ESAB EPP-450 Plasma Power Source User manual

Type
User manual
14
LE SCOSSE ELETTRICHE POSSONO UCCIDERE!
I TERMINALI AD ANELLO DEVONO AVERE UNO SPAZIO TRA IL PAN
NELLO LATERALE ED IL TRASFORMATORE PRINCIPALE. LO SPAZIO
DEVE ESSERE SUFFICIENTE IN CASO DI EVENTUALE CONTATTO
D’ARCO. ACCERTARSI CHE I CAVI NON INTERFERISCANO CON LA
ROTAZIONE DELLA VENTOLA DI RAFFREDDAMENTO.
UNA MESSA A TERRA ERRATA PUÒ RISULTARE IN MORTE O LESIONE.
IL TELAIO DEVE ESSERE COLLEGATO AD UNA MESSA A TERRA ELET
TRICA APPROVATA. ACCERTARSI CHE IL CAVO DI MASSA NON SIA
COLLEGATO AD ALCUN TERMINALE PRIMARIO.
LE SCOSSE ELETTRICHE POSSONO UCCIDER E! TENSIONE E CORRENTE
PERICOLOSI!
QUANDO SI LAVORA INTORNO AD UN GENERATORE DI ENERGIA AL
PLASMA CON I COPERCHI RIMOSSI:
• DISINNESTARE IL GENERATORE DI ENERGIA NEL SEZIONATORE
(A PARETE).
• UN INDIVIDUO QUALIFICATO DOVREBBE CONTROLLARE LE SBAR-
RE COLLETTRICI (POSITIVE E NEGATIVE) CON UN VOLTMETRO.
3.5 Connessioni di uscita
AVVERTIMENTO
AVVERTIMENTO
AVVERTIMENTO
3.5.1 Cavi di uscita (forniti dal cliente)
Scegliere i cavi di uscita del taglio a getto di plasma (forniti dal cliente) sulla base di un cavo di rame 4/0 AWG
isolato da 600 volt per 400 ampere di corrente di uscita. Per 450 ampere, devono essere usati cavi a 600 volt,
taglio 100% lavoro, due 2/0 AWG paralleli.
Nota:
Non usare un cavo di saldatura isolato da 100 volt.
SEZIONE 3 INSTALLAZIONE
3.5.2 Procedura di connessione di uscita - Generatore di energia singolo
1. Rimuovere il pannello di accesso sul lato anteriore inferiore del generatore di energia.
2. Inlare i cavi di uscita attraverso le aperture sul fondo del pannello anteriore o sul fondo del generatore di energia subito
dietro il pannello anteriore.
3. Collegare i cavi ai terminali specicati montati all’interno del generatore di energia, usando i connettori del cavo di
pressione classicata UL.
4. Riposizionare il pannello rimosso nel corso del primo procedimento.
30
SEZIONE 4 FUNZIONAMENTO
1. Applicare l’alimentazione chiudendo il sezionatore (a parete).
(L’EPP-450 non è dotato di un interruttore on / o (acceso/
spento). La luce dell’alimentazione principale si accende e la
luce dei guasti lampeggia e quindi si spegne.
2. Il pulsante E-stop viene estratto.
3. Selezionare l’impostazione Pannello / Remoto.
4. Impostare l’interruttore Alto / Basso dell’arco pilota. Se l’arco
pilota Alto / Basso è selezionato da un telecomando, l’inter-
ruttore deve trovarsi in posizione Basso. (Fare riferimento ai
dati di taglio nel manuale del cannello).
5. Se si utilizza la modalità del pannello, visualizzare gli am-
pere preimpostati con l’interruttore degli AMP EFFETTIVI /
PREIMPOSTATI. Regolare la corrente no a quando il valore
approssimativo desiderato appaia sull’amperometro. Se si
utilizza la modalità remota, il collocamento dell’interrutto-
re degli Amp eettivi / preimpostati nella posizione Amp
preimpostati garantisce la corrente di uscita iniziale richiesta
dal telecomando.
6. Iniziare l’operazione di taglio a getto di plasma. Questa opera-
zione potrebbe includere la congurazione manuale di altre
opzioni, in base al pacchetto del plasma totale.
7. Se si utilizza la modalità del pannello, dopo che il taglio è
iniziato, regolare la corrente sulla quantità desiderata.
8. Se il taglio o la marcatura non iniziano, controllare la luce
dei guasti. Se la luce dei guasti è accesa, fare riferimento alla
sezione sulla risoluzione dei guasti.
Nota:
La luce dei guasti lampeggia quando il contattore
viene inizialmente acceso per indicare che il Bus CC
è alimentato normalmente.
4.3 Sequenza del funzionamento
SECTION 4 Operation
ESP 400C Plasma Power Source
ESP 400C Plasma Power SourceESP 400C Plasma Power Source
ESP 400C Plasma Power Source
4-4
Begin
Cutting
ACTUAL AMPS
PRESET AMPS
HIGH
LOW
PILOT
ARC
PANEL
REMOTE
Apply Power
4.3 Sequence of Operation
1. Apply power by closing the line (wall) switch.
(The ESP-400C does not have an on/off
switch). The main power light will illuminate
and the fault light will flash and then go out.
2. Select the Panel/Remote setting.
3. Set pilot arc High/Low switch. (Refer to cutting
data in the torch manual.)
4. If using panel mode, view preset amps with the
ACTUAL/PRESET AMPS switch. Adjust current
until the approximate desired value is shown on
the ammeter.
5. Begin plasma cutting operation. This may
include manually setting up other options,
depending on the total plasma package.
6. If using panel mode, after cutting has begun,
adjust current to desired amount.
7. Check for fault light. If a fault light illuminates,
refer to troubleshooting section.
Note: The fault light flashes when the contactor is
Note: The fault light flashes when the contactor isNote: The fault light flashes when the contactor is
Note: The fault light flashes when the contactor is
first turned on signifying the DC Bus powered up
first turned on signifying the DC Bus powered upfirst turned on signifying the DC Bus powered up
first turned on signifying the DC Bus powered up
normally.
normally.normally.
normally.
4.4 Arc Initiation Settings
The time to achieve full current can be adjusted to
suit your particular system. This feature uses 50%
of the cutting current to start, dwell and then
gradually (less than a second) achieve full current.
The ESP-400C is factory shipped with this feature
enabled. The default settings are:
Minimum Start Current 40A
Start Current 50% of cut current
Timing to achieve full current 800 msec
Dwell Time 50 msec
SECTION 4 Operation
ESP 400C Plasma Power Source
ESP 400C Plasma Power SourceESP 400C Plasma Power Source
ESP 400C Plasma Power Source
4-4
Begin
Cutting
ACTUAL AMPS
PRESET AMPS
HIGH
LOW
PILOT
ARC
PANEL
REMOTE
Apply Power
4.3 Sequence of Operation
1. Apply power by closing the line (wall) switch.
(The ESP-400C does not have an on/off
switch). The main power light will illuminate
and the fault light will flash and then go out.
2. Select the Panel/Remote setting.
3. Set pilot arc High/Low switch. (Refer to cutting
data in the torch manual.)
4. If using panel mode, view preset amps with the
ACTUAL/PRESET AMPS switch. Adjust current
until the approximate desired value is shown on
the ammeter.
5. Begin plasma cutting operation. This may
include manually setting up other options,
depending on the total plasma package.
6. If using panel mode, after cutting has begun,
adjust current to desired amount.
7. Check for fault light. If a fault light illuminates,
refer to troubleshooting section.
Note: The fault light flashes when the contactor is
Note: The fault light flashes when the contactor isNote: The fault light flashes when the contactor is
Note: The fault light flashes when the contactor is
first turned on signifying the DC Bus powered up
first turned on signifying the DC Bus powered upfirst turned on signifying the DC Bus powered up
first turned on signifying the DC Bus powered up
normally.
normally.normally.
normally.
4.4 Arc Initiation Settings
The time to achieve full current can be adjusted to
suit your particular system. This feature uses 50%
of the cutting current to start, dwell and then
gradually (less than a second) achieve full current.
The ESP-400C is factory shipped with this feature
enabled. The default settings are:
Minimum Start Current 40A
Start Current 50% of cut current
Timing to achieve full current 800 msec
Dwell Time 50 msec
34
PKH: VI_Curves_EPP-450-600_Bus; EPP-450 VI Curves
EPP-450 V-I CURVES
0
100
200
300
400
0 100 200 300 400 500
OUTPUT CURRENT (Amperes)
OUTPUT VOLTAGE (Volts)
431V Open Circuit
INTERNAL CURRENT LIMIT
DATA PLATE
MAX RATING
VREF = 8.000
VREF = 6.000
VREF = 4.000
VREF = 2.000 HIGH RANGE
VREF = 1.000 MIN HIGH RANGE
Output of Boost/Start Circuit
Max Output Voltage
@
Nominal Line
I
OUT
= (50) x (V
REF
) High Range
VREF = 9.000
VREF = 10.00 MAX LOW RANGE
I
OUT
= (10) x (V
REF
) Low Range
VREF = 5.00 HIGH RANGE
VREF = 1.00 MIN LOW RANGE MARKING*
SEZIONE 4 FUNZIONAMENTO
4.5.1 Curve approssimative V-I EPP-450 per tutti i modelli
Tensione di uscita (Volt)
Corrente di uscita (Ampere)
Circuito aperto 431 V
Uscita del circuito di spinta / avviamento
I
OUT
= (50) x (V
REF
) Gamma alta
I
OUT
= (10) x (V
REF
) Gamma bassa
Tensione di uscita massima
sulla linea nominale
Limite della corrente interno
V
REF
= 8,000
V
REF
= 6,000
V
REF
= 5,00 Gamma alta
V
REF
= 1,00 Min. Marcatura a gamma bassa *
V
REF
= 4,000
V
REF
= 1,00 Min. Gamma alta
PIASTRA DEI DATI
CLASSIFICAZIONE
MASSIMA
V
REF
= 10,00 Max. Gamma bassa
V
REF
= 2,00 Gamma alta
V
REF
= 9,000
35
SECTION 5 MAINTENANCE
5.1 General
ELECTRIC SHOCK CAN KILL!
SHUT OFF POWER AT THE LINE WALL DISCONNECT BEFORE AT
TEMPTING ANY MAINTENANCE.
WARNING
WARNING
EYE HAZARD WHEN USING COMPRESSED AIR TO CLEAN.
• Wear approved eye protection with side shields when cleaning the
powersource.
• Useonlylowpressureair.
CAUTION
Maintenance On This Equipment Should Only Be Performed By
Trained Personnel.
5.2 Cleaning
Regularlyscheduledcleaningofthepowersourceisrequiredtohelpkeeptheunitrunningtroublefree.Thefrequencyof
cleaningdependsonenvironmentanduse.
1. Turnpoweroatwalldisconnect.
2. Removesidepanels.
3. Uselowpressurecompresseddryair,removedustfromallairpassagesandcomponents.Payparticularattentionto
heatsinksinthefrontoftheunit.Dustinsulates,reducingheatdissipation.Besuretoweareyeprotection.
36
SECTION 5 MAINTENANCE
Air restrictions may cause EPP-450 to over heat.
Thermal Switches may be activated causing interruption of func-
tion.
Do not use air lters on this unit.
Keep air passages clear of dust and other obstructions.
WARNING
CAUTION
5.3 Lubrication
• Someunitsareequippedwithoiltubesonthefans.Thesefansshouldbeoiledafter1yearofser-
vice.
• AllotherEPP-450shavefanmotorsthatarepermanentlylubricatedandrequirenoregularmainte-
nance.
ELECTRIC SHOCK HAZARD!
BE SURE TO REPLACE ANY COVERS REMOVED DURING CLEANING
BEFORE TURNING POWER BACK ON.
37
SECTION 6 TROUBLESHOOTING
6.1 General
ELECTRIC SHOCK CAN KILL!
DO NOT PERMIT UNTRAINED PERSONS TO INSPECT OR REPAIR THIS
EQUIPMENT. ELECTRICAL WORK MUST BE PERFORMED BY AN EXPE
RIENCED ELECTRICIAN.
WARNING
Stop work immediately if power source does not work properly.
Have only trained personnel investigate the cause.
Use only recommended replacement parts.
CAUTION
6.2 Fault Indicators
FaultindicatorsarefoundonthefrontpanelUsedwith
theLEDsonPCB1(locatedbehindthecoverwiththe
EPPlabel)problemscanbediagnosed.
NOTE:
Itisnormal for momentarylight-
ing(ashing)ofthefaultindicator
andLED3whenacontactoron”
signalisappliedatthebeginning
ofeachcutstart.
FaultIndicatorusedwith:
LED3-BusRipple
LED4-HighBus
LED5-LowBus
LED7-ArcVoltageSaturation
LED8-ArcVoltageCuto
PowerResetFaultIndicatorusedwith:
LED6-RightOvercurrent
LED9-LeftOvercurrent
LED10-LeftIGBTUnsaturated
LED11-RightIGBTUnsaturated
LED12-Left-12VBiasSupply
LED13-Right-12VBiasSupply
PCB1 Located behind
thispanel.
Front Panel Fault
Indicators
38
SECTION 6 TROUBLESHOOTING
FaultIndicator(FrontPanel)
Illuminateswhen thereareabnormalitiesinthecuttingprocessorwhentheinput
voltagefalls±10%outsidethenormalvalue.Momentaryilluminationisnormal.If
continuouslylit,checkLEDs3,4,5,7,and8onPCB1forfurtherdiagnosis.
38
38
LED3–(yellow)BusRippleFault-Momentarilyilluminatesatthebeginningof
eachcut.Continuouslylitduringsingle-phasingorimbalancedline-to-linevolt-
agesofthethreephaseinputline(ExcessiveRipple).PowerSourceisshutdown.
LED4–(yellow)HighBusFault–Illuminateswheninputlinevoltageistoohigh
forproperoperation(approximately20%abovenominallinevoltagerating).
Powersourceisshutdown.
LED5–(yellow)LowBusFault–Illuminateswheninputline
voltageislowerthan10%belownominallinevoltagerating.
PowerSourceisshutdown.
LED7–(yellow)ArcVoltageSaturationFault–Illuminates
whenthecuttingarcvoltageistoohighandcuttingcurrent
dropsbelowpresetlevel.LEDwill extinguishaftervoltage
decreasesandcurrentrises.
LED8–(yellow)ArcVoltageCutoFault–Illuminateswhen
arcvoltageincreasesoverthepresetvalue.PSisshutdown.
39
SECTION 6 TROUBLESHOOTING
PowerResetFaultIndicator(onfrontpanel)
Illuminateswhenaseriousfaultisdetected.Inputpowermustbedisconnectedfora
least5secondstoclearthisfault.CheckPCB1RedLEDs6,9,10,11,12,and13ifthis
faultisilluminatedforfurtherdiagnosis.
LED6–(red)RightOvercurrentFault–Illuminateswhenthecurrentoutoftheright
sidechopperistoohigh(300amps).Thiscurrentismeasuredbytheright-sidehall
sensor.Thepowersourceisshutdown.
38
LED9–(red)LeftOvercurrentFault–Illuminateswhenthecurrentfromtheleftside
chopperistoohigh(300amps).Measuredbythelefthallsensor.Powersourceis
shutdown.
LED10_(red)LeftIGBTUnsaturatedFault–IlluminateswhenleftIGBTisnotfully
conducting.PS(PS)isshutdown.
LED11–(red)RightIGBTUnsaturatedFault–Illuminates
whenrightIGBTisnotfullyconducting.PowerSource(PS)
isshutdown.
LED12–(red)Left-(neg)12VBiasSupplyFault–Illuminates
whennegative12V biassupply tothe leftside IGBTgate
drivecircuit(locatedonPWM-driveboardPCB2)ismissing.
PSisshutdown.
LED13–(red)Right–(neg)12VBiasSupplyFault-Illuminateswhennegative12Vbias
supplytotherightsideIGBTgatedrivecircuit(locatedonPWMdriveboardPCB3)is
missing.PSisshutdown.
40
SECTION 6 TROUBLESHOOTING
6.3 Fault Isolation
Manyofthemostcommonproblemsarelistedbysymptom.
6.3.1 Nooutputwithcontactorsignalapplied
6.3.2 Outputlimitedto100A
6.3.3 Fansnotworking
6.3.4 Powernotonorlowvoltage
6.3.5 Faultlightillumination
6.3.6 Torchwon’tre
6.3.7 Fussesblown-F1andF2
6.3.8 Intermittent,interruptedorpartialoperation
6.3.3 Fans Not Working
Problem Possible Cause Action
All4fansdonotrun
Thisisnormalwhennotcutting.
Fans run only when “Contactor On”
signalisreceived.
None
1,2or3fansdonotrun.
Broken or disconnected wire in fan
motorcircuit.
Repairwire.
Faultyfan(s) Replacefans
6.3.1 No output with contactor signal applied
Problem Possible Cause Action
Contactor signal is applied,
contactor lamp on front
panelis illuminated,K2 and
K3 contactors do not close
andlowbusfault light,LED
5illuminates.
External emergency stop (E-stop) is
open.
ConnectisolatedcontactofE-stopswitchtopro-
videconnectionbetweenJ1-EandJ1-F.
E-stopbuttononfrontpanelispushed
in.
TwistandpullouttoresetE-stopcondition.
Powerresetlamponfrontpanelindi-
catesaseriousfaultcondition.
Refertosectionunderfaultlightillumination.
6.3.2 Output limited to 100A
Problem Possible Cause Action
Powersourcewillnotgoover
100A.
Highcurrentrangesignalmissing.
ExternalcontrolshouldconnectJ1-RtoJ1-T.As
analternative,inthepowersource,movethered
wireonTB8-1toTB8-2.
41
6.3.4 Power Not On or LOW Voltage
Problem Possible Cause Action
Powersourceinoperable:
Mainpowerlampiso.
Missing3-phaseinputvoltage
Restoreall 3 phases of input voltageto within
±10%ofnominalline.
Missing1of3-phaseinputvoltage
Restoreall 3 phases of input voltageto within
±10%ofnominalline.
Lowopencircuitvoltage
FuseF3/F4blown ReplaceF3/F4
PilotarcContactor(K4)faulty ReplaceK4
FaultyControlPCB1 ReplaceControlPCB1(P/N
0558038312
)
Problem Possible Cause Action
Faultlightilluminatesattheendof
cutbutgoesoatthestartofthe
next.
Normalconditioncausedwhenter-
minatingthearcbyrunningthetorch
otheworkorthearcbeingattached
toapartthatfallsaway.
Reprogramcuttingprocessto
ensurearcisterminatedonlyby
removingthe“ContactorOnsignal.
LED3–(amber)BusRipple
Imbalanceof3-phaseinputpower
Maintainphasevoltageimbalance
oflessthan5%.
Momentary loss of one phase of
inputpower
Restoreandmaintaininputpower
within±10%nominal
FaultycontrolPCB1 ReplacePCB1P/N
0558038312
LED4–(amber)HighBus
Oneormorephasesofinputvoltage
exceednominallinevoltagebymore
than15%.
Restoreandmaintainlinevoltage
within±10%
FaultycontrolPCB1 ReplacePCB1P/N
0558038312
Oneormoreshorteddioderectiers
(D25-D28)onthe“ElectrodePlate
Replaceshorteddioderectiers
LED5–(amber)LowBus
One or more phases of input volt-
agearelowerthannominalbymore
than15%.
Restoreandmaintainwithin
±10%ofnominal
BlownF1andF2fuses
SeeF1andF2inBlown
FusesSection
OvertempLightcomeson. SeeovertempinFaultLightSection
Imbalanced3-phaseinput
power
Maintainphasevoltageimbalance
oflessthan5%
Momentary loss of one phase of
inputpower
Restoreandmaintainwithin
±10%ofnominal
FaultyMainContactor(K1) ReplaceK1
FAULTYControlPCB1 ReplacePCB1P/N
0558038312
SECTION 6 TROUBLESHOOTING
6.3.5 Fault Light Illumination
42
SECTION 6 TROUBLESHOOTING
Problem Possible Cause Action
LED 6 – (red) Right Over Cur-
rent
Note:
Ifoperationat275Aorlessis
possible,thentheLEFTsideis
notworking.
Cuttingatover275Awithafaultyleftside
(leftsideoutput=0)
Seefaultyleftorrightside
Rightcurrenttransducerconnectorloose
orunplugged.PCBloose.
Secureconnections
Loose or unplugged connector at right
PWM/DrivePrintedcircuitboard.
Secureconnection
P2atleftofPWM/DrivePCBlooseorun-
plugged.
Secureconnection
CheckvoltagebetweenP7-6andP7-7.A
voltage in either polarity of greater than
0.01Vindicatesafaultyrightcurrenttrans-
ducer(TD2).
Replace right current transducer
(TD2)
FaultyPCB1 ReplacePCB1P/N
0558038312
FaultyrightPWM/DrivePCB
Replace right PWM / Drive PCB P/N
0558038324
LED9–(red)LeftOverCurrent
Note:
Ifoperationat275Aorlessis
possible,thentheRightsideis
notworking.
Cuttingatover275Awithafaultyrightside
(rightsideoutput=0)
Seefaultyrightside
Leftcurrenttransducerconnectorlooseor
unplugged.PCBloose.
Secureconnections
LooseorunpluggedconnectoratleftPWM
/DrivePrintedcircuitboard.
Secureconnection
P2 at right of PWM / Drive PCB loose or
unplugged.
Secureconnection
CheckvoltagebetweenP7-2andP7-3.A
voltage in either polarity of greater than
0.01Vindicatesafaultyleftcurrenttrans-
ducer(TD1).
Replaceleftcurrenttransducer(TD1)
FaultyPCB1 ReplacePCB1P/N
0558038312
FaultyleftPWM/DrivePCB
Replace left PWM / Drive PCB P/N
0558038324
NEVER attempt to power-up or operate the power source with any
Gate / Emitter IGBT Plug disconnected from its PWM / Gate Drive
Board. Attempting to operate the power source with any open (un-
plugged) IGBT Gate / Emitter Connector may damage the IGBT and
the plasma cutting torch.
CAUTION
43
SECTION 6 TROUBLESHOOTING
Problem Possible Cause Action
VeryhighOutputcurrentac-
companiedbyeitheraleftor
rightovercurrent(LED6)
ShortedIGBT ReplacetheIGBTs
Currentpotsettoohigh Lowerthecurrentsetting
FaultyleftPWM/DrivePCB ReplaceleftPWM/DrivePCB
Highremotecurrentsignal Decreaseremotecurrentsignal
FaultyPCB1 ReplacePCB1P/N0558038312
LED10-(red)LeftIGBTUn-
saturated
BlackwireconnectingIGBT(Q2)collectortoP3ofthe
leftPWM/DrivePCB(PCB2)isdisconnected.
Secureconnector
ShortedFreewheelingDiode(s) Replacefreewheelingdiode(s)
LooseorunpluggedP1connectorattheleftPWM/
DrivePCB
SecureP1
LooseorunpluggedP10connectoratPCB1 SecureP10
FaultyPCB1 ReplacePCB1P/N0558038312
FaultyleftPWM/DrivePCB ReplacePCB2P/N0558038324
LED 11 - (red) Right IGBT
Unsaturated
BlackwireconnectingIGBT(Q5)collectortoP3ofthe
rightPWM/DrivePCB(PCB3)isdisconnected.
Secureconnector
ShortedFreewheelingDiode(s) Replacefreewheelingdiode(s)
LooseorunpluggedP1connectorattheleftPWM/
DrivePCB
SecureP1
LooseorunpluggedP10connectoratPCB1 SecureP11
FaultyPCB1 ReplacePCB1P/N0558038312
FaultyrightPWM/DrivePCB ReplacePCB3P/N0558038324
44
SECTION 6 TROUBLESHOOTING
Problem Possible Cause Action
LED12–(red)Left–12VMissing
LooseorunpluggedP1connectorat
theleftPWM/DrivePCB
SecureP1connector
Loose or unplugged P10 connector
atPCB1
SecureP10connector
FaultyleftPWM/DrivePCB
Replace left PWM / Drive PCB P/N
0558038324
LED12–(red)Right–12VMissing
LooseorunpluggedP1connectorat
therightPWM/DrivePCB
SecureP1connector
Loose or unplugged P11 connector
atPCB1
SecureP11connector
FaultyrightPWM/DrivePCB
Replace right PWM / Drive PCB P/N
0558038324
VeryhighOutputcurrentaccompa-
niedbyeitheraleftorrightovercur-
rent(LED9orLED6respectively)
ShortedIGBT ReplacetheIGBTs
Currentpotsettoohigh Lowerthecurrentsetting
FaultyleftPWM/DrivePCB
Replace left PWM / Drive PCB P/N
0558038324
Highremotecurrentsignal Decreaseremotecurrentsignal
FaultyPCB1 ReplacePCB1P/N0558038312
OverTempLampilluminates
Oneormorefansinoperable Repairorreplacefan(s)
Brokenwireorunpluggedconnector
atthermalswitch.
Repair brokenwires and unplugged con-
nector
Obstructiontoairowcloserthan3feet
(1m)torearofpowersource.
Allow3ft.(1m)minimumbetweentherear
ofthepowersourceandanyobjectthatmay
restrictairow.
Excessive dirt restricting cooling air
ow
Cleanout excessivedirt, especially in the
extrusionsfortheIGBTsandfreewheeling
diodes,thePOS,NEGandElectrodePlates,
the main transformer (T1) and the lter
inductors(L1andL2).
Obstructedairintake
Checkandclearanyobstructionsfromthe
bottom, front, and toprear of the Power
Source.
45
SECTION 6 TROUBLESHOOTING
6.3.6 Torch Will Not Fire
Problem Possible Cause Action
MainArcTransfersto the workwitha
short“pop,placingonlyasmalldimple
inthework.
Remote control removes the start
signalwhen the main arc transfersto
thework.
Panel/Remoteswitchin“Remote”with
noremotecontrolofthecurrent
Place Panel/Remote switch in“Panel”
position
Remote current control present but
signalmissing.
CheckforcurrentreferencesignalatTB1-
4(+)andTB1-5(-).SeeSignalvs.Output
CurrentCurvethissection.
Currentpotsettoolow. Increasecurrentpotsetting.
Start current pot, located behind the
cover for the control PCB is set too
low.
Increasethestartcurrentpostsetting
to“7”.
Arcdoesnotstart.Thereisnoarcatthe
torch.OpencircuitvoltageisOK.
Openconnectionbetweenthepower
sourcepositiveoutputandthework.
Repairconnection
FuseF6inthePilotarccircuitisblown. ReplaceF6
FuseF7inthepilotarccircuitisblown. ReplaceF7
PilotarcHigh/Lowswitchisinthe”LOW
positionwhen using consumablesfor
100Aorhigher(Refertoprocessdata
includedintorchmanuals)
Change Pilot arc to “High” position.
(Refertoprocessdataincludedintorch
manuals)
Pilotarccontactor(K4)faulty. ReplaceK4
FaultyPCB1
ReplacePCB1P/N
0558038312
46
Problem Possible Cause Action
FusesF1andF2blown.
Processcontrollerignitespilotarctoo
soon after providing the Contactor
Onsignal
Process controller must allow at least
300MS to lapse between the applica-
tion of the“Contactor On” signal and
theignitionofthepilotarc.Fixprocess
controllerlogicandreplacediodes.
Faultynegative(Electrode)outputcable
shortingtoearthground.
Repaircable
Shortedfreewheelingdiode.
Replace shorted freewheeling diode
andF1-F2
One or more shorted diode rectiers
(D13-D18)on“POSPlate.
Replacealldioderectiersonthe“POS
P l a t e ”.
One or more shorted diode rectiers
(D7-D12)on“NEGPlate.
Replacealldioderectiersonthe“NEG
P l a t e ”.
SECTION 6 TROUBLESHOOTING
6.3.7 Fuses F1 and F2 Blown
Problem Possible Cause Action
WorksOKat275Aorless-Over
current right side when cutting
over275A.LED6oncontrolboard
illuminated.
LooseorunpluggedconnectoratleftPWM/
DrivePCB(PCB2)
Secureconnector
FaultyleftPWM/DrivePCB
Replace right PWM / Drive PCB P/N
0558038324
CheckvoltagebetweenP5-1andP5-2atthe
leftPWM/DrivePCB(PCB2).Shouldbe20V
AC.BetweenP5-1andP5-3shouldbe40VAC.
Ifnotthecontroltransformer(T5)isfaulty.
ReplacecontroltransformerT5
6.3.8 Intermittent, Interrupted or Partial Operation
NEVER attempt to power-up or operate the power source with any
Gate / Emitter IGBT Plug disconnected from its PWM / Gate Drive
Board. Attempting to operate the power source with any open (un-
plugged) IGBT Gate / Emitter Connector may damage the IGBT and
the plasma cutting torch.
CAUTION
WorksOKat275Aorless-Over
current left side when cutting
over275A.LED9oncontrolboard
illuminated.
LooseorunpluggedconnectoratRightPWM
/DrivePCB(PCB3)
Secureconnector
FaultyRightPWM/DrivePCB
Replace right PWM / Drive PCB P/N
0558038324
CheckvoltagebetweenP5-1andP5-2atthe
rightPWM/DrivePCB(PCB3).Shouldbe20V
AC.BetweenP5-1andP5-3shouldbe40VAC.
Ifnotthecontroltransformer(T7)isfaulty.
ReplacecontroltransformerT7
47
SECTION 6 TROUBLESHOOTING
Problem Possible Cause Action
Power Supply turns o prema-
turelyinthemiddleofthecut.
“ContactorOnsignalisremovedfromunit.
PowersourceisOK.Troubleshootpro-
cesscontroller.
Momentarylossofprimaryinputpower.
Restore and maintain input voltage
within±10%ofnominal.
Faulty condition, indicated by illumination
ofthefaultlamp.
RemovecontrolPCB(PCB1)accesspanel
todeterminethefaultcausingtheshut-
down.Refertofaultlightillumination
section.
Faultycondition,indicatedbytheillumination
ofthepowerresetfaultlamp.
RemovecontrolPCB(PCB1)accesspanel
todeterminethefaultcausingtheshut-
down.Refertofaultlightillumination
section.
Currentsettingtoolow. Increasecurrentsetting
Remotecurrentsignalremovedduringcut. Fixremotecurrentsignal
Problem Possible Cause Action
Output current is unstable and
drifts above or below the set-
ting.
PlacethePANEL/REMOTEswitchinthe“PANEL
position.Adjustcurrentcontrolpot.Ifcurrent
nolongerdrifts,theremotecurrentcontrol
signalisfaulty.
Fixtheremotecurrentcontrolsignalto
operatethePANEL/REMOTEswitchin
the“PANELposition.
Select“PANELonthePANEL/REMOTEswitch
andadjustthecurrentcontrolpot.Thecur-
rentstilldrifts,measurethecurrentreference
signalatTB1-4(+)andTB1-5(-).Ifthesignal
drifts,thecurrentcontrolpotisfaulty.Ifthe
signaldoesnotdrift,theControlPCB(PCB1)
isfaulty.
Replacethecurrentcontrolpot.
Replace the control PCB (PCB1) P/N
0558038312
48
SECTION 6 TROUBLESHOOTING
6.4 Testing and Replacing Components
• ReplaceaPCboardonlywhenaproblemisisolatedtothatboard.
• AlwaysdisconnectpowerbeforeremovingorinstallingaPCboard.
• Donotgrasporpullonboardcomponents.
• Alwaysplacearemovedboardonastaticfreesurface.
• IfaPCboardisfoundtobeaproblem,checkwithyourESABdistribu-
torforareplacement.Providethedistributorwiththepartnumberof
theboardaswellastheserialnumberofthepowersource.
• Donotattempttorepairtheboardyourself.Warrantywillbevoidedif
repairedbythecustomeroranunauthorizedrepairshop.
NOTICE
Power Semiconductor Components
Categoriesofpowersemiconductorsinclude;
• PowerRectiers
• ModulescontainingthefreewheelingdiodesandIGBTs
49
SECTION 6 TROUBLESHOOTING
6.4.1 Power Rectiers and Blocking Diodes
1. Removetopcoverandsidepanels
2. Locateanddisconnectpluginrearofammeter(attached
toneredandoneblackwire)
3. Removepilotarcswitch
4. Disconnectvoltmeter
5. DisconnectorangeandyellowwiresfromrelayK4.
6. Removetwoboltsholdingtheleftsideofthefrontpanel
tothebase.
7. Removethreeboltsholdingacrossthecenterbaseofthe
frontpanel.Theseareaccessedfromunderneath.
8. Removeoneof the boltsholdingtherightsideofthe
front panel to the base. Loosen the second bolt. Of
thesetwobolts,removetheboltontheleftandloosen
theboldontheright.
9. Swingthefrontpanelouttogainaccesstopowerrecti-
ercomponents.
Troubleshooting Procedures –Negative Plate
1. VisuallyinspectfusesF8andF9.Replaceiftheyshowsigns
ofbeingblownormelted.Inspectdiodes.Ifruptured
orburned,replacealldiodesontheNEGPlate.Ifdiodes
appeartobeOK,proceedtonextstep.
LocationofNeg.Plate
LocationoffusesF8andF9
PowerRectiers
Proceduretoaccessbehindthefrontpanel
BlockingDiodes
PowerRectiers
50
SECTION 6 TROUBLESHOOTING
1. CheckohmsbetweenNEGPlateandBRABus.Areading
of2ohmsorlessindicatesoneormoreshorteddiodes.
ReplaceallDiodesonNEGPlate.
2. IffusesF8and/orF9wereopenintherststep,maketwo
moreohmmeterreadings.
 A.MeasureresistancebetweentheNEGPlateand
BR“B”bus.
 B.MeasurebetweenNEGPlateandBR“C”bus.
If resistanceis 2ohms or less in either case, replace allthe
diodesontheNEGPlate.
POSPlateElectrodePlate
DiodeRectierNEGPlate
LocationofPos.Plate
LocationoffusesF8andF9
Troubleshooting POS Plate
1. CheckohmsbetweenPOSPlateandBRABus.Areading
of2ohmsorlessindicatesoneormoreshorteddiodes.
ReplaceallDiodesonPOSPlate.
2. IffusesF8and/orF9wereopenintherststep,maketwo
moreohmmeterreadings.
A.MeasureresistancebetweenthePOSPlateandBR
“B”bus.
B.MeasurebetweenPOSPlateandBR“C”bus.
If resistanceis 2ohms or less in either case, replace allthe
diodesonthePOSPlate.
CathodeLeads
Bus
1. Visuallyinspectforrupturedorburneddiodes.Replace
onlythosedamaged.
2. CheckresistancebetweenElectrodePlateandtheparallel
pigtails(cathodeleads)ofD25andD26.Ifreadingis2
ohmsorless,disconnectleadsfrombusandcheckeach
diode.Replaceonlyshorteddiodes.
Repeat procedure for D27 and D28. Replace only shorted
diodes.
Blocking Diodes D25, D26, D27 and D-28
Troubleshooting Electrode Plate
51
SECTION 6 TROUBLESHOOTING
6.4.2 IGBT / Freewheeling Diode (FWD) Replacement
The emitter and the gate of each aected IGBT must be jum-
pered together to prevent electrostatic damage. Each power
source is supplied with six jumper plugs that mate to the IGBT
Gate / Emitter Plug.
CAUTION
Electrostatic Discharge Hazard
Electrostatic discharge may damage these components.
• Damageisaccumulativeandmayonlyappearasshortenedcompo-
nentlifeandnotasacatastrophicfailure.
• Wearaprotectivegroundstrapwhenhandlingtopreventdamage
toPCBcomponents.
• Alwaysplaceapcboardinastatic-freebagwhennotinstalled.
CAUTION
The module gate plugs must be plugged into the PWM/Gate
Drive PC Board whenever the power source is in operation.
Failure to plug them in will result in damage to the module and
possible damage to the torch.
CAUTION
REMOVAL:
A. Insurethatinputpowerisremovedbytwoactionssuchasadisconnectswitchandremovaloffuses.Tagandlockany
disconnectswitchtopreventaccidentalactivation.
B. Removethetoppaneltogainaccesstothemoduleslocatedinthetoprearofthepowersource.
C. Cleanthecompartmentcontainingthemoduleswithdry,oil-freecompressedair.
D. UnplugthegatedriveleadsconnectingtheIGBTGatestothePWM/GateDrivePCBoard.Inordertopreventdamage
totheIGBT,installjumperplugsintotheIGBTGateDriveConnector.SeeCautionbelow.Jumperplugsaresupplied
witheachpowersource.
E. RemovethecopperbussplatesandbarsconnectedtotheIGBT’s.SavetheM6hardwareconnectingthebusstructure
tothemoduleterminals.Youmayneedtore-usethehardware.Longerhardwarecandamagethemodulebycontact-
ingthecircuitrydirectlybelowtheterminals.
F. RemovetheM6hardwaremountingthemodulestotheheatsink.Savethehardwarebecauseyoumayneedtore-use
it.HardwaretooshortcanstripthethreadsintheAluminumheatsink.Hardwaretoolongcanhitthebottomofthe
holescausingthemodulestohaveinsucientthermalcontacttotheheatsink.Hardwaretoolongortooshortcan
causemoduledamageduetooverheating.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

ESAB EPP-450 Plasma Power Source User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI