Dwyer Series EDA User manual

Type
User manual

Dwyer Series EDA is a versatile electronic pressure controller known for its accuracy, stability, and durability. It offers a wide range of pressure measurement capabilities, from vacuum levels to high pressures up to 6,000 psi. The device is equipped with a user-friendly interface, featuring a backlit LCD display and intuitive controls, making it easy to set up and operate. With its compact design and weatherproof construction, the Dwyer Series EDA is suitable for both indoor and outdoor applications, ensuring reliable pressure monitoring and control in various industrial environments.

Dwyer Series EDA is a versatile electronic pressure controller known for its accuracy, stability, and durability. It offers a wide range of pressure measurement capabilities, from vacuum levels to high pressures up to 6,000 psi. The device is equipped with a user-friendly interface, featuring a backlit LCD display and intuitive controls, making it easy to set up and operate. With its compact design and weatherproof construction, the Dwyer Series EDA is suitable for both indoor and outdoor applications, ensuring reliable pressure monitoring and control in various industrial environments.

Series EDA Electronic Pressure Controller
Specications - Installation and Operating Instructions
Bulletin IN-EDAW-1
By Dwyer
MERCOID
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
A DIVISION OF
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000
Fax: 219/872-9057
dwyer-inst.com
TABLE OF CONTENTS
Dimensions.................................................... 1
Specications .................................................. 2
ModelChart ................................................... 3
Display ....................................................... 3
InstallationInstructions..........................................4-5
UnpackingandMounting........................................ 4
ElectricalConnections .......................................... 5
OperatingInstructions .........................................6-18
FrontPanelFunctions .......................................... 6
SetPoints&Alarms ...........................................7-8
Alternation(Lead/Lag)Operation ................................. 8
ProgrammingChart ..........................................9-11
MainMenuSelections ......................................... 12
MenusandValues ..........................................12-18
SecurityMenu .............................................. 12
OperationMenu ............................................ 13
OutputMenu .............................................14-15
DisplayMenu .............................................. 16
AdvancedMenu ............................................ 16
TestMenu ................................................. 17
FailsafeMenu .............................................. 17
DiagnosticErrorMessages ...................................... 18
WarrantyInformation ........................................... 18
DIMENSIONS
3-3/32˝
[78.58]
1 [25.40]
1/2 FEMALE
NPT CONDUIT
ENTRY
3-1/2 [88.90]
3X 1/8
[3.18]
2X 5/16
[7.93]
1-59/64 [50.00]
27/32 [21.43]
Ø5
[127]
Ø4-15/32
[115.90]
9/32 [7.14]
1/4 MALE NPT
WITH 3/4 [19.05]
WRENCHING HEX
1-5/8
[40.88]
1
SPECIFICATIONS
Service:Compatibleliquidsandgases.
Wetted Materials:316LSS.
Housing:Polycarbonate.
Accuracy:±1%ofF.S.includinglinearity,hysteresis,andrepeatability(indicator
andtransmitter).
Stability:<±2%ofF.S.peryear.
Pressure Limits:Rangesupto6,000psi:1.5xrange;8,000psirange:10,000psi.
Temperature Limits: Ambient:20to140°F(-6.6to60°C);Process:0to176°F(-18
to80°C).
Compensated Temperature Limits:32to122°F(0to50°C).
Thermal Effect:±0.05%ofF.S./°F.
Process Connection:1/4˝NPTmale,1/4˝BSPTmale,or7/16”SAE.
Display:4-digitbacklitLCD(Digits:0.60˝Hx0.33”W).
Display Update: 600ms(dampeningsetto1).
Power Requirements:12to28VDC()/AC(~)50/60Hz.(Canworkat8VDC
()for45seconds).ForT5option:14to30VDC()/AC(~)50/60Hz.
Power Consumption: 2.5watts.
Electrical Connections: Removableterminalblockswithtwo1/2˝femaleNPS
conduitconnections.
Enclosure Rating:Weatherprooftype4XIP65(IP65notevaluatedbyUL).
Warm Up Time:<10seconds.
Mounting Orientation:Anyposition.
Weight:1.18lbs(535g).
Installation Category:II(transientover-voltage).
Pollution Degree: 2.
Altitude Limit: 6560ft(2000m)max.
Environment:Intendedforindoorandoutdooruse.
Humidity:0to95%RHupto104°F(40°C)non-condensing,10to50%at140°F
(60°C)non-condensing.
SWITCH SPECIFICATIONS
Switch Type:2SPDTrelays.
Electrical Rating: 5A@120/240VAC(~)50/60Hz,1A@28VDC().
Repeatability:±1%ofFS(switchingonly).
Set Points:Adjustable0-100%ofFS.
Switch Indication:ExternalLEDforeachrelayonthefrontpanel.
Switch Reset:Manualorautomatic.
TRANSMITTER SPECIFICATIONS
Output Signal:4–20mA,1-6VDC(),1-5VDC(),0-5VDC(),or0-10
VDC()(directorreverseoutputselection).
Minimum Excitation:14VDC().
Zero and Span Adjustments:Menuscalablewithintherange.
2
MODEL CHART
Example EDA W N1 E1 01 T0 NIST EDAW-N1E1-01T0-NIST
Series EDA Electronicpressurecontroller
Housing W Weatherproof
Process Connection N1 1/4˝MaleNPT
Conduit Connection E1 Two1/2˝NPT
Range 01
02
03
04
05
06
07
08
09
10
010-30INHGVAC
020-20PSIG
030-60PSIG
040-100PSIG
050-150PSIG
060-300PSIG
070-600PSIG
080-1000PSIG
090-1500PSIG
100-3000PSIG
Transmitter
Output
T0
T1
T2
T3
T4
T5
None
4to20mA
1to5VDC
0to5VDC
1to6VDC
0to10VDC
Options AT
NIST
P
23444
StainlessSteelTag
NISTcerticate
1/2NPSMConduitPLug
Oxygencleaning
Display
TheEDAhastwodisplays:alowerlargerdisplayandasmallerupperdisplay.TheHomeDisplayisthenormaldisplay
whilethecontrolisinoperationiftherearenoerrorsorfunctionsactive.TheHomedisplaywillindicatetheprocess
variableatthecurrentconditionwiththelowerdisplayandtheselectedpressureunitsfortheprocessvariablewith
theupperdisplay.Whenprogrammingtheunitbothdisplaysarealsoused.TheProgrammingChartinthisinstruction
manualindicateswhatbothdisplaysshowwhileprogrammingtheunit.Forprogrammingdescriptionsinthisinstruc-
tionmanualtheformatusedis“lowerdisplay–upperdisplay”.ForexampleCtrl–1SPshowsthatCtrlwouldbeinthe
lowerdisplayand1SPwouldbeintheupperdisplay.
WhentheuserpressestheEkeytoeditanitem’svaluetheupperdisplaywillash“EDIT”andthelowerdisplaywill
blink.WhentheuserpressestheEkeytothensavetheedittothevaluetheupperdisplaywillash“SAVE”andthe
lowerdisplaywillstopblinking.
3
4
1.0 INSTALLATION
1.1 UNPACKING
RemovetheEDAfromtheshippingcartonandinspectfordamage.Ifdamageisfound,notifythecarrierimmediately.
1.2 MOUNTING
TheEDAcanbepipe,panel,orsurfacemounted.Forpipemountingthreadtheunitintoamatingfemalettingonthe
pipe.Useawrenchonthe3/4˝hexatthebaseofthehousingtotightentheunittothematingtting.Donotthreadthe
unitinbyforceonthehousing.Forpanelmounting,inserttheunitintothepanelopeningandsecureinplacewiththe
machinescrewsandadaptersprovidedwiththeunitasshowninFigure1below.Maximumpanelthicknessis1/8”(3.5
mm)withsuppliedscrews.Forsurfacemounting,panelmounttheunitintotheA-EDA-BRKmountingbracket(Seethe
Dwyercatalogorwebsitefororderingdetails)alsoshowninFigure1.Theunitcanalsobedirectlysurfacemounted,
asshowninFigure2,withtheproperpanelcutoutfortheconduitentrances.Supportthepressureconnectionhexwith
awrenchifattachingattingtotheunitinthecaseofpanelorushmountingsothatthepressureconnectiondoesnot
twist.Useasmallamountofplumberstapeorothersuitablesealantstopreventleaksaroundtting.
Figure 1: Panel Mounting and Mounting in A-EDA-BRK Bracket
Figure 2: Surface Mounting
EDAW
A-EDA-BRK
MOUNTING BRACKET
2X 6-20 X
2-1/4 SCREWS
3X 6-19 X
3/8 SCREWS
3X MOUNTING
LUG
3X Ø5/32 [3.97]
3-3/32
[78.58]
2X R 5/8
[15.88]
3X 6-19 X 3/8
SCREWS
1-5/8
[41.28]
3-1/2 [88.90]
5
1.3 ELECTRICAL CONNECTIONS
Note: Installationmustbemadeinaccordancewithlocalcodesandregulations.
Electricalconnectionsaremadetotheremovableterminalblocksinsidetheenclosure.Removethetopbackcover,
donotremovebottomcover.Feedstrippedandtinnedleadsthroughtheconduitopeningandconnectthemasshown
inFigure3.TheEDAprovidestwo1/2˝NPTfemaleportsforconduitconnection.Theconduitconnectionsmustbe
madesuchthatcondensationisnotallowedtoenterthesensorhousing.Ifnecessaryinstallaconduitbreatherdrain
inaseparateconduitbodytopreventbuildupofmoisture.Itisrecommendedthatshieldedtwistedpairwirebeused
forthetransmitteroutputoptionifthepotentialexistsforinterferencefromexternalnoisesources.Whenreplacingtop
backcovertightenscrewsto2±.25in.lbs.
LoadscanbeconnectedtoconnectorsCONN7andCONN8terminalblocksbasedontheControlsettings:
•Forsinglesetpointmode(CtrL-1SP),connecttheLoadtoSP1relay(CONN7).
•Fortwosetpointsmode(CtrL-2SP),connecttheLoad1toSP1relay(CONN7)and
Load2toSP2relay(CONN8).
•Forsinglesetpointandalarmmode(CtrL-SPAL),connecttheLoad1toSP1relay
(CONN7)andLoad2toALARMrelay(CONN8).
Wiring
Anexternalswitchorcircuitbreakershouldbeaddedtoduringtheinstallationasadisconnectingdevice.Theswitch
orcircuitbreakermustmeettherequirementsofIEC60947-1andIEC60947-3,shalldisconnectallcurrentcarrying
conductors,andshallnotinterrupttheprotectiveearthground.Thedisconnectingswitchorcircuitbreakermustbe
markedorlabeledwiththesymbols“I”foronand“O”foroff,perIEC60417-5007&IEC60417-5008andshallbe
markedas“DisconnectingDevice”.DonotpositionthePLSinaspacewhereitisdifculttooperatethedisconnecting
devicethatprovidespower.300V@90°C18AWG/0.75mm2wiringwithPVCorequivalentinsulationwith94-V0or
FV-0ammabilityratingisrecommendedfortheswitchoutputsandpower.Terminalblocksratedfor16-22solidor
strandedcopperconductor.6lbinissuggestedtighteningtorque.
Figure 3: Wiring
Anexternalpowersupplyof12-28VDC/
AC with minimum current capability
of 200 mA must be used to power the
unit. The power supply connection is
notpolaritysensitivesothepositive and
negative connections may be made to
eitherterminalofCONN9terminalblock.
For voltage output option, connect the
voltage receiver (-) to terminal 1 and
voltage receiver (+) to terminal 2 of the
CONN10 terminal block. For current
outputoption,connectthecurrentreceiver
(-) to terminal 3 and current receiver
(+) to terminal 4 of CONN10 terminal
block. DO NOT APPLY EXTERNAL
POWER TO CONN10 TERMINALS -
PERMANENTDAMAGENOTCOVERED
BYWARRANTYWILLRESULT.
Asapermanentlyinstalledpieceofequipment,apowerdisconnectswitch,circuitbreaker,orother
approveddisconnectdevicemustbeinstalledincloseproximitytotheinstalledboardandwithin
easyreachoftheoperator.Thisdisconnectdevicemustincludealabelindicatingitsfunctionasamainsdisconnect.
Acircuitbreakerorfusedeviceisrecommended(seeFigure3).
SP1
RELAY
5A 250 VAC FOR LOADS USING 120/240 VAC POWER
1A 32 VDC FOR LOADS USING 30 VDC POWER
375 mA 250 VAC
LINE
INPUT
12 TO 30 VDC/AC
POWER
SP2 OR ALARM
RELAY
Explanation of Symbols:
Symbol Publication Description
IEC50417-5031 Directcurrent
IEC50417-5032 Alternatingcurrent
IEC50417-5019 Protectiveconductorterminal
IEC50417-5007 On(supply)
IEC50417-5008 Off(supply)
~
ELECTRIC SHOCK HAZARD. DISCONNECT POWER BEFORE MAKING ELECTRICAL
CONNECTIONS.Failuretodosowillresultininjuryordeath.
DANGER
TomaintainType4Xratingofthe enclosure,1/2NPTconduitttingsmust haveaULType4X
outdoorrating.
NOTICE
EQUIPMENT DAMAGE.DonotallowwiretotouchorpressonPCBAcomponentswhenshing
wirethroughtheconduitconnection.Failuretodosomayresultindamagetothecircuitry.
CAUTION
EQUIPMENT DAMAGE.Donotexceedthespeciedsupplyvoltagerating.Failuretodosomay
resultinpermanentequipmentdamage.
CAUTION
NOTICE
6
Key Functions
Home Position Function Main Menu Function Item Function
SP/AL
Sequencesthedisplay
throughSETPOINTand
ALARMsettings
Returntohomeposition Returntohomeposition
MENU
Allowsaccesstomenus Returntohomeposition Returntopreviousmenu
UP
ARROW
Sequencesthroughmenus Incrementsavalue
DOWN
ARROW
Sequencesthroughmenus Incrementsavalue
ENTER
Displaysfullscalerange
ofunit
Enterintoitems
Changesavalueorsetting.
PressEnteranddisplay
willblink.AdjustwithUP
orDOWNarrows.Press
ENTERtostore.Display
willstopblinking.
RESET
ClearsorresetsanAlarm
(alarmsetformanual
reset)
Peak/Valleyresetsdisplay
topresentvalue.
2. OPERATING INSTRUCTIONS
2.1 FRONT PANEL & KEY FUNCTIONS
Figure 4: Front Panel Functions
7
2.2 SET POINTS & ALARMS
Setting Set Points and Alarms
Set Point Adjustment
Adjustingthesetpointsisquickandsimple.Insteadofsettingasetpointanddeadband,simplyadjustSP1H,Set
Point1High,andSP2H,SetPoint2High,forthedesiredrelayturnonpoint,andthenadjustSP1L,SetPoint1Low,
andSP2L,SetPoint2Low,forthedesiredrelayturnoffpoint.
Intheabovegraph,aninstrumentwitha100psirangewouldhavetheSP1relayturnONat80psiandOFFat40psi.
SP1HsetstherelayturnONpoint,andSP1LsetstherelayturnOFFpoint.
The hot key provides direct access to the Set Point and
Alarm settings.
The Set Point and
Alarm settings that are displayed are based upon the Control (CtrL) menu item.
8
Relay Action
Therelaysoutputsnormallyfunctioninthedirectactingmode,whichmeanstherelaysturnONwithanincreasein
pressure.SP1andSP2maybeconguredtoactasreverseactingrelays(refertotheCtrLmenuitem).Whensetfor
reverseacting,SP1HandSP2HsettherelayturnOFFpoint,andSP1LandSP2LsettherelayturnONpoint.The
abovegraphdemonstratesdirectandreverseactiononprocess(pressure)change.
Alternating (Lead/Lag) Operation
TheEDAisdesignedtoeasilyoperateapairofpumpsinanalternatingoperationtominimizepumpwear.Theunithas
programmableonandoffsetpointsforpumponeandtwo.Ifthelead/lagfeatureisturnedoffthentherelaysremain
attachedtotheircorrespondingsetpoints,SP1HandSP1Lcontrolrelay1(pump1)andSP2HandSP2Lcontrolrelay
2(pump2).Thereisnoalternatingfunction.
Iflead/lagfeatureisturnedonthentherelayswillalternatewithsetpointsSP1HandSP1LtoSP2HandSP2Lwith
everycycleofsetpoints.TheLastrelayturnedoffwillbelastrelayturnedonwiththenextcycle.Ontherstcycle
onincreaseofpressure,assumingdirectacting,theSP1relay(pump1)willcomeonandthenonfurtherincreaseof
pressuretheSP2relay(pump2)willcomeon.OnthesubsequentdecreaseofpressuretheSP2relay(pump2)will
comeoffandthentheSP1relay(pump1)willcomeoff.Whenpressureincreasesonthenextcycletherelayused
onthelastcycleforSP2willnowbeusedforSP1,sothatSP1nowcontrolspump2andSP2nowcontrolspump1.
EvenifSP2isnotusedonthepressurecycletherelaysstillalternateonnextcycle.
9
2.3 PROGRAMMING CHART
MENU MAP
HOME MAIN MENUS
ITEMS SETTINGS
10
HOME
MAIN MENUS ITEMS SETTINGS
CONTROL MODE
SELECTION
ITEMS PRESENT
WHEN “CtrL” SET
TO “1SP”, “2SP”
OR “SPAL”
ITEMS PRESENT
WHEN “CtrL” SET
TO “2SP”
ITEMS PRESENT
WHEN “CtrL” SET
TO “SPAL”
11
HOME
SEE PAGE 17.
MAIN MENUS ITEMS SETTINGS
12
2.4 MAIN MENU SELECTIONS
Menu Selections
PresstheMENUbuttontostartthemenusothattheupperrightdisplaysreadsMENU.Pressthe▼keytoadvance
tothenextmenuitem.Youcanpressthe▲keytogobacktothepreviousmenu.PresstheEkeytoenteramenu.
SECr SecurityMenu
Lockoutaccesstosetpointandalarmsettings,orlockoutaccesstoallsettings.
OPEr OperationMenu
Selectpressureunits,zerothedisplay,andturnthebacklightonoroff.
Out OutputMenu
Selectrelaymodeofoperation,alternatingfunction,timedelay,andlampindication.
diS DisplayMenu
 Monitorandadjustdisplayrelatedsettings:Peak,ValleyandDampening.
AdU AdvancedFunctionsMenu
 Modifyadvancedfunctionparameters:transmitteroutputscaling,directorreverseoutputsetting,
calibration,orrestoringfactorydefaultcalibration.
tESt TestMenu
 Simulateinputovertherangewithoutpressuretotestswitchandtransmitteroutputfunction.
FAIL FailsafeMenu
 Settherelayandtransmitteroutputstocertainpresetvalueswhenfailsafeconditionsoccur.Errorcodes
willshowonthedisplayindicatingtheproblem.Userchoosesifrelayisde-energized,energized,orno
actiontaken.Withtransmitteroption,userchoosesanoutputof3.6mA,22mA,ornoactiontaken.
Menus and Values
SECr SecurityMenu
SECr Whenthesecurityitemisselected,thepresentsecuritylevelisdisplayedintheupperright hand
display.Tochangethesecuritylevel,adjustthenumberdisplayedtothepasswordvalueinthe
PasswordTable,shownbelow,bypressingthe▲or▼keyandthenpressingtheEkeyatthedesired
securitylevel.
Thepasswordvaluesshowninthetablecannotbealtered,soretainacopyofthesepagesforfuturereference.
Security Level
Displayed Access
Password
Value to Enter
1
2
3
4
Allmenusaccess
MenuAccess
SP/ALLocked
SP/ALAccess
MenusLocked
Allsettingslocked
10
70
90
111
13
OPEr OperationMenu
Unit PressureUnits
 WiththedisplayreadingUnit-PSI,presstheEkey.Theupperdisplaywillblink.Pressthe▼keyto
changeunitthenpressEkeytosavethenewunit.
PSI Poundspersquareinch
FS %offullscale
OZIN Ouncespersquareinch
CMWC Centimetersofwatercolumn
MPA Megapascals
BAR Bar
MBAR Millibar
KPA Kilopascals
FTWC Feetofwatercolumn
KGCM Kilogramspersquarecentimeter
MMHG Millimetersofmercury
INWC Inchesofwatercolumn
INHG Inchesofmercury
Pressure Range vs. Available Units
ZERO AutoZero
Note:DONOTapplyanypressurewhenperformingthisfunction.Withthedisplayreadingxx - ZERO,
presstheEkey.Theupperdisplaywillblink.PressEagaintozerothedisplay.Thedisplaywillread0.0
ifthezerooffsetislessthan±5%offullscale.
bCLt Backlight
ON Backlightalwayson.
OFF Backlightalwaysoff.
30 Backlightstaysonfor30minutes.
10 Backlightstaysonfor10minutes.
5 Backlightstaysonfor5minutes.
2 Backlightstaysonfor2minutes.
PSI KG/CM2 BAR INHg FTWC KPA MPA INWC MBAR CMWC MMHg OZ/IN2 % FS
-14.70
20.00
60.0
100.0
150.0
300.0
600
1000
1500
3000
6000
8000
-1.033
1.406
4.22
7.03
10.55
21.09
42.2
70.3
105.5
210.9
422
562
-1.013
1.379
4.14
6.89
10.34
20.68
41.4
68.9
103.4
206.8
414
551
-29.93
40.7
122.2
203.6
305.4
611
1222
2036
3054
-33.94
46.1
138.4
230.7
346.0
692
1384
2307
3460
-101.4
137.9
414
689
1034
2068
-0.101
0.1379
0.414
0.689
1.034
2.068
4.14
6.89
10.34
20.68
41.4
55.1
-407.3
554
1663
2771
-1013
1379
-1034
1406
-761
1035
3105
-235.2
320.0
960
1600
2400
100
100
100
100
100
100
100
100
100
100
100
100
14
OUtOutputMenu
CtrL ControlMode
1SP Singlesetpoint.
2SP Twofullyindependentsetpoints.
SPAL Singlesetpointandalarm.
1SP SP1,SetPoint1,ReverseorDirectActing
DIR Direct.Relayturnsonwithincreasingpressure.
REV Reverse.Relayturnsonwithdecreasingpressure.
DEL1 SP1,SetPoint1,TimeDelay
Setstheamountoftimeasetpointconditionmustbecontinuouslymetbeforethesetpointcondition
isrecognized.TheDEL1delayisadjustablefrom0-60seconds.
LEd1 SP1,SetPoint1,Lamp
OFF The SP1LEDonthefrontpanelturnsOFFwhentheSP1relayturnsOFF.
The SP1LEDonthefrontpanelturnsONwhentheSP1relayturnsON.
ON The SP1LEDonthefrontpanelturnsONwhentheSP1relayturnsOFF.
The SP1LEDonthefrontpanelturnsOFFwhentheSP1relayturnsON.
ThefollowingSP2functionvaluesareonlyactivatedwhenCtrLissetto2SP:
2SP SP2,SetPoint2,ReverseorDirectActing
DIR Direct.Relayturnsonwithincreasingpressure.
REV Reverse.Relayturnsonwithdecreasingpressure.
DEL2 SP2,SetPoint2,timedelay
Setstheamountoftimeasetpointconditionmustbecontinuouslymetbeforethesetpointconditionis
recognized.TheDEL2delayisadjustablefrom0-60seconds.
LEd2 SP2,SetPoint2,Lamp
OFF The SP2LEDonthefrontpanelturnsOFFwhentheSP2relayturnsOFF.
The SP2LEDonthefrontpanelturnsONwhentheSP2relayturnsON.
ON The SP2LEDonthefrontpanelturnsONwhentheSP2relayturnsOFF.
The SP2LEDonthefrontpanelturnsOFFwhentheSP2relayturnsON.
LdL9 RelayAlternation(Seepage8)
OFF Thereisnoalternatingfunction.
ON RelayswillalternatewithsetpointsSP1H/LandSP2H/Lwitheverycycleofsetpoints.2SP
controlmodeonly.
15
ThefollowingalarmfunctionmenuitemsareactivatedwhenCtrLissettoSPAL:
DELA AlarmDelay
Setstheamountoftimeanalarmconditionmustbecontinuouslymetbeforethealarmconditionis
recognized.Thealarmdelayisadjustablefrom0-60seconds.
LEdA AlarmLamps
OFF The ALLOLEDorALHILEDonthefrontpanelturnsOFFwhenthealarmrelayturnsOFF.
The ALLOLEDorALHILEDonthefrontpanelturnsONwhenthealarmrelayturnsON.
ON The ALLOLEDorALHILEDonthefrontpanelturnsONwhenthealarmrelayturnsOFF.The
ALLOLEDorALHILEDonthefrontpanelturnsOFFwhenthealarmrelayturnsON.
AL AlarmType(seeAlarmAdjustmentbelow)
HIGH Highalarmonly.
LOW Lowalarmonly.
HILO Forahighandlowguardbandtypealarm.Sharethesamerelayoutput.
Alarm Adjustment
Alarmsettingsaredependentupontheselectedalarmtype.TheEDApressurecontrolleralarmmaybeconguredas
aHighAlarm,LowAlarm,orHigh/LowAlarm.Alarmsettingsmaybesettoanywherewithintherangeoftheinstru-
ment.Thedeadbandsofthealarmsarexedat1%offullscale.
ALrE AlarmReset
AUTO Automaticreset.
HOLD Manualreset.AnalarmisresetbypressingtheRSTkeyonthefrontpanel.
ALiHLowAlarmInhibit
OFF Alarminhibitisoff.
ON Alarminhibitison.
Note:IfALiHis selected ON, alowalarmconditionissuspended upon power up untiltheprocessvaluepasses
throughthealarmsetpointonce.
16
diS Display Menu
PEAK Peak
ThePeakfeaturestoresthehighestpressurereadingtheinstrumenthasmeasuredsincethelastresetor
powerup.AtpowerupPEAKisresettothepresentpressurereading.TomanuallyresetthePEAKvalue,
presstheRST(RESET)keywhileinPEAK.
VALY Valley
TheValleyfeaturestoresthelowestpressurereadingtheinstrumenthasmeasuredsincethelastreset
orpowerup.AtpowerupVALYisresettothepresentpressurereading.TomanuallyresettheVALY
value,presstheRST(RESET)keywhileinVALY.
DAMP Dampening
Adjustfrom1-15.Dampeningstabilizesthedisplayfrominstabilitiesduetothingssuchasvibration
andexcessivepressureuctuations.Thedampeningsettingadjuststheamount ofreadingsthatare
averagedforeachdisplayupdate.Adjustthedampeningvalueuntilthedisplayreadsastablevaluefor
theapplication.
AdUAdvancedMenu
POL,ProcessOutputLow,andPOH,ProcessOutputHighareusedtoscalethetransmitteroutputforaunitwiththe
outputoptionof4to20mA,0-5VDC,0-10VDC,1-5VDC,or1-6VDC.Belowshowswith4to20mAoutputoption.
POL ProcessOutputLow
Settothedesireddisplayreadingforthe4mAoutput.Maybesetfrom2%belowminimumscaleupto
POH.
POH ProcessOutputHigh
Settothedesireddisplayreadingforthe20mAoutput.MaybesetfromPOLto2%abovemaximum
scale.
CAL – ZERO ZeroCalibration
DONOTapplyanypressurewhenperformingthisfunction.Withthedisplayreading
CAL - ZERO,presstheEkey.Theupperdisplaywillblink.PresstheEkeyagaintocomplete
thezeroingoftheinstrumentorpresstheMENUkeytocancel.
CAL – FS Full-scaleCalibration
WiththedisplayreadingCAL - FS,applyfull-scalepressuretotheunit,presstheEkey.
Theupperdisplaywillblink.PresstheEkeyagaintocompletethecalibrationorpressthe
MENUkeytocancel.
trAnsetsthetransmitteroutputoptionfunctionforaunitwiththeoutputoptionof4to20mA,0-5VDC,0-10VDC,1-5
VDC,or1-6VDC.Belowshowswith4to20mAoutputoption.
trAn
DIR DirectOutput.4mAoutputatzero,20mAoutputatfullscalepressure.
REV ReverseOutput.20mAoutputatzero,4mAoutputatfullscalepressure.
CAL - DFLT FactoryDefaultCalibration
WiththedisplayreadingCAL - DFLT,presstheEkey.Theupperdisplaywillblink.PressE
againtorestoretheoriginalfactorycalibrationvaluesorpresstheMENUkeytocancel.
17
tEStTestMenu
tESt Whenselectedtheunitsimulatesapressureinputovertherangetotesttheprogrammingandoutput 
function.TostartanautomaticsimulatedcyclingthroughthepressurerangepresstheEkey.Thistest
willruncontinuallyuntiltheEkeyispressedagain.Tomanuallyadjustthesimulatedpressure
pressthe▲or▼keytoadjustthepressurevalue.ToexittEStpresstheMENUkey.
FAILFailsafeMenu
TheFailsafemenuisusedtosettherelayandtransmitteroutputstocertainpresetvalueswhenfailsafeconditions
occur.Errorcodeswillshowonthedisplayindicatingtheproblem.SeeDiagnosticErrorMessagesonthenextpage.
rEL RelayOutputFailsafeCondition
OPEN Therelayisde-energizeduponfailsafecondition.TheNOcontactswillbeopened,andthe
NCcontactswillbeclosed.
CLSE Therelayisenergizeduponfailsafecondition.TheNOcontactswillbeclosed,andtheNC
contactswillbeopened.
NORM Nochangeappliedtotherelayuponfailsafecondition.
OUtPsetsthetransmitteroutputoptionfailsafeconditionforaunitwiththeoutputoptionof4to20mA,0-5VDC,0-10
VDC,1-5VDC,or1-6VDC.Seebelowchartoftransmitteroutputactionaccordingtooutputsignaltype.
OUtP TransmitterOutputFailsafeCondition
LOW Transmitteroutputgoestolowfailsafecondition.
HIGH Transmitteroutputgoestohighfailsafecondition.
NORM Nochangeappliedtotransmitteroutputuponfailsafecondition.
FrEs Failsafereset
AUTO Automaticreset-Failsafeisresetautomaticallywhenthefailsafeerrorconditionisremoved.
HOLD Manualreset-FailsafeisresetwhentheMENUkeyispressed.
Output Signal 4-20 mA 0-5 VDC 0-10 VDC 1–6 VDC 1-5 VDC
LOW
HIGH
3.6mA
22mA
-0.125VDC
5.625VDC
-0.250VDC
11.250VDC
0.875VDC
6.625VDC
0.9VDC
5.5VDC
©Copyright2019DwyerInstruments,Inc. PrintedinU.S.A.4/19 FR#443725-50Rev.2
18
4. DIAGNOSTIC ERROR MESSAGES
5. MAINTENANCE/REPAIR
UponnalinstallationoftheSeriesEDA,inspectandcleanwithwaterordampclothatregularintervals.TheSeries
EDAisnoteldserviceableandshouldbereturnedifrepairisneeded(eldrepairshouldnotbeattemptedandmay
voidwarranty.
Thissymbolindicateswasteelectricalproductsshouldnotbedisposedofwithhouseholdwaste.Please
recyclewherefacilitiesexist.CheckwithyourLocalAuthorityorretailerforrecyclingadvice.
6. WARRANTY/RETURN
Referto“TermsandConditionsofSales”inourcatalogandonourwebsite.Contactcustomerservicetoreceivea
ReturnGoodsAuthorizationnumberbeforeshippingtheproductbackforrepair.Besuretoincludeabriefdescription
oftheproblemplusanyadditionalapplicationnotes.
Display Meaning
Err1
Err2
Err3
Err4
Err5
Lowtemperaturelimit
Atemperaturebelow0°Fhasbeenappliedtothesensor
Hightemperaturelimit
Atemperatureabove180°Fhasbeenappliedtothesensor
Sensorfailure
Themicro-controllerisreceivinginvalidsignalfromthesensor
Overpressurelimit
Proofpressurehavebeenexceeded
Keypadshort
MERCOID
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
A DIVISION OF
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000
Fax: 219/872-9057
dwyer-inst.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Dwyer Series EDA User manual

Type
User manual

Dwyer Series EDA is a versatile electronic pressure controller known for its accuracy, stability, and durability. It offers a wide range of pressure measurement capabilities, from vacuum levels to high pressures up to 6,000 psi. The device is equipped with a user-friendly interface, featuring a backlit LCD display and intuitive controls, making it easy to set up and operate. With its compact design and weatherproof construction, the Dwyer Series EDA is suitable for both indoor and outdoor applications, ensuring reliable pressure monitoring and control in various industrial environments.

Ask a question and I''ll find the answer in the document