1.3 ELECTRICAL CONNECTIONS
Note: Installationmustbemadeinaccordancewithlocalcodesandregulations.
Electricalconnectionsaremadetotheremovableterminalblocksinsidetheenclosure.Removethetopbackcover,
donotremovebottomcover.Feedstrippedandtinnedleadsthroughtheconduitopeningandconnectthemasshown
inFigure3.TheEDAprovidestwo1/2˝NPTfemaleportsforconduitconnection.Theconduitconnectionsmustbe
madesuchthatcondensationisnotallowedtoenterthesensorhousing.Ifnecessaryinstallaconduitbreatherdrain
inaseparateconduitbodytopreventbuildupofmoisture.Itisrecommendedthatshieldedtwistedpairwirebeused
forthetransmitteroutputoptionifthepotentialexistsforinterferencefromexternalnoisesources.Whenreplacingtop
backcovertightenscrewsto2±.25in.lbs.
LoadscanbeconnectedtoconnectorsCONN7andCONN8terminalblocksbasedontheControlsettings:
•Forsinglesetpointmode(CtrL-1SP),connecttheLoadtoSP1relay(CONN7).
•Fortwosetpointsmode(CtrL-2SP),connecttheLoad1toSP1relay(CONN7)and
Load2toSP2relay(CONN8).
•Forsinglesetpointandalarmmode(CtrL-SPAL),connecttheLoad1toSP1relay
(CONN7)andLoad2toALARMrelay(CONN8).
Wiring
Anexternalswitchorcircuitbreakershouldbeaddedtoduringtheinstallationasadisconnectingdevice.Theswitch
orcircuitbreakermustmeettherequirementsofIEC60947-1andIEC60947-3,shalldisconnectallcurrentcarrying
conductors,andshallnotinterrupttheprotectiveearthground.Thedisconnectingswitchorcircuitbreakermustbe
markedorlabeledwiththesymbols“I”foronand“O”foroff,perIEC60417-5007&IEC60417-5008andshallbe
markedas“DisconnectingDevice”.DonotpositionthePLSinaspacewhereitisdifculttooperatethedisconnecting
devicethatprovidespower.300V@90°C18AWG/0.75mm2wiringwithPVCorequivalentinsulationwith94-V0or
FV-0ammabilityratingisrecommendedfortheswitchoutputsandpower.Terminalblocksratedfor16-22solidor
strandedcopperconductor.6lbinissuggestedtighteningtorque.
Figure 3: Wiring
Anexternalpowersupplyof12-28VDC/
AC with minimum current capability
of 200 mA must be used to power the
unit. The power supply connection is
notpolaritysensitivesothepositive and
negative connections may be made to
eitherterminalofCONN9terminalblock.
For voltage output option, connect the
voltage receiver (-) to terminal 1 and
voltage receiver (+) to terminal 2 of the
CONN10 terminal block. For current
outputoption,connectthecurrentreceiver
(-) to terminal 3 and current receiver
(+) to terminal 4 of CONN10 terminal
block. DO NOT APPLY EXTERNAL
POWER TO CONN10 TERMINALS -
PERMANENTDAMAGENOTCOVERED
BYWARRANTYWILLRESULT.
Asapermanentlyinstalledpieceofequipment,apowerdisconnectswitch,circuitbreaker,orother
approveddisconnectdevicemustbeinstalledincloseproximitytotheinstalledboardandwithin
easyreachoftheoperator.Thisdisconnectdevicemustincludealabelindicatingitsfunctionasamainsdisconnect.
Acircuitbreakerorfusedeviceisrecommended(seeFigure3).
SP1
RELAY
5A 250 VAC FOR LOADS USING 120/240 VAC POWER
1A 32 VDC FOR LOADS USING 30 VDC POWER
375 mA 250 VAC
LINE
INPUT
12 TO 30 VDC/AC
POWER
SP2 OR ALARM
RELAY
Explanation of Symbols:
Symbol Publication Description
IEC50417-5031 Directcurrent
IEC50417-5032 Alternatingcurrent
IEC50417-5019 Protectiveconductorterminal
IEC50417-5007 On(supply)
IEC50417-5008 Off(supply)
~
ELECTRIC SHOCK HAZARD. DISCONNECT POWER BEFORE MAKING ELECTRICAL
CONNECTIONS.Failuretodosowillresultininjuryordeath.
DANGER
TomaintainType4Xratingofthe enclosure,1/2NPTconduitttingsmust haveaULType4X
outdoorrating.
NOTICE
EQUIPMENT DAMAGE.DonotallowwiretotouchorpressonPCBAcomponentswhenshing
wirethroughtheconduitconnection.Failuretodosomayresultindamagetothecircuitry.
CAUTION
EQUIPMENT DAMAGE.Donotexceedthespeciedsupplyvoltagerating.Failuretodosomay
resultinpermanentequipmentdamage.
CAUTION
NOTICE