P_M_v0501-02_EN
5.2.3 CHANGING CONFIGURATION SETTINGS
A menu item either contains a value (a number with optionally a decimal point and sign, e.g.
-123.45) or a selection list (e.g. L – m3 - USGAL). After a menu item is selected in the SETUP menu,
a new value can be programmed by performing the following steps. During the programming
sequence, the
PROGRAM
indicator is shown on the display.
Step 1: Start the programming sequence
PROG-key
When a menu item is selected in the SETUP menu, this key is used to start the
programming sequence.
Step 2a: Change a value
START-key
This key is used to increment the selected digit or to select de next position of the decimal
point.
When the entered value is out of range, the increase sign ▲ or decrease sign ▼ will be
displayed; the value will be automatically brought within range when confirmed later.
STOP-key
This key is used to select the next digit. If a decimal point can be set, this will be included
in the sequence as well (e.g. [decimal point] à digit 1 à digit 2 à digit 3 à [decimal
point].
Step 2b: Change the selection in a list
START-key
This key is used to select the next item in the list (e.g. L àà USGAL).
At the end of the list, the selection will wrap around to the first selection.
STOP-key
This key is used to select the previous item in the list (e.g. USGAL àà L).
At the end of the list, the selection will wrap around to the last selection.
Step 3: Finish the programming sequence
PROG-key
During the programming sequence, this key is used to confirm or cancel the new value
and return to SETUP mode. To cancel the operation, either press the PROG-key for 3
seconds or wait for 20 seconds: the programming sequence is cancelled and the former
value is reinstated.
5.2.4 RETURNING TO OPERATOR MODE
When all configuration settings are set correctly, return to OPERATOR mode by pressing the
PROG-key for three seconds, or do not press any key for 2 minutes to return automatically. The
RUN
indicator is now activated on the display and the
SETUP
indicator is deactivated.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 13
5.3 SETUP MENU OVERVIEW
1 PRESET DEFAULT
1.1 UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit L
1.2 DECIMALS 0 - 3 0
1.3 K-FACTOR 0.000010 - 9,999,999 0
1.4 DECIMALS K-FACTOR 0 - 6 0
1.5 BATCH MAXIMUM x,xxx,xxx 0
2 OVERRUN DEFAULT
2.1 OVERRUN disable - enable disable
2.2 TIME 0.1 - 999.9
3 DISPLAY DEFAULT
3.1 FUNCTION increase - decrease increase
3.2 BACKLIGHT off - on off
3.3 BACKLIGHT
BRIGHTNESS
1 - 5 5
4 POWER MANAGEMENT DEFAULT
4.1 LCD UPDATE fast - 1 sec - 3 sec - 15 sec - 30 sec - off 1 sec
4.2 BATTERY MODE operational - shelf operational
5 FLOWMETER DEFAULT
5.1 SIGNAL npn - npn_lp - reed - reed_lp - pnp - pnp_lp - namur -
coil_hi - coil_lo - active
coil_lo
6 OTHERS DEFAULT
6.1 TYPE / MODEL fixed F030-P
6.2 SOFTWARE VERSION fixed 03.xx.xx
6.3 SERIAL NUMBER fixed xxxxxxx
6.4 PASS CODE 0000 - 9999 0000
6.5 TAG NUMBER 0000000 - 9999999 0000000
5.4 SETUP MENU EXPLANATIONS
5.4.1 MENU 1: PRESET
Calculating the K-factor
The K-factor is used to convert the flowmeter pulse frequency to a quantity. Two examples are
given.
Example 1
The flowmeter generates 2.4813 pulses per liter.
The flow will be displayed using cubic meters (m3; 1.1: PRESET > UNIT).
A cubic meter equals 1000 liters, thus the flowmeter generates 2,481.3 pulses per m3.
Enter the K-factor as 248130 at 1.3: PRESET > K-FACTOR and 2 at 1.4: PRESET > DECIMALS K-FACTOR.
Example 2
The flowmeter generates 6.5231 pulses per gallon.
The flow will be displayed using gallons (1.1: PRESET > UNIT).
Enter the K-factor as 652310 at 1.3: PRESET > K-FACTOR and 5 at 1.4: PRESET > DECIMALS K-FACTOR.
User Manual F030-P
Page 14 FW_F030-P_M_v0501-02_EN
1 PRESET
1.1 UNIT Determines the measurement unit for preset, total and accumulated
total. The following units can be selected:
L - m3 - kg - lb - GAL - USGAL - bbl - no unit
Changing the measurement unit will have consequences for operator
and setup values. Please note that the K-factor should be checked also.
Recalculation is not done automatically.
1.2 DECIMALS Determines for Preset, Total and Accumulated Total the number of digits
after the decimal point.
1.3 K-FACTOR This value is used to convert the flowmeter pulse signals into a total unit.
The K-Factor is based on the number of pulses generated by the
flowmeter per selected measurement unit, as defined in 1.1: PRESET > UNIT.
Accuracy of the measurement system depends on the accuracy of the
K-factor.
Examples are given just above this table.
1.4 DECIMALS K-FACTOR This setting determines the number of decimals for the K-factor
(1.3: PRESET > K-FACTOR). Please note that this setting influences the
accuracy of the K-factor indirectly.
This setting has NO influence on the displayed number of digits set for
Unit (1.1: PRESET > UNIT).
1.5 BATCH MAXIMUM Sets the operator limit for entering a new preset value.
5.4.2 MENU 2: OVERRUN
Overrun can occur at the end of the batch process, as a result of slowness of a valve / pump.
Consequently, the accuracy is less. With this function, the F030 analyses the actual overrun
characteristic after every batch. This information is used to correct the overrun automatically.
2 OVERRUN
2.1 OVERRUN Enables/disables overrun function. Please note that, for accurate
overrun correction, the flowmeter used must have sufficient resolution
and an acceptable update time.
Do not enable the overrun functionality if the flowmeter does not meet
these requirements.
2.2 TIME The overrun characteristic of the system will be analyzed during a
certain time after ending of the batch. In this way, false signal generated
through leakage is eliminated. It is advisable to provide extra time in
order to avoid an incorrect overrun correction or false leakage alarms.
Enter here the expected time needed by the system to stop a batch.
Note that the next batch can only be started after the overrun time has
passed.
The minimum overrun time is 0.1 second, maximum 999.9 seconds.
5.4.3 MENU 3: DISPLAY
3 DISPLAY
3.1 FUNCTION The large 17mm digits can be set to display actual batched quantity
(increase) or to display the remaining quantity to be batched (decrease).
Display backlight is only available with Type ZB. The following functions
will affect this optional backlight.
3.2 BACKLIGHT With this setting, the optional backlight can be turned on or off.
3.3 BACKLIGHT
BRIGHTNESS
Backlight brightness can be adjusted with this setting. A value from 1 to
5 can be selected, where 1 is minimum, and 5 maximum brightness.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 15
5.4.4 MENU 4: POWER MANAGEMENT
4 POWER MANAGEMENT
4.1 LCD UPDATE Sets the LCD display refresh rate. The following can be selected:
fast - 1 sec - 3 sec - 15 sec - 30 sec - off
When a key is pressed, the display refresh rate will switch to ‘fast’ for 30
seconds. After this the refresh rate will return to the set update rate.
Please note that no information will be lost at low refresh rates: all
sensor input will be processed in the background.
Calculating the display information significantly affects the power
consumption. When the application does not require a fast display
refresh rate, it is strongly advised to select a slow rate.
Indication of expected battery life:
4.1: POWER MANAGEMENT > LCD UPDATE set to fast: 2 years
4.1: POWER MANAGEMENT > LCD UPDATE set to 1sec: 5 years.
4.2 BATTERY MODE The F030-P has two main modes: operational and shelf mode. In shelf
mode the product can be stored for several years with extremely low
power consumption from the battery. All settings and totals are
maintained in memory.
To wake up the F030 from shelf mode, simply press the ▲ key twice.
5.4.5 MENU 5: FLOWMETER
5 FLOWMETER
5.1 SIGNAL Selects the type of input sensor pickup / signal. The F030-P can process
several types of input signal. The settings with LP are used to apply a
built-in low-pass filter.
FLOWMETER SELECTION CHARACTERISTICS
TYPE OF SIGNAL EXPLANATION RESISTANCE FREQ / mVpp REMARKS
NPN NPN input 100kΩ pull-up max.6kHz
threshold1.2V Open collector
NPN - LP NPN input
with low pass filter 100kΩ pull-up max.1.2kHz
threshold1.2V
Open collector
less sensitive
REED Reed-switch input 1MΩ pull-up max.600Hz
threshold1.2V
REED - LP Reed-switch input
with low pass filter 1MΩ pull-up max.120Hz
threshold1.2V Less sensitive
PNP PNP input 47kΩ pull-down max.6kHz
threshold1.2V
PNP - LP PNP input
with low pass filter 100kΩ pull-down max.1.2kHz
threshold1.2V Less sensitive
NAMUR NAMUR input 820Ω pull-down max.4kHz External power
required
COIL HI Coil input
high sensitivity -
min.20mVpp Sensitive for
interference
Type ZF min.10mVpp
Type ZG min.5mVpp
COIL LO Coil input
low sensitivity - min.90mVpp Normal sensitivity
ACTIVE
Active pulse input
detection level
1.2VDC
47 kΩ max.10kHz External power
required
5.4.6 MENU 6: OTHERS
6 OTHERS
6.1 TYPE / MODEL
Provides important information on your product. This information may be
required for maintenance or support.
6.2 SOFTWARE VERSION
6.3 SERIAL NUMBER
User Manual F030-P
Page 16 FW_F030-P_M_v0501-02_EN
6 OTHERS
6.4 PASS CODE All SETUP values can be password protected.
A four-digit password can be programmed, for example 1234.
To disable password protection, enter four zeros (0000).
6.5 TAG NUMBER For identification of the F030 and communication purposes, a unique tag
number of maximum seven digits can be entered.
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 17
6 INSTALLATION
Mounting, electrical installation, start-up and maintenance of this instrument may only be
carried out by trained personnel authorized by the operator of the facility. Personnel must read
and understand this Operating Manual before carrying out its instructions.
The F030-P may only be operated by personnel who are authorized and trained by the operator
of the facility. All instructions in this manual are to be observed.
Ensure that the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is removed
or the panel cabinet has been opened (danger from electrical shock). The housing may only be
opened by trained personnel.
Take careful notice of Section 2: Safety[»5] at the front of this manual.
6.1 INSTALLATION / ENVIRONMENTAL CONDITIONS
The F-Series can be supplied for use in Safe Areas or for Hazardous Locations. This is indicated in
the model code by the Type X- designator, shown on the label.
Type XX Suitable for Safe Area applications only. Follow the mechanical and electrical
installation instructions in this chapter.
Type XI Suitable for intrinsically safe applications in Hazardous Locations. Follow the General
mechanical and electrical installation instructions in this chapter, and the specific
instructions in Section 7: Intrinsically safe applications[»36]. In case of conflict,
Section 7: Intrinsically safe applications[»36] has precedence over Section 6:
Installation[»17].
Type XF Suitable for explosion proof/flame proof applications in Hazardous Locations. Follow
the instructions in this chapter and the installation instructions supplied separately.
Take the relevant IP classification of the enclosure
into account (see identification plate). Even an
enclosure rated for IP67 / NEMA Type 4X should
NEVER be exposed to strongly varying (weather)
conditions.
When used in very cold environment or varying
climatic conditions, inside the instrument case, take
the necessary precautions against moisture.
Mount the F030-P onto a solid structure to avoid
vibrations.
For use in Safe and Hazardous Areas (or Locations), the following conditions apply:
Relative humidity < 90% RH
Outdoor use Suitable for outdoor use
IP and NEMA rating Panel mount: IP65. Field mount: IP67. NEMA Type 4X
Supply voltage
fluctuation
As indicated by supply range (e.g. 10 to 30 V). Otherwise+/-10% unless
stated otherwise
Means of protection Intrinsically safe IS
Ordinary locations Class I (PE connected to metal enclosure)
Class II (non-metallic enclosure)
Over-voltage category II (when supplied from mains)
Pollution degree 2 (internal environment), 3 (external environment)
Ambient Intrinsically safe -40 ºC to +70 ºC, -40 ºF to +158 ºF
For EPL Da -40 ºC to +50 ºC, -40 ºF to +122 ºF
Ordinary locations -40 ºC to +80 ºC, -40 ºF to +176 ºF
Altitude up to 2000 meters (6600 feet)
User Manual F030-P
Page 18 FW_F030-P_M_v0501-02_EN
6.2 HANDLING THE F030-P ENCLOSURE
6.2.1 IDENTIFICATION
The F-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for
Intrinsic Safety is indicated in the model Type XI.
Refer to Section 7: Intrinsically safe applications[»36] for identification and installation labels
for Intrinsically Safe applications.
Your product is supplied with external (top) and internal (back) labels, except panel mount versions
(Type HB or HC) which do not have a top label.
Identification label
To identify your F0-Series device, all field mount enclosures have a weatherproof identification label
placed on the outside of the product.
Fig.9: Example of F0-Series identification label (Safe Area)
Installation label
An installation label is located at the inside of the enclosure (Type HB or HC: backside).
Fig.10: Example of F0-Series installation label (Safe Area – Type PX or PD)
F030-P User Manual
FW_F030-P_M_v0501-02_EN Page 19
Fig.11: Example of F0-Series installation label (Safe Area - Type PM or PF)
Serial number and year of production
The serial number can be reviewed on the identification label, the
installation label, or in
SETUP
6.3: OTHERS > SERIAL NUMBER. The production
date is shown on the label and also indicated by the first 4 digits of the
serial number representing year and week number (YYWW).
6.2.2 OPENING, ASSEMBLING AND CLOSING THE F-SERIES
Panel mount versions (Type HB or HC) do not have a back cover. When removed from their
mounting panel the connectors are readily accessible.
Opening the unit
To open the F-Series enclosure, the front cover needs to be removed. Please follow this procedure.
1. If necessary, clean the enclosure with an anti-static
cloth made damp with a mild soap solution. Wait for
the enclosure to dry before opening.
2. While loosening the screws, hold on to the front cover
to prevent it from falling down.
3. Unscrew all 4 screws from the front of the enclosure
and (if present) mind that the serrated washers are
kept with the screws.
4. Carefully take the front cover away from the rear
cover, minding that the wiring stays intact.
5. Depending on the work to be done, all terminal
connectors can be removed from their mating parts
and the front cover is now completely separate.
User Manual F030-P
Page 20 FW_F030-P_M_v0501-02_EN
Closing / replacing the cover
1. Re-insert all terminals to their original position.
2. Carefully position the front cover onto the back cover,
making sure that the gasket falls nicely into the gutter of
the back cover.
3. Place all 4 screws into the front cover and mind that the
serrated washers are replaced (metal enclosure only).
4. Fasten all 4 screws in an alternating way so that the front
cover is placed evenly across the edge of the back cover.
5. Tighten the 4 screws with the torque value for the type of
enclosure as specified in following table
Plastic enclosure 1 Nm
Aluminum enclosure 1 Nm
Stainless steel enclosure 2 Nm
6. The F-Series is now ready to be returned to service.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

Fluidwell F030 Owner's manual

Category
Motor vehicle accessories & components
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI