ADEMCO 1007 User manual

  • Hello! I am an AI chatbot trained to assist you with the ADEMCO 1007 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
No;1007
DELUXE CONTROL
WITH ENTRY-EXIT DELAY
:‘c
1
No. 1007
No. 1007
* +
‘f
CONTAC
*=NO
CONNKTION
No. 492 or 497
USING RECklARGEABLE ~PbVVER SUPPLY
:,
Terminals
POLARITY
2 Na 6 CELLS
USING -BATTERIES
I,2
Bet I Circuit: Connect to a 6 V.DC rechargeable power suppJy (e.g.
No. 492 or 497) or battery as shown.
OBSERVE POLAR,1 TY.
394
t: Sounding Device: Connect to 6 volt sound? ng dev.i.% ‘such as a No. 5 I8
Horn or a No. AD-8 Bell. Maximum alarm load i,s 2 amperes at 6.voI.t~.
596
Panic Circuit: Any number of open circuit devices with momentary
closure may be wired in paral lel. The No. 219 Emergency Switch is
recommended.
7,8 Protective Circuit: Wire closed circui
OBSERVE POLARITY.
Notes: I .
A single 6 V.DC rechargeable power supp
“?,sep-arate batteries may be used to power
y (such ‘&,No... 492 or 497) or
the bei~i~?$-ki ,protective circuits.
*; “:., ;
2.
If polarity is not observed on the bell d’i’r&‘,it,“the lfuse will blow;
i-f. polarity is not observed on the protecti’ve tit-cui?,‘the unit’will
not set up,
-AL _
1,
3.
When testing “No Delay” circuit al low 60 seconds for unit to “set up”.
r\
Any door opened after -tFGe set up time will provide an instant alarm.
contacts in series as shown,
! I
I, :
136
www.PDF-Zoo.com
4.
Always remove key from control after pt-oper position is obtalned.
5.
When using a mat such as the,.Ademco No. 158 without a mat coupler, add
a 500 ohm, I watf resis$or (Adeticd No. 604) between the two protective
circuit batteries (if used) as shown (resistor not needed if recharge-
able power supply Is used):
Termid
Termiml7
137
www.PDF-Zoo.com
.
+.
TROUBLE :
I. PROTECTIVE CIRCUIT WILL NOT SET UP (WARNING.LIGHT ON PANEL COMES ON).
PROBABLE CAUSE
REMEDY
A. Weak..end-of-l ine 3 volt batteries.
A. Replace~batteries if voltage is
not 3 volts.
B.
Too much resistance in the protective B. Check total resistance of pro-
circuit.
tective loop. A higher than nor-
mal reading (above 300 ohms indi-
cates poor splices or poor window
foil connections).
C. Open or short in protective circuit.
C. Using an ohmmeter, check the resis-
tance.of the protective circuit (see
Part I. Section H for trouble-
shooting aids).
Repair wiring as re-
quired.
TROUBLE : 2. PANEL FUNCTIONS POORLY OR INTERMITTENTLY.
PROBABLE CAUSE REMEDY
A. Dirty or damaged contacts on wafer
A. inspect wafer switch contacts for
switch (lock switch).
T-3
possible damage or corrosion. Clean
contacts with No. 317 spray cleaner
and then spray with a TV tuner
TROUBLE : 3. PANEL DOES NOT OPERATE
PROBABLE CAUSE
I ubr
IN THE “NO DELAY” POS IT
A. Keyswitch has been turned beyond
the extreme right-hand stop.
cant.
ON.
REMEDY
A. Turn
keysw itch to “ON-NO DELAY”
position and remove key. Key should
be removed in this position for
proper operation.
TROUBLE: 4. BELL(S) RINGS BUT DOES NOT GIVE FULL SOUND. (See also Part I, Section HI.
PROBABLE CAUSE
REMEDY
A. Low bell battery or power supply volt- A. Replace battery if voltage mea-
age ( in the case of a rechargeable
sures substantially less than 6
.Ger supply, be sure that the batteries
volts while the bell is operating.
are fully charged
- charge batteries
Al low rechargeable batteries to
for.24 hours without a load).
charge ful ly.
138
www.PDF-Zoo.com
PROBABLE CAUSE
REMEDY
Make changes.in bell wiring.
B.
Bell line run does not conform to
B.
specified procedures (see note at
the end of this section; see also
Part I, Section G).
C.
Improper bell mountina has caused
C.
Inspect mounting and bell dome
position. Correct any binding
or jamming.
clapper to jam.
D.
Short circuit in bell wires (see D.
Replace wires to bell, being care-
Part I, Section G for troubleshooting
ful not to avoid conditions that
bell connection).
will cause short circuits.
Defective bell (if possible, test E.
system with new bell).
Dirty or corroded keyswitch contacts. F.
E.
F.
Replace bell if necessary.
Replace keyswitch with proper
type (see catalog).
WITH SYSTEM ARMED, BELL DOES NOT OPERATE WHEN PROTECTIVE CIRCUIT IS TROUBLE: 5.
BROKEN. (see also Part I, Section HI.
PROBABLE CAUSE
REMEDY
Check each contact for proper
operation. Replace as necessary.
@
A.
B.
Stuck contact in protective circuit
A.
failing to release on entry.
Check connections of bell battery
or power supply to terminals I
and 2 of control panel. Replace
defective batteries if they do not
measure substantially close to
6 volts when the bell or other
sounding device is operating.
Disconnected or discharged bel I bat-
B.
tery or power supply (be sure any re-
chargeable batteries in Recharge-A-
Packs are fu I ly charged. Charge
batteries for 24 hours without a load).
C.
0.
Disconnected, broken, or shorted wires C. Check wiring and repair or re-
between relay panel and bel I. Check
place as needed (see Part I,
wiring between terminals 3 and 4 on
Section G).
control panel to the bell.
Dirtv or corroded kevswitch contacts. D.
Replace keyswitch with proper type
Tsee catalog)
E. Bound bell clapper.
E.
Free or,adjust bell clapper. If
necessary, rep lace bel I.
BELL WILL NOT RESET WHEN SYSTEM I’S DISARMED.
TROUBLE: 6.
139
www.PDF-Zoo.com
A
PROBABLE CAUSE
A. A short circuit exists In the panic
circuit wiring (look for shorts in
the wlres at terminals 5 and 6 of
the control panel).
B. A tripped panic switch is causing
a panic alarm.
TROUBLE:
7. FALSE ALARMS ACCUR DUE TO SWINGERS
Section HI.
PROBABLE CAUSE
A. Swinger or intermittent break in
protective circuit. loop.
REMEDY
A. Use an ohmmeter to locate an
g#ggfmba’le,:~‘;;~~l
terminals 5 and 6; look for an
open circuit across wires). Repair
or replace defective wiring.
8. Reset panic switch.
IN PROTECTIVE CIRCUIT. (See also Part I,
REMEDY
A. Use No. I2 tester or equivalent
to locate faults., (See Part I,
Section H for instructions).
8. Weak batteries or insufficiently
B. Replace batteries if defective.
charged power source supp I y i ng power
Be sure that any rechargeable
to alarm system (check for presence
batteries 1 n. Recharge-A-Packs
of 6 volts at terminals I and 2).
are fu I ly charged (charge bat- ,A
teries for 24 hours without a load)
C. Dirty or corroded keyswitch contacts. C. Replace keyswitch with proper type
(see catalog).
TROUBLE :
8. STEPPING ON FLOOR MAT (IF USED) DOES NOT TRIP THE ALARM.
PROBABLE CAUSE
REMEDY
A. Too much resistance in wires from
floor mat.
A. See Installation Instructions for
notes on floor mats.
B. Improper mat instal lation.
B. See Installation Instructions for
notes on floor mats.
TROUBLE:
9.
A.
WHEN USING A SIREN, HOWLER, OR BLASTER,
PROBABLE CAUSE
Problems exist with particular sound-
ing device and/or module supplying
signal.
TI
iERE IS NO SOUND OUTPUT ON ALARM.
REMEDY
A.
After first makina the checks out-
lined below, see ihe Troubleshooting
Section for the particular sound-
ing devices and modules being used.
140
www.PDF-Zoo.com
PROBABLE CAUSE
REMEDY
‘0
B. Wi ring breaks and/or short circuits
B. Check all wiring to sounding de-
do not permit device(s) to operate. vices.
Repair or replace as re-
quired. In the case of sirens
using driver modules, check for a
blown fuse.
C. Polarity to driver module ‘is re-
- versed at relay pane I.
C. Observe proper polarity. Bear in
mind that terminal 4 on relay
panel is negative (-1 and terminal
3 is positive (+I.
i D. Disconnected or discharged bell bat-
D. Check connections of bell battery
tery or power supply (be sure any re-
or power supply to terminals I
chargeable batteries in Recharge-A-
and 2 of control panel. Rep lace
Packs are f ul I y charges; charge bat-
defective batteries if i-hey do not
teries for 24 hours without a load).
measure substantially close to 6
volts when the bell or other sound-
_ .
ing device is operating.
E. Wires leading from control panel to
E. Makechanges in wiring (see note
sounding devices do not conform to
at the end of this section; see
specified procedures. also Part I, Section G.
TROUBLE: IO. WHEN USING A STROBE LIGHT AS AN ALARM INDICATOR, THE LIGHT FAILS TO
FLASH WHEN ACT I VATED.
PROBABLE CAUSE
REMEDY
A. Polarity reversed to strobe light.
A. Observe proper polarity. To ter-
minal 4 or the relay panel attach
the negative (-1 wike’. To termi-
nal 3, attach the positive (+I wire.
B. Trouble in strobe light circuitry, B. Correct particular trouble as
burned out strobe lamp, breaks in
requ i red.
wiring.
C. Low battery or power supply voltage
C. Replace battery if voltage measures
(in the case of a rechargeable power
less than 6 volts while bell is
supply, be sure that the batteries are operat
ng. Allow rechargeable
ful ly charged -
charge batteries for
24 hours without a load).
batter
NOTES: I. When panel is put in “ON-NO
DELAY” pos
60 seconds to set up (allow
Ing delay t
es to charge fully.
tion, it takes approx
me to run our first).
imately
2. POLARITY MUST BE OBSERVED for all battery connect! ons: termi na I
I t-1, terminal 2 (+I, terminal 7 t-1, terminal 8
(+I.
3. Failure to observe proper polarity on terminals I
sult in blowing the fuse inslde the panel and maki
inoperative.
and 2 will re-
ng the system
141
www.PDF-Zoo.com
NOTE: WIRE RUNS FOR BELLS OR OTHER SOUNDING DEVICES.
For runs of up to 50 feet, use I6 gauge wire..
For runs between 50 and 100 feet, use 14 gauge wire, or
preferably double I6 gauge wlre (thus having four wlres
golng to the soundlng devlce).
For wlre runs of over 100 feet, see Part I, Sectlon G of this
manual.
.
142
www.PDF-Zoo.com
/