Pepperl+Fuchs PS3500-DM Owner's manual

Type
Owner's manual

This manual is also suitable for

REDUNDANT POWER SUPPLY
INSTALLATION & OPERATION MANUAL
PROCESS AUTOMATION
PS3500 N+1
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
1
Contents
1 Introduction .................................................................................................................. 2
2 Instructions ................................................................................................................... 3
2.1 Intended use .......................................................................................................... 3
2.2 Product label.......................................................................................................... 3
2.3 Mounting................................................................................................................ 4
3 Specications ............................................................................................................... 5
3.1 Powersupplymodulespecications ...................................................................... 5
3.2 Systemspecications ............................................................................................ 7
3.3 Dimensions ............................................................................................................ 8
4 TemperatureConsiderations ...................................................................................... 9
4.1 Convection cooling ................................................................................................ 9
4.2 Forced cooling ..................................................................................................... 10
4.3 Clearances .......................................................................................................... 10
5 TechnicalConcept ...................................................................................................... 11
5.1 N+1 redundancy .................................................................................................. 11
5.2 Hot swapping ....................................................................................................... 11
5.3 Automatic load-sharing ........................................................................................ 11
5.4 Variable output voltage ........................................................................................ 11
5.5 Alarm output ........................................................................................................ 11
5.6 Internal diagnostics, recovery, and LEDs ............................................................. 12
6 Wiring .......................................................................................................................... 13
6.1 Specicconditionsofuse .................................................................................... 13
6.2 Input supply line ................................................................................................... 13
6.3 Inputcongurations ............................................................................................. 14
6.4 Outputconguration ............................................................................................ 16
6.5 Alarmconguration .............................................................................................. 17
7 OutputCongurations ............................................................................................... 18
8 Operations .................................................................................................................. 19
8.1 Supply line checks ............................................................................................... 19
8.2 Output line checks ............................................................................................... 19
8.3 Alarm lines checks ............................................................................................... 19
8.4 Commissioning .................................................................................................... 19
9 Maintenance&Repair ............................................................................................... 20
10 Troubleshooting ......................................................................................................... 21
11 SpecialWarnings! ...................................................................................................... 22
12 Notes ........................................................................................................................... 23
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
2
1 Introduction
ThismanualappliestothePepperl+FuchsPS3500system,whichconsistsoftheproducts
shown in Table 1:
Modelnumber Description
PS3500-PM-1.24.15 N+1 power supply module, 24 V DC @ 15 A
PS3500-TB-3 Backplaneforthreepowermodulesandonediagnosticmodule
PS3500-TB-6 Backplaneforsixpowermodulesandonediagnosticmodule
Table 1. PS3500 series product range
Themanualassumesthattheuserhastechnicalknowledgeofandexperiencewithpower
supplysystems,explosionprotection,aswellasplanningandinstallingpowersystems.It
doesnotprovideanintroductiontopowersystemsorexplosionprotectionforinexperienced
users.Thecontentofthismanualappliesinconjunctionwiththerespectivedatasheets,
DeclarationofConformityandCerticateofCompliance.Forfurtherinformationpleaserefer
to the Pepperl+Fuchs "Wiring and Installation Guide."
Substantialamountsofvoltage,currentandpowerareprovidedbythesupply.Readthis
manualcarefullybeforeinstallationandoperationtoavoidriskofdamage,failures,or
personalinjury.Takegreatcareoninputandoutputsupplylinestoprotectfromtheeectsof
short circuits and provide the required ground connections.
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
3
2 Instructions
2.1 Intended use
The PS3500 product range may be installed in Zone 2 or Class I/Division 2
hazardousareas.TypeofprotectionisExecnC(non-arcing,sealeddevice)
forZone2GasGroupsIIC,andnon-incendiveforuseinClassIDivision2Gas
GroupsA,B,C,andD.Pleaseconsultlocalelectricalcodesforhazardouslocation
installation guidelines.
NOTE:ThisequipmentissuitableforuseinClassI,Division2;GroupsA,B,C,DandClass
I,Zone2;GroupIICornonhazardouslocationsonly.
TheDeclarationofConformity,CerticateofComplianceanddatasheetsareconsidered
asanintegralpartofthisusermanual.Thedatasheetscontaintheelectricaldataofthe
DeclarationofConformityandtheCerticateofCompliance.Lawsand/orregulations
governing the use or intended use must be observed.
ThePS3500productsareonlyapprovedforproperprofessionaluseinaccordancewith
the intended purposes. Improper handling will void any claim made under the warranty as
wellasanymanufacturer’sliability.ThePS3500systemcanonlybeoperatedbytrained
professionalsinaccordancewiththismanual.
2.2 Productlabel
Forproperidenticationandoperation,examinethesystemmodelnumbernameplateto
identifytheappropriateapprovals,areaclassication,andtypeasnotedinFigure1:
Figure 1. Power Supply Module
Figure 2. Backplane
Warning
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
4
2.3 Mounting
2.3.1 Mounting PS3500 backplanes (termination boards) PS3500-TB-*
ThePS3500backplanesaredesignedforprotectionclassIP20inaccordancewithEN60529and
must be protected against adverse ambient conditions such as water or dirt ingress.
Thebackplanechassisismountedonaatmetalsheetplateorontwoproperlyspacedrails.Drill
four5mm(0.2")DIAholesandtapthem6MA(or1/4"NC).Insertthetopandbottomscrewsbut
leaveagapofapproximately5mm(0.2")betweenthescrewheadsandmountingsurface.Slide
thechassisthroughthekeyedholesandhangitrmlyonthescrewheads.Proceedtotightenall
the screws.
2.3.2 Mounting PS3500-PM-1.24.15 power modules
ThehousingofPS3500-PM-1.24.15meetsthedegreeofprotectionclassIP20.Itisintendedfor
mounting on the PS3500 backplane PS3500-TB-*.
Toinstallanewmoduleonthebackplaneproceedasfollows:
1. Carefullycenterandmatetheplugandconnectoronthebackofthepowermoduletothe
backplane;thenpressrmlyonthemodule.
2. With a screwdriver, screw in the top and bottom mounting screw on the power module to
secure the module in the slot.
3. Themodulesarehotswappable;theycanbereplacedwithoutshuttingdownthesystem.See
Section 5.2, Hot swapping.
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
5
3 Specications
PS3500 has a wall-mount, multi-slot backplane accepting hot swappable plug-in power
converter modules that provides an isolated output at 24 V DC nominal.
Each power module has an individually isolated input port accepting either AC or DC that
providesinrushcurrentlimitingandpowerfactorcontrol.Theoutputportiscompletely
isolatedfromtheinputandprovidesupto15Apermoduleatanominal24VDC(adjustable
22.5to30Vfromchassismountedtrimmer)withaloadsharingcongurationforparalleled
output operation. Input and output lines can be wired independently or in parallel providing
N+1 redundant structures.
SystemcongurationisobtainedbywiringandcongurationDIPswitchesonthevarious
backplane slots leaving power modules interchangeable and easily swappable under load.
AllrelevantfailuresinthemodulesaredetectedandsignaledbyindividualLEDsandalarm
relaysprovidingaexiblecombinationofredundancy,faulttolerance,andautomaticfault
detection ideally suited to critical applications.
FullcompliancetotheEUdirectivesforEMCandlow-voltageequipmentensureminimum
emissionsandhighimmunityinharshenvironments.Highconversioneciencynormallypermits
naturalconvectioncoolingoperationeliminatingcoolingfansformostapplicationrequirements.
3.1 Powersupplymodulespecications
Mechanicalspecications
Dimensions (134mmx62mmx268mm)5.3”x2.5”x10.6”
Input
Voltage 90…250VAC±10%;90...300VDC,overvoltagecategoryII
Input current Max.6.5A
Eciency Up to 91%
Inrush current <50Apeakfor50µs
Powerfactor > 0.97, 50...100% load
Output
Voltage 24VDC+/-1%,adjustablebetween22.5...30V
Current 15A(SeeOutputDeratingCurves)
Fault signal Relay50V/0.6Aor30V/1ADC
Short-circuit current ≤20A
Temperaturecoecient ±0.01%per°Cmax
Input regulation <100mV(90...250VAC;90...300VDC)
Load regulation <100mV(0...15Aoutputload)
Turn-on/turn-ovoltagetransient 200mstonalvalue(noover/undershoot)
Ripple 35 mV rms(<100mVpp)
Responsetime Min.hold-uptime:≥25msatnominalinputvoltage&outputload
Indicators/settings
Display elements LED Power, green: power on
LEDFault,red:faultindication
LED Alarm, red: module shut-down
Table 2. Power supply module specications
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
6
3.2 Systemspecications
Electricalisolation
Input/output 4.25 kV DC
3.0 kV AC
Input/ground 2.12 kV DC
1.5 kV AC
Output/ground 2.12 kV DC
1.5 kV AC
Ambient conditions
Ambient temperature -25…+45 °C derated 45...70 °C at 0.45A per °C above 45 °C
Altitude Installation is 2000 m or less
Polution degree Polution degree 2 or 1
Storage temperature -40…+85 °C
Shock resistance 15 g, 11 ms
Vibration resistance 1 g, 58...150 Hz
Relativehumidity < 95 % non condensing
Mechanicalspecication
Protection degree IP20
Weight Approximately1.8kg(4.125lbs)
Directiveconformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
EN 61000 sections 4-2, 4-4, and 4-6
EN 55011
Conformity
Electrical isolation IEC 61131-2
Electromagnetic compatibility NE 21
Protection degree EN 60529
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
7
Dataforapplicationinconjunction
withhazardousareas
TypeExaminationCerticate DEMKO12ATEX1103387XRev.2
Group,category,typeofprotection II3GExecnCIICT4Gc(PS3500-PM)
II3GExecIICT4Gc(PS3500-TB)
Directiveconformity
Directive 2014/34 EU EN IEC 60079-0:2018, EN 60079-7:2015+A1:2018, EN
60079-11:2012, EN 60079-15:2019, EN 61010-1
UKSI2016No.1107(EX) EN IEC 60079-0:2018, EN 60079-7:2015+A1:2018, EN
60079-11:2012, EN 60079-15:2019
Internationalapprovals
IECExapprovals ExecnCIICT4Gc(PS3500-PM)
ExecIICT4Gc(PS3500-TB)
IECExUL13.0082X
UL Listed UL121201(9thEd.,2019)
UL 508
CSA C22.2 No. 213-17,
CSA C22.2 No. 107.1-16
Approvedfor Class I, Zone 2, Group IIC T4
Class I, Division 2, Groups A, B, C, D, T4
CCC approval ExicnAnCIICT4Gc(PS3500-PM-1.24.15)
ExnAnCIICT4Gc(PS3500-DM)
CerticateNo.:2021322303003616
ExnAnCIICT4Gc(PS3500-TB)
CerticateNo.:2021322308004230
Generalinformation
Supplementaryinformation StatementofConformity,DeclarationofConformityand
instructions have to be observed where applicable.
Forinformation,seewww.pepperl-fuchs.com.
Table 3. System specications
3.2 Systemspecications(continued)
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
8
3.3 Dimensions
 mm(in)
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
9
4 TemperatureConsiderations
Temperatureacceleratesthefailuremechanismofeveryelectroniccomponent(Arrhenius
criteria).Iftheoperatingtemperatureisincreasedby10°Cfromitsnormaloperatingrange,
-25…+45°C(-11...+113°F),itsexpectedlifeisalmostcutinhalf.
Temperature rise depends on dissipated power density. For the same enclosure volume
morepowerdissipatedproduceshighertemperaturerise.Forexample,acabinet600x
600x2000mmdissipating300Wwithnaturalconvectioncoolingproducesaninternal
temperatureriseof10°C.Thisshouldberegardedasanidealcase.
Identifytheworstload/temperatureenvironmentthatthepowersupplywillencounterand
determine the recommended cooling method.
Use convection coolingwhenthesupplyloadistypicallyinthelowerpartoftheshaded
regioninFigure3andfreeaircirculationisensured.
Use forced coolingwhenthesupplyloadisintheupperpartoftheshadedregionin
Figure3forextendedperiodsoftimeorwhenaveryhighsystemreliabilityisrequired.
Figure 3. Recommended load current per module vs. operating temperature
4.1 Convectioncooling
Hotcomponentsexchangeheatwiththesurroundingairproducingaverticallyrisinghot
airow.Thisdeterminesnewcoolairintaketocoolthecomponentinanaturalconvection
coolingmode,whichiscontrolledbytheintakeairtemperatureandow.
Forgoodconvectioncooling,installtheequipmentwithanunobstructedvertical
owofrelativelycool(ambienttemperature)airenteringfromthebottomandow
outatahighertemperaturefromthetop.Toavoidexcessivetemperaturebuildup,
donotstackpowerdissipatingdevicesverticallyincloseproximity.
PS3500 Temperature Derating
0
2
4
6
8
10
12
14
16
Ambient Temperature (°C)
Load Current (A)
70°
0° 4
100 %
25 %
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
10
4.2 Forcedcooling
Forcedcoolingisobtainedbyusingsuitablefans.Fansgenerateastrongairowthat
removesheatfromthepowergeneratingequipment.Usetwo(PS3500-TB-3)orfour
(PS3500-TB-6)120mm,100m3/h,brushless,long-lifefansoperatedfromtheoutputbusat
24VDC(e.g.,PAPSTtype)installedimmediatelybelowthebackplanesandblowingairup
againstthebottomofthepowermodules.Makesuretoallowrelativelyfreeairowbelowthe
fansandabovethesupplyrack.
4.3 Clearances
Forclearances,wewouldrecommend1.25”fromthesidesofthepowersupplies,and5”
fromthetopandbottomwhenorientedinthestandardhorizontalposition,forconvection
cooling.Ifusingforcedairconvectioncooling,thismaybereducedsome.Thisassumesthat
belowthebackplaneisnotanothersourceofheat.
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
11
5 TechnicalConcept
Thepowersupplysystemconsistsoftwodierentbackplanes(3and6slots)andthepower
supplymodule.Thekeyfeaturesofthesystemare:
Nominal output 24 V/15 A per module
• Nominalinputof90to250VAC/90to300VDCpermodule
N+1 redundancy
Automatic load-sharing
• Higheciency(upto91%)
• Fanless
• Moduleoutputvoltageisadjustableatthebackplanefrom22.5Vto30V
• Basicmodulefailurealarmingviarelaycontact(normallyopen/closecongurable)
• Redundancyonsupplyline
5.1 N+1redundancy
N+1redundancyisbasedonthefact,thatthemaximumdrawncurrentislowerthanthe
maximumcurrentprovidedbytheoverallnumberofmodulesminusone.Basedonthe
backplane size, N can be any number between 1 and 5.
5.2 Hotswapping
Hotswappingallowsreplacementofamoduleunderpowerwithoutanyvisiblefunctional
impact on the output side. Hot swapping is allowed only in an environment where no
hazardousmaterialsarepresent.ThehotswappingfeatureisnotpermittedinaClassI/Div2
area or Zone 2 area unless under a hot permit.
5.3 Automaticload-sharing
Thepowersupplymodulesimplementarealload-sharingfunction;allmodulessupplythe
sameamountofcurrent.Thetoleranceforthecurrentdierencebetweenthemodules
shouldbewithinarangeof±1.5A.
5.4 Variableoutputvoltage
Thefactorydefaultoutputvoltageis24V.Theoutputvoltageisadjustableinarangefrom
22.5Vto30Vforeachmodulebyusingapotentiometer.Insertedmodulescanbeeasily
adjustedwithascrewdriverduringsetup.Potentiometersareaccessibleontheadjacent
backplaneslotmakingthevoltagesettingtamperproofduringoperation.
5.5 Alarmoutput
Eachpowermodulehasitsownalarmmonitoringcircuitthatcontrolsarelayforacommon
failureoutputsignal.Itcanbecongurednormallyopenornormallyclosedusingtheterminal
blocks on the backplane.
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
12
5.6 Internaldiagnostics,recovery,andLEDs
Overvoltage(OV),overcurrent(OC),andoverheat(OHT)conditionsleadtoanoutput
shutdownoftheunit.Theyalsocreateanalarmsignalattheinternalrelay.Undervoltage
(UV)createsanalarm,butdoesnotshutdowntheunit.
Duringshutdownmode,theunitcontinuouslychecksfortheactualfailureconditiontogo
away.Ifthatisthecase,theunitwouldgobacktonormaloperation.However,thisbehavior
must not impact the remaining running units in an N+1 redundant system.
There are three LEDs:
• Powergood(green)
• Fault(red)
• Alarm(red)
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
13
6 Wiring
ThePS3500systemhasseparateinput/outputterminalblocksforsimpleconguration.
Connectgroundterminalstothemainsground,otherwiselethalvoltages
mayoccur.
Permanentpowermoduledamagewillresultincaseofinputvoltage
overload.
6.1 Specicconditionsofuse
1. Tobeinstalledinanend-useATEXapprovedsystem,providingre,impact,grounding,
andaccessibilityprotection.ThepowersupplymustbeinstalledinanATEXCertied,
IP54 enclosure. Alternatively, the power can be installed in an IP4X enclosure, having
adequateprotectionagainsttheentryofsolidforeignobjectsorwatercapableof
impairingsafety.
2. GND connection on backplane at Mains supply connections is a protective ground
connection.Thewireguageshouldbeatleastthesameaswhatisusedforthemains
powerfeed.
3. Foranyhazardouslocations(ClassI/Div2,Zone2)thePS3500systemmustbeinstalled
in a locked enclosure.
4. Powersupplymustbesecuredtosystemusingscrewsrequiringtoolsforremoval.
5. Forindooruseonly;nottobesubjectedtoUVexposurefromluminaires.
6. Ambientratingsforoperationare-25…+45°C,derated45...70°Cat0.45Aper°Cabove
45 °C. See Figure 3, temperature curve.
7. ThePS3500systemisdesignedforuseinpollutiondegree2environments.
8. For use with Class 1 conductors or equivalent.
9. For use with CU conductors or equivalent.
10. Use 14 AWG conductors or equivalent.
11. Use conductors rated 75 °C minimum or equivalent.
12.Alarmrelaycontactsareratedfor50VDCorlessandareintendedtobepoweredbyDC
sourceswithproperisolationfromMAINS.
13.Thedevicemustbeinstalledandoperatedonlyinanenvironmentofovervoltage
categoryII(orbetter)accordingtoEN60664-1.
14. The device must be installed and operated only in a controlled environment that ensures
apollutiondegree2(orbetter)accordingtoEN60664-1.
15. The device must be installed and operated only in surrounding enclosures that
 ComplywiththerequirementsforsurroundingenclosuresaccordingtoEN60079-0
 AreratedwiththedegreeofprotectionIP54accordingtoEN60529.
6.2 Inputsupplyline
Powerlinevoltageis90...250VAC±10%(90...300VDC).Checksupplylinevoltageto
meetpowermodulesupplyrequirements.Planfordisconnectingcapabilityandovercurrent
protectionbyadequatelysizedfusesorcircuitbreakersonthelines.
Circuitbreakersorfusingsholdbe20Aorless.connectionsto6poitionbackplanewill
require2breakersorfusedsourcesfeedingthebackplane.Groupof3slotsneeds20A
breaker or less. A single 40A breaker is not allowed.
Groundconnectionshouldbemaderst.
Warning
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
14
InputTerminals
strip length = 8mm
wireguagemax=4mmsq(10AWG)
tightening torque 0.6–0.8 N-m
OutputTerminals
strip length = 12mm
wireguagemax=10mmsq(6AWG)
tightening torque 1.2–1.5 N-m
OtherTerminals
strip length = 7mm
wireguagemax=2.5mmsq(12AWG)
tightening torque 0.5–0.6 N-m
6.3 Inputcongurations
6.3.1 Single line input
Usewithuninterruptiblepowersystems(UPS)supplyorwheninputlineintegrityisnot
critical, wire per sketch in Figure 4. For DC input, polarity does not matter.
N
L
Note!
Each spur to the individual group
of 3 power supplies needs its own 20 A breaker.
Figure 4. Single line input connection
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
15
6.3.2 Dual Line Input
WirepersketchinFigure5.Forredundantinputlineconguration,loadshouldnotexceed
45 Amps per every 6-position backplane used.
Figure 5. Dual line input connection
6.3.3 Independent line connection
WirepersketchinFigure6.Forindependentinputlineconguration,loadshouldremain
separated.
Figure 6. Independent multi input line connections
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
16
6.4 Outputconguration
Each power module slot has a 6-position DIP switch that enables the various alarm
congurationsaswellastheloadsharingabilityofeachPS3500powermodule.SeeTable4
forproperconguration.Thesecongurationsareonaperslotbasis.
Sx.1 Sx.2 Sx.3 Sx.4 Sx.5 Sx.6
Parallel alarm Off On Off Off x x
Serial alarm+On Off On On/ Off* x x
Load share OFF x x x x Off Off
Load share ON x x x x On On
*Any slot not having a module should have DIP switch #4 turned on
+Slot#1,S1.1andS1.2areinparallelthereforeeitheronecanbeon.
Table 4. Alarm/load sharing conguration
6.4.1 Independent outputs
Useforseparateoutputapplications;wireperFigure7.
+
Out 1
- +
Out 2
- +
Out 3
- +
Out 4
- +
Out 5
- +
Out 6
-
Figure 7. Independent output lines
6.4.2 Common outputs
Useforbusconnectedoutputorredundantcongurations;wireperFigure8.RefertoTable
4forloadshareDIPswitchconguration.Formultibackplaneparalleloperation,extendload
sharingconnectionsatterminals5and6tothenextbackplane.
NOTE:Aseparatebusisrequiredforloads>45A.
+
Load Sharing
-
Figure 8. Bus connected output or redundant congurations
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
17
6.5 Alarmconguration
6.5.1 Parallel alarm
Connectinparallel,asperFigure9,thenormallyclosed(N.C.)alarmcontactsonallpower
modules,andrefertoTable4forparallelalarmDIPswitchconguration.Whenanyspecic
relayonamoduledeenergizesunderalarmcondition,includingpowero,thecircuitwill
closeandactuateanalarm(atterminals1-2ofthealarmterminalblock).Pullingapower
moduleoutofthebackplanewillnotactuateanalarm.
Figure 9. Parallel alarm
6.5.2 Serial alarm
Connectinseries,asperFigure10,thenormallyopen(N.O.)alarmcontactsonallpower
modulesandrefertoTable4forserialalarmDIPswitchconguration.Whenanyspecic
relay on a module de-energizes under alarm condition, the circuit will open and cause an
alarm.Removingamodulewillsetothealarm.Anyslotwithoutamodulewillneedtohave
DIPswitchSx.4turnedon.
Figure 10. Serial alarm connection
1
1 2 3
NC
NOTE: Alarm relay # 3 shown in alarm position
2
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
18
7 OutputCongurations
Alarmconguration Module Nomodule
(emptyslot)
Parallel with
Load Share
Sx
OFF OFF = Open
Parallel without
Load Share
Sx
Serial with
Load Share
Sx
Sx
Serial without
Load Share
Sx
Sx
Note: DiagnosticModuleDIPSwitches
When the Diagnostic Module is not in use, all Diagnostic Module port DIP
switches must be set to the "OFF" position.
Subject to modifications www.pepperl-fuchs.com
USA: +1 330 486 0002 Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PS3500 N+1 Redundant Power Supply
19
8 Operations
Warning!
Donotplugandpowermodulesonthebackplanebeforecheckingallthesystems
as recommended.
8.1 Supplylinechecks
1. GroundingconductortobeconnectedandrmlysecuredtotheGNDterminals.
2. Inputlinestobeprotectedbyappropriatelysizedfusesorsectioningcircuitbreakers
(turningthemo).
3. Lineconductorstobeofadequatesizeandrmlysecuredwithnoexposedconductors
risking contacts with the backplane or short circuits.
4. Supplylinevoltagetomeetpowermodulerating.(Checksidelabel.)
8.2 Outputlinechecks
1. Outputpolaritytobecorrect.(Severedamagetothepoweredequipmentmightresultin
caseofreversepolaritypowering.)
2. Outputvoltagevalue24V.Checkonsidelabelofpowermodules.
3. Outputconductorstobeofadequatesizeandrmlysecuredwithnoexposedrisking
contacts with the backplane or short circuits.
4. LoadsharingDIPswitchescongurationareset.(SeeSection6.4.)
8.3 Alarmlineschecks
1. Alarmcircuittobecorrectlywiredandconductorsrmlysecuredwithnoexposed
conductors risking contacts with the backplane or short circuits.
2. AlarmDIPswitchescongurationset.(SeeSection6.4.)
8.4 Commissioning
1. Pulloutallmodulesfromthebackplane
2. Disconnect load on the 24 V output bus and switch the input mains ON.
3. PlugoneofthePS3500modulesinslot1ofthebackplaneandvalidatetheoutputtobe
withinthelimits(fora24Vnominaloutput,23.6Vto24.24V).
Factorydefaultforthemodulesis24V+/-1%.Ifadierentoutputvoltageisrequired(within
the22.5Vto28Vrange),adjustthepotentiometeronthebackplanetoobtainthedesired
output.
4. Repeatstep3,usingthesamemodulepluggedinthebackplaneslot2,3,etc.,and
check the output voltage to be within the limits
5. Turnpowero,reconnecttheloadpluginandtightenallmodulesonthebackplanewith
thexingscrews.
6. Turn power ON. Only the green LED should appear (no alarms). If any alarm is
displayed, check mains voltage, module conguration and adjustment. If problem
remains refer to the troubleshooting section.
Warning
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

Pepperl+Fuchs PS3500-DM Owner's manual

Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI