Johnson Controls YORK BCHO-104G Datasheet

Category
Split-system air conditioners
Type
Datasheet
Ref.: N-27515 0707
Air-Air Heat Pumps models
BCHO-74 to 154G/BLI, BCI, BVI
Technical Information
Johnson Controls Manufacturing España, S.L. is participating in the EUROVENT Certification
Program.
Products are as listed in the EUROVENT Directory of Certified Products, in the program AC1,
AC2, AC3, LCP and FC.
The LCP program covers air condensed water chillers and heat pumps of up to 600 kW.



3
Accessories 26
- Standard accessories 26
Duct electric heaters for BLI-74 to 154 27
- Technical specifications 27
- General dimensions 27
- General characteristics 28
- Dimensions with packing and weights 28
- Installation 28
- Wiring diagrams 29 - 30
Internal electric heaters for BCI-74 to 174 31
- Technical specifications 31
- Assembly and general dimensions 31
- General characteristics 32
- Dimensions with packing and weights 32
- Installation 32
- Wiring diagrams 33 - 34
Internal electric heaters for BVI-74 to 154 35
- Technical spcifications 35
- Assembly and general dimensions 35
- General characteristics 36
- Dimensions with packing and weights 36
- Installation 36
- Wiring diagrams 37 - 38
Octopus plenum 39
- Zone control 40 - 42
Index
General Information 5
- General description 5
- Nomenclature 5
Technical Specifitations 5
- Mechanical specifications 5
- Cooling interconnection 5
- Control panel 5
- Thermostat 6
- Ambient thermostat DPC-1 6
- Physical data 6 - 7
- Limits of use 7
- General dimensions 8 - 11
- Indoor unit diagrams 12
- Orientations of suction and discharge,
outdoor air BCHO 12
- Variant chart 13
- Nominal capacities 14
- Test conditions 14
- Correcting factors 14 - 15
- Nominal flows 15
- Sensible cooling capacities 16 - 18
- Fan services 18 - 21
- Electrical characteristics 22
Control Board 22
Wiring Diagrams 23 - 24
Configuration of switches 25
Page Page
5
General Information
General description
The heat pump of the split system air-air type allows air
conditioning both in summer as well as in winter by inverting
its operating cycle.
It is made up of two units: one to be installed outdoors and
another to be installed indoors.
To operate, they must be interconnected electrically and
frigorifically.
The combination of the BCHO heat pump as the outdoor
unit, with BCI, BLI or BVI as the indoor unit, allows easy
installation due to their limited dimensions and assembly
characteristics.
Nomenclature
equipped with internal protection of the motor. Includes an
electric heater for heating oil in the sump, which makes
start-ups easier and avoids oil being removing from the
compressor.
Coils
Of a large surface, made of grooved copper tubing and
notched aluminium fins.
Fans BCHO
Centrifugal, with direct drive motor. Sufficient pressure avail-
able for the installation of ducts and optional accessories.
Casing BCHO
Made of galvanised steel sheeting, finished with oven-poly-
merised powdered paint, which allows installing outdoors.
Insulated internally so as to avoid condensation of humid-
ity and reduce noise level. These units are equipped with
galvanised trays, with corresponding drains, for collecting
condensation from the coils.
Cooling circuit
Made of welded copper tubing. These units are supplied
with their corresponding optimised refrigerant charge and
having passed the maximum pressure and airtightness tests.
Refrigerant expansion is carried out by means of calibrated
holes and distributors located in both the indoor as well as
outdoor units. The circuit includes: four-way valve, suction
accumulator, high and low pressure switches, and suction
and discharge pressure intakes.
Refrigerant
These units are manufactured with R-407C refrigerant.
Fan (BVI, BCI or BLI indoor units)
Of the centrifugal type, 3 speeds, direct drive and mounted
on shock absorbers.
Complementary heater (indoor units)
Of the exposed wire type to allow fast heat dispersion, avoid-
ing temperature inertia that could affect the components.
Equipped with contactor and thermal protector.
Casing (indoor units)
Made of galvanized aluminium steel sheeting and finished
with oven polymerized powdered paint. Insulated internally
so as to avoid condensation of humidity and reduce noise
level.
Equipped with a galvanised tray, with corresponding drain,
for collecting condensation from the coil.
There is sufficient space inside for fitting the electric heat-
er.
On BLI units, the electric heater is installed externally, in
the duct.
Cooling interconnection
The cooling connection of the units should be made at the
time of installation at the job site. See the cooling connection
table in the Physical Data section.
Control Panel
Accessible directly from outside. Includes: connecting strip,
protectors, electronic board and probes, power supply con-
Manufacturing edition
Power rating:
Cooling / Heating
74G = 7 800 W / 8 000 W
94G = 8 600 W / 8 500 W
104G = 10 800 W / 13 650 W
154G = 14 400 W / 15 200 W
BCHO = Outdoor unit, heat pump
with centrifugal fan.
BCI = Indoor unit, horizontal heat
pump.
BLI = Indoor unit, low level hori-
zontal heat pump.
BVI = Indoor unit, low level vertical
heat pump.
Voltage:
21 = 230.1.50
22 = 230.3.50
38 = 400.3.50
Technical Specifications
Mechanical specifications
Compressor
Vertical Scroll type, mounted on antivibratory supports and
BCHO 104 38 1
6
tactors, operating relay and transformer. Complies with the
European standards in force.
Thermostat
The BCHO units include, as standard equipment, the elec-
tronic DPC-1 thermostat.
For connecting the thermostat to the board, screened 10 x
0.22 mm² communication cable should be used.
Ambient thermostat DPC-1
Programmable digital thermostat with communication
This thermostat was designed to give close control of the
ambient temperature and graphic information regarding
the mode it is currently operating in. This control unit, in
accordance with the differential between the programmed
temperature and the ambient temperature, responds varying
the on/off cycles.
The liquid crystal display (LCD) normally indicates the ambi-
ent temperature, operating mode and whether the system is
in heat or cool.
It allows selecting different set point temperatures for cool and
heat, besides choosing between °C and °F on the display.
Fan operation can be in continuous or automatic mode, off
or in operation along with the compressor. Three speeds
can be selected.
The controls are beneath a cover.
Physical Data
Outdoor units with centrifugal fan
*Flared. **Weld.



        


Model BCHO-74G BCHO-94G BCHO-104G BCHO-154G
Amount 1 1 1 1
Type Scroll Scroll Scroll Scroll
Nominal power kW 2.94 3.2 3.9 5.1
Power supply V.ph.Hz 230.1.50 230.1.50 230/400.3.50 230/400.3.50
Amount 1 1 1 1
Front area m
2
0.32 0.32 0.41 0.51
Tubing diameter 3/8" 3/8" 3/8" 3/8"
Amount 1 1 1 1
Turbine diameter mm 270 270 320 320
Turbine width mm 270 270 240 240
Nominal power kW 0.37 0.37 0.99 0.99
Nominal motor rpm 950 950 950 950
Power supply V.ph.Hz 230.1.50 230.1.50 230.1.50 230.1.50
Cooling connections *3/8" x 5/8" *3/8" x 3/4" *3/8" x 3/4" *3/8" x 7/8"**
Refrigerant charge R-407C Kg 2.45 2.5 2.9 4.1
Dimensions with standard packing mm 1168x802x600 1168x802x600 1218x842x680 1405x931x675
Nett kg 119 122 142 161
Gross kg 126 129 151 172
Fan
motor
Compressor
Approx.
weight
Coil
7
Indoor units
Limits of use
Heat
-20
(1)
Heat DB
27
Cool WB
15
Cool
46
Operating cycleOperating cycle
Voltage limits
Air intake temperature to indoor coil
Air intake temperature to outdoor coil (DB)
Maximum °C
Maximum °C
Minimum °C
Minimum °C
Cool WB
23
Heat
24
Cool
19
Heat DB
10
(2)
Nominal 230 V
Nominal 400 V
Minimum
198
Maximum
254
Minimum
342
Maximum
436
Model BLI-74 BLI-104 BLI-154 BCI-74 BCI-104 BCI-124 BCI-154 BVI-74 BVI-104 BVI-154
Nominal power W 250 250 700 260 475 475 665 475 505 700
Power supply V.ph.Hz 230.1.50
Nominal motor r.p.m. 1 340 1 370 1 350 950 950 950 870 950 950 950
Number of turbines 2 2 2 2 2 2 2 1 1 2
Turbine Ø mm 146 160 190 190 190 190 240 240 240 240
Turbine width mm 220 240 200 190 190 190 240 240 240 240
Amount 1
Front area m
2
0.26 0.29 0.352 0.228 0.279 0.279 0.463 0.377 0.377 0.617
Tubing dia. 3/8"
Tubing, depth x height 3 x 10 4 x 11 4 x 14 3 x 12 4 x 15 4 x 15 3 x 20 2 x 27 3 x 27 3 x 27
kg 42 47 60 50 65 65 88 74 77 113
Height mm 268 299 335 350 350 350 430 1 595 1 595 1 595
Width mm 1 144 1 144 1 100 860 860 860 1 100 820 820 1 155
Depth mm 502 542 750 715 935 935 1 139 490 490 490
Fan
Coil
Approximate weight
Dimensions
Notes: WB = Wet bulb. DB = Dry bulb.
(1) Below -20°C, only the emergency electric heater (optional) remains connected.
(2) The unit can operate during a short period of time at temperatures below 10°C so as to raise the air conditioning to 10°C.
8
General dimensions mm.
BCHO-74G, 94G
BCHO-104G









 



 





































 






 
















 



























 












9
General dimensions mm.
BCHO-154G
BLI-74 to 154
Model A B C D E F G H I J K L M N O P
BLI-74 268 465 21 78 229 5/8" SAE 19 55 17 24 75 75 1 144 147 147 169
BLI-104 299 505 26 104 260 3/4" SAE 19 55 17 24 75 75 1 144 147 147 169
BLI-154 335 750 23 75 300 7/8" Weld 15 15 15 15 72 34 1 100 125 125 235
 











 























  



 













 





























10
General dimensions mm.
BCI-74
BCI-104 and 124
Model A B
BCI-104 3/8" SAE 3/4" SAE
BCI-124 3/8" SAE 7/8" WELD
BCI-154
















































































 










11
General dimensions mm.
BVI-74 and 104
BVI-154
Model A B
BVI-74 3/8" SAE 5/8" SAE
BVI-104 3/8" SAE 3/4" SAE










































12
BCI
BLI
BVI
Indoor unit diagrams
Orientation of suction and discharge, outdoor
air BCHO
Orientation supplied from factory
BCHO-74, 94, 104, 154
Variations to be carried out at job site, BCHO
outdoor unit
Based on the standard unit, the orientation of the air suc-
tion and discharge can be varied until any of the indicated
combinations is achieved.
BCHO-74, 94, 104, 154











































































13
Variant chart
14
Nominal capacities
Test conditions
Correcting factors
Correcting factors for cooling capacities
For flows that differ from the nominal flows of the indoor
coil.
Correction of the real temperature of air intake to the outdoor
coil for flows that differ from the nominal values.
7 800 2 970 8 000 2 470 37
7 800 3 270 8 000 2 770 37
8 600 3 760 8 500 3 270 37
8 600 3 760 8 500 3 270 37
10 250 4 720 12 705 4 660 37
10 780 4 830 13 650 4 690 37
9 760 3 550 10 700 3 170 37
13 600 4 780 14 000 4 815 50
14 400 5 470 15 200 4 370 50
14 400 5 470 15 200 4 370 50
BCHO-104G
Outdoor unit
Indoor unit
Cooling
capacity W
Consumption W
Cooling
capacity W
Consumption W
Indoor fan
available pressure
Pa
Summer
Winter
BCI-74
BLI-74
BCHO-74G
BCI-104
BLI-104
BCHO-154G
BCI-124
BCI-154
BVI-154
BCHO-94G
BLI-104
BCI-104
BVI-104
Winter
DB WB DB WB DB WB DB WB
230 or 400 7.5 meters 35 24 27 19 7 6 20 12
Indoor temp. °C Outdoor temp. °C
Indoor temp. °C
Outdoor temp. °C
Voltage
Length
interconnecting
tubing
Summer
Flow % 70 80 90 100 110 120 130
5 3 1.5 0 -1 -2 -2.5
Correction in °C on real temperature of air going
to the outdoor coil
Flow % 80 90 100 110 120 130
Total capacity 0.960 0.980 1 1.016 1.032 1.046
Sensible capacity 0.945 0.973 1 1.038 1.075 1.118
Comp. absorbed power 0.980 0.990 1 1.009 1.017 1.025
15
Correction of the real temperature of intake air to the outdoor
unit for flows that differ from the nominal values.
Nominal flows
Outdoor units
The cooling and heating capacities of the corresponding
tables are valid for the following nominal flows.
Indoor Units
Correcting factors for the heating capacities
14 10 6 0 -8
23 1.20 1.04 0.96 0.77 0.58
20 1.25 1.10 1.00 0.80 0.69
17 1.30 1.13 1.04 0.83 0.63
Indoor unit intake tem-
perature
°C DB
Outdoor unit air temperature °C WB
Flow % 70 80 90 100 110 120 130
BCHO-74G 2 380
BCHO-94G 2 380
BCHO-104G 3 450
BCHO-154G 4 370
Model
Outdoor fan m³/h
(1) Fan connected in 2nd speed.
BCI-74 1 670 0.46
BLI-74 1 315 0.36
BVI-74 1 975 0.55
BCI-104 2 300 0.64
BLI-104 2 060 0.57
BVI-104 2 430 0.68
BLI-154 2 700 0.75
BVI-154 2 910 0.81
BCI-124 2 300 0.64
BCI-154 (1) 2 910 (1) 0.80
Nominal flow
Model
m
3
/h
m
3
/s
For other flows, apply the correcting factors of the corre-
sponding table.
-2 -1.5 -0.5 0 0.5 1 1.2
Correction in °C on real temperature of air intake
to the outdoor unit
16
Sensible cooling capacities
22 9 360 2 879 3 876 5 370 6 363 2.01
19.5 8 424 4 117 5 113 6 608 7 608 2.10
17 7 800 5 445 6 442 7 800 7 800 2.20
22 8 658 2 636 3 633 5 127 6 124 2.27
19.5 7 800 3 881 4 878 6 372 7 369 2.39
17 7 176 4 860 5 856 7 176 7 176 2.51
22 7 800 2 366 3 363 4 857 5 854 2.63
19.5 7 020 3 613 4 610 6 104 7 020 2.75
17 6 396 4 871 5 867 6 396 6 396 2.87
22 9 360 2 855 3 919 5 514 6 580 2.01
19.5 8 424 4 180 5 244 6 840 7 906 2.10
17 7 800 5 596 6 660 7 800 7 800 2.20
22 8 658 2 615 3 679 5 275 6 339 2.27
19.5 7 800 3 948 5 012 6 608 7 671 2.39
17 7 176 4 791 5 855 7 176 7 176 2.51
22 7 800 2 349 3 413 5 008 6 072 2.63
19.5 7 020 3 683 4 747 6 343 7 020 2.75
17 6 396 5 028 6 092 6 396 6 396 2.87
22 10 320 3 287 4 158 5 463 6 335 2.60
19.5 9 288 4 350 5 220 6 526 7 398 2.72
17 8 600 5 519 6 390 7 695 8 567 2.85
22 9 546 3 003 3 873 5 179 6 049 2.94
19.5 8 600 4 076 4 947 6 252 7 122 3.10
17 7 912 5 037 5 907 7 213 7 912 3.25
22 8 600 2 689 3 559 4 865 5 735 3.40
19.5 7 740 3 766 4 636 5 942 6 812 3.56
17 7 052 4 856 5 727 7 032 7 052 3.71
22 10 320 3 054 4 537 6 850 8 370 2.60
19.5 9 288 4 963 6 481 8 758 9 288 2.72
17 8 600 6 966 8 484 8 600 8 600 2.85
22 9 546 2 803 4 321 6 598 8 117 2.94
19.5 8 600 4 717 6 236 8 513 8 600 3.10
17 7 912 6 344 7 862 7 912 7 912 3.25
22 8 600 2 522 4 040 6 317 7 836 3.40
19.5 7 740 4 437 5 955 7 740 7 740 3.56
17 7 052 6 363 7 052 7 052 7 052 3.71
BCHO-74G
BLI-74
BCHO-74G
BCI-74
Model
Dry outdoor air
temperature
°C (DB)
Humid
intake air tem-
perature
°C (WB)
Dry intake air temperature to coil °C (DB)
Sensible capacity (W)
Compressor
absorbed
power
24
22 27 29
kW
WWWWW
25
35
45
25
35
45
25
35
45
25
35
45
Total
capacity
BCHO-94G
BLI-104
BCHO-94G
BCI-104
17
Sensible cooling capacities
22 12 300 3 797 5 073 6 988 8 266 3.55
19.5 11 070 5 380 6 656 8 570 9 849 3.72
17 10 250 7 083 8 359 10 250 10 250 3.89
22 11 378 3 476 4 752 6 666 7 943 4.02
19.5 10 250 5 069 6 345 8 259 9 535 4.23
17 9 430 6 389 7 665 9 430 9 430 4.44
22 10 250 3 119 4 395 6 310 7 586 4.65
19.5 9 225 4 715 5 991 7 905 9 181 4.86
17 8 405 6 325 7 601 8 405 8 405 5.08
22 12 936 3 940 5 425 7 653 9 141 3.55
19.5 11 642 5 792 7 277 9 505 10 993 3.72
17 10 780 7 767 9 252 10 780 10 780 3.89
22 11 966 3 610 5 095 7 323 8 808 4.02
19.5 10 780 5 471 6 956 9 184 10 669 4.23
17 9 918 7 106 8 592 9 918 9 918 4.44
22 10 780 3 242 4 728 6 956 8 441 4.65
19.5 9 702 5 106 6 591 8 819 9 702 4.86
17 8 840 6 984 8 469 8 840 8 840 5.08
22 11 712 3 536 4 981 7 150 8 598 2.83
19.5 10 541 5 343 6 789 8 958 10 406 2.97
17 9 760 7 262 8 707 9 760 9 760 3.10
22 10 834 3 241 4 681 6 855 8 301 3.20
19.5 9 760 5 057 6 502 8 671 9 760 3.32
17 8 979 6 365 7 810 8 979 8 979 3.54
22 9 760 2 913 4 358 6 527 7 973 3.71
19.5 8 784 4 730 6 175 8 344 8 784 3.88
17 8 003 6 560 8 003 8 003 8 003 4.04
22 17 280 5 150 7 536 11 115 13 504 3.85
19.5 15 552 8 144 10 530 14 109 15 552 4.03
17 14 400 11 299 13 685 14 400 14 400 4.21
22 15 984 4 724 7 110 10 689 13 075 4.35
19.5 14 400 7 729 10 115 13 694 14 400 4.58
17 13 248 9 749 12 135 13 248 13 248 4.81
22 14 400 4 248 6 635 10 214 12 600 5.04
19.5 12 960 7 255 9 641 12 960 12 960 5.27
17 11 808 10 280 11 808 11 808 11 808 5.50
Model
Dry
outdoor air
temperature
°C (DB)
Humid
intake air tem-
perature
°C (WB)
Dry intake air temperature to coil °C (DB)
Sensible capacity (W)
Compressor
absorbed
power
24
22 27 29
kW
WWWWW
25
35
45
25
35
45
25
35
45
25
35
45
Total
capacity
BCHO-104G
BVI-104
BCHO-154G
BCI-154
BVI-154
BCHO-104G
BLI-104
BCHO-104G
BCI-104
18
Sensible cooling capacities
Fan services, indoor units
22 16 320 5 113 6 642 8 935 10 466 4.20
19.5 14 688 6 996 8 525 10 818 12 350 4.50
17 13 600 9 044 10 572 12 866 13 600 4.70
22 15 096 4 676 6 205 8 498 10 027 4.90
19.5 13 600 6 574 8 103 10 369 11 925 5.08
17 12 512 8 174 9 702 11 996 12 512 5.70
22 13 600 4 192 5 721 8 014 9 543 6.30
19.5 12 240 6 095 7 624 9 917 11 446 6.40
17 11 152 8 018 9 547 11 152 11 152 6.60
BCHO-154G
BCI-124
Model
Dry outdoor air
temperature
°C (DB)
Humid intake
air temperature
°C (WB)
Dry intake air temperature to coil °C (DB)
Sensible capacity (W)
Compressor
absorbed
power
24
22 27 29
kW
WWWWW
25
35
45
Total
capacity
0 1 660 0.46 226
20 1 350 0.37 211
40 1 220 0.34 197
60 990 0.27 181
0 1 285 0.35 191
20 1 170 0.32 177
40 1 045 0.29 164
60 885 0.24 152
0 922 0.25 144
20 849 0.23 135
40 723 0.20 126
60 652 0.18 120
0 2 188 0.61 407
20 2 100 0.58 390
38 2 044 0.57 372
60 1 913 0.53 352
80 1 787 0.49 330
100 1 621 0.45 306
0 1 636 0.45 329
20 1 607 0.44 316
30 1 577 0.43 307
60 1 485 0.41 280
80 1 370 0.38 248
100 1 263 0.35 228
0 1 272 0.353 280
20 1 261 0.35 272
30 1 250 0.34 261
60 1 216 0.33 238
80 1 123 0.31 220
100 1 022 0.28 200
Fan speed
Model
Static pressure
available (1)
Pa
Air flow
Absorbed
power
W
High
Medium
Low
High
Medium
Low
BLI-74
BLI-104
m
3
/h
m
3
/s
Notes: Factory set to maximum speed. (1) Calculated with wet coil.
19
Fan services, indoor units
0 2 880 0.80 700
50 2 720 0.75 650
80 2 550 0.71 620
100 2 400 0.66 595
0 2 450 0.68 565
50 2 340 0.65 525
80 2 230 0.62 495
100 2 100 0.58 465
0 2 190 0.61 510
50 2 100 0.58 485
80 2 020 0.56 455
100 1 920 0.53 425
0 1 800 0.50 265
25 1 670 0.46 260
40 1 600 0.44 255
80 1 525 0.42 250
100 1 390 0.39 235
0 1 250 0.35 135
40 1 120 0.31 125
60 1 020 0.28 120
0 990 0.27 110
40 800 0.22 100
0 2 470 0.69 505
40 2 300 0.64 475
80 2 100 0.58 440
100 2 010 0.56 435
0 2 100 0.58 410
40 1 970 0.55 385
80 1 840 0.51 365
100 1 750 0.49 350
0 1 800 0.50 345
40 1 700 0.47 325
60 1 620 0.45 310
0 2 470 0.69 505
50 2 250 0.62 475
80 2 100 0.58 440
100 2 010 0.56 435
0 2 100 0.58 410
50 1 930 0.54 385
80 1 840 0.51 365
100 1 750 0.49 350
Fan speed
Model
Static
pressure
available (1) Pa
Air flow
Absorbed
power
W
High
Medium
Low
High
Medium
Low
BLI-154
BCI-74
m
3
/h
m
3
/s
BCI-104
BCI-124
Low
Medium
High
Medium
High
Notes: Factory set to maximum speed. (1) Calculated with wet coil.
20
Fan services, indoor units
0 4 380 1.22 1 090
40 4 240 1.18 1 020
80 4 060 1.13 950
100 3 960 1.10 900
0 3 040 0.84 705
40 2 950 0.82 675
80 2 770 0.77 635
100 2 670 0.74 600
0 2 115 0.59 590
40 1 910 0.53 570
0 2 010 0.56 440
20 1 990 0.55 425
40 1 975 0.55 415
60 1 960 0.54 400
80 1 940 0.54 395
100 1 925 0.53 385
120 1 905 0.53 375
0 1 465 0.41 340
20 1 395 0.39 337
40 1 380 0.38 332
60 1 370 0.38 325
80 1 350 0.38 320
100 1 320 0.37 310
120 1 300 0.36 300
0 2 510 0.7 490
20 2 475 0.69 475
40 2 430 0.68 455
60 2 385 0.66 445
80 2 365 0.66 435
100 2 320 0.64 425
120 2 275 0.63 415
140 2 215 0.62 402
0 1 990 0.55 425
20 1 975 0.55 415
40 1 960 0.54 400
60 1 940 0.54 400
80 1 925 0.53 395
100 1 905 0.53 375
120 1 835 0.51 362
140 1 780 0.49 360
0 3 315 0.92 690
20 3 310 0.92 670
40 3 255 0.90 650
60 3 190 0.89 630
80 2 910 0.86 610
100 2 750 0.81 580
0 2 255 0.63 580
20 2 150 0.56 570
40 2 080 0.55 555
Model
BCI-154
Low
Absorbed
power
W
Static pressure
available
(1) Pa
Air flow
Fan
speed
m
3
/h
BVI-104
BVI-154
Low
High
Medium
BVI-74
Low
High
Low
(3
rd
)
High
(2
nd
)
High
m
3
/s
Notes: Factory set to maximum speed. (1) Calculated with wet coil.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44