Installation
The accumulator tank should stand on a solid surface and be leveled with assistance from the setscrews
underneath the tank. The tank models that come without setscrews can be leveled with assistance of a
shim. This must be done before the tank is connected to the pipes and lled with water. Connections not
in use must be plugged appropriately. During water lling, condensed water may emerge on the outside
of the tank. This will result in water underneath the tank, on the oor. This will cease when the tank is
heated. There must be a oor drain in the same room.
Commissioning
Start by lling the tank, then pressurize it. Continue to ll the radiator system (the enclosed water). The
working pressure may not exceed 3 bar (gauge), a safety valve with a releasing pressure of 3 bar must
always be installed.
Maintenance
Check the safety valve annually by manually opening and closing the valve handle and making sure that
water is released. Check annually all connections for eventual leakage (also peripheral installations, i.e. a
heat pump, etc).
Electrical Installation
The electrical installation must be performed by an authorised installer and follow applicable norms
and regulations.
When selecting electrical equipment, it must be selected with approved materials and enclosure
class.
Disassembling the product
When disassembling the product, applicable laws and regulations must be observed. Contact your
installer for more information.
WT-V 100 200 300 500 750 1000
Height (mm) 1558 1153 1564 1754 1809 1913
Dimensions (mm)
ø380
601 x 600 635 x 600 726 x 695
ø960 ø1090
Dimensions
WT-V 100 200 300 500 750 1000
Storage volume V 101,8 litres 204,4 litres 292,7 litres 472,2 litres 721,1 litres 970,9 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 40 kg 68 kg 91 kg 113 kg 120 kg 165 kg
Standing loss S 60,3 W 64,9 W 78,3 W 85,6 W 126,8 W 136,5 W
Energy eciency class C
Technical data
© Danfoss A/S 2017-10 VIBNE302 5
Connection WT-V 100
1 Venting, (1/8” int.)
2 Connections (DN25) (x4) int.
3 Sensor connection, ø9 int
4 Drain tap, DN15 int.
2
31
2
2
2
100
100
40
Radiator in
Radiator out
HP in
HP out
4
0
85
1 558
1 540
125
502
Required ceiling height for tilting: min. 1595 mm
Dimensions
Technical data
WT-V 100
Height (mm) 1558
Diameter (ømm) 380
WT-V 100
Storage volume V 101,8 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 40 kg
Standing loss S 60,3 W
Energy eciency class C
ø380
6 VIBNE302 © Danfoss A/S 2017-10
Required ceiling height for tilting: min. 1280mm
Connection WT-V 200
1 Expansion/Venting, DN25 int.
2 Connections (4x), DN32 int.
3 Temperature sensor (2x)
4 Drainage valve, DN15
5 Temperature sensor pipe, ø7 int.
6 Diuser
7 Connection DN50
600
601
1153
1126
147
227
377
777
0
1
4
7
5
6
2
3
Dimensions
WT-V 200
Height (mm) 1153
Dimensions (mm) 601 x 600
Technical data
WT-V 200
Storage volume V 204,4 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 68 kg
Standing loss S 64,9 W
Energy eciency class C
3
© Danfoss A/S 2017-10 VIBNE302 7
Required ceiling height for tilting: min. 1665mm
Connection WT-V 300
1 Expansion/Venting, DN25
2 Connections (4x), DN32
3 Temperature sensor conn. DN20
4 Drainage valve , DN15
5 Temperature sensor pipe (5x), ø7 int.
6 Immersion heater conn. DN50
7 Diuser, DN32
8 Temperature sensor (2x)
600
635
0
227
527
147
1 536
1 082
1 564
1
4
5
6
2
3
7
8
Dimensions
Technical data
WT-V 300
Height (mm) 1564
Dimensions (mm) 635 x 600
WT-V 300
Storage volume V 292,7 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 91 kg
Standing loss S 78,3 W
Energy eciency class C
8 VIBNE302 © Danfoss A/S 2017-10
Connection WT-V 500
1 Expansion/Venting, DN25 ext.
2 Connections (6x), DN50 int.
3 Temperature sensor conn. DN20
4 Immersion heater conn. DN50 int.
Required ceiling height for tilting: min. 1850mm
1754
1710
1492
367
842
192
0
2
3
1
2
4
695
696
726
Dimensions
Technical data
WT-V 500
Height (mm) 1754
Dimensions (mm) 726 x 695
WT-V 500
Storage volume V 472,2 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 113 kg
Standing loss S 85,6 W
Energy eciency class C
© Danfoss A/S 2017-10 VIBNE302 9
Connection WT-V 750
1 Expansion/Venting, DN32 ext.
2 Connections (4x), DN50
3 Temperature sensor conn. DN20
4 Immersion heater conn. DN50 int.
5 Drain tap/Expansion, DN20
Required ceiling height for tilting: min. 2005mm
1 809
1 775
1 515
1 410
1 300
1015
665
420
295
185
1
2
2
2
4
3
3
5
ø960
ø780
0
Dimensions
Technical data
WT-V 750
Height (mm) 1809
Diameter (ømm) 960
WT-V 750
Storage volume V 721,1 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 120 kg
Standing loss S 126,8 W
Energy eciency class C
10 VIBNE302 © Danfoss A/S 2017-10
Connection WT-V 1000
1 Expansion/Venting, DN25 ext.
2 Connections (4x), DN50
3 Temperature sensor conn. DN20
4 Immersion heater conn. (2x), DN50
Required ceiling height for tilting: min. 2125mm
1 913
1 560
1 656
1 380
835
585
455
340
235
1
2
2
4
4
3
3
3
ø1090
ø890
0
Dimensions
Technical data
WT-V 1000
Height (mm) 1913
Diameter (ømm) 1090
WT-V 1000
Storage volume V 970,9 litres
Test pressure 4,3 bar
Working pressure 3 bar
Max. temperature 100 °C
Weight 165 kg
Standing loss S 136,5 W
Energy eciency class C
© Danfoss A/S 2017-10 VIBNE302 11
12 VIBNE302 © Danfoss A/S 2017-10
Danfoss Heat Pumps
Box 950
SE-671 29 ARVIKA
Phone +46 570 81300
E-mail: dhpinfo@danfoss.com
Internet: www.heating.danfoss.com, www.thermia.com
Danfoss assumes no responsibility whatsoever for any errors occurring in catalogues, brochures or other printed material. Danfoss reserves the right to make changes to (the design of) its products
with no prior warning. The same applies to products already on order provided that the previously agreed specications remain unchanged. All trademarks in this material are the property of the
respective company. Danfoss and the Danfoss logotype are trademarks which belong to Danfoss A/S. All rights reserved.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Danfoss WT-V Accumulator tanks Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI