EVD ice

Carel EVD ice User manual

  • Hello! I am an AI chatbot trained to assist you with the Carel EVD ice User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
High Efficiency Solutions
EVD ice
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
User manual
Superheat control
for unipolar electronic expansion valve
3
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
WARNINGS
CAREL bases the development of its products on decades of experience
in HVAC, on the continuous investments in technological innovations
to products, procedures and strict quality processes with in-circuit and
functional testing on 100% of its products, and on the most innovative
production technology available on the market. CAREL and its subsidiaries
nonetheless cannot guarantee that all the aspects of the product and the
software included with the product respond to the requirements of the nal
application, despite the product being developed according to start-of-the-
art techniques. The customer (manufacturer, developer or installer of the nal
equipment) accepts all liability and risk relating to the conguration of the
product in order to reach the expected results in relation to the specic nal
installation and/or equipment. CAREL may, based on specic agreements, acts
as a consultant for the positive commissioning of the nal unit/application,
however in no case does it accept liability for the correct operation of the nal
equipment/system.
The CAREL product is a state-of-the-art product, whose operation is specied
in the technical documentation supplied with the product or can be
downloaded, even prior to purchase, from the website www.carel.com.
Each CAREL product, in relation to its advanced level of technology, requires
setup/conguration/programming/commissioning to be able to operate in
the best possible way for the specic application. The failure to complete such
operations, which are required/indicated in the user manual, may cause the
nal product to malfunction; CAREL accepts no liability in such cases.
Only qualied personnel may install or carry out technical service on the
product.
The customer must only use the product in the manner described in the
documentation relating to the product.
In addition to observing any further warnings described in this manual, the
following warnings must be heeded for all CAREL products:
prevent the electronic circuits from getting wet. Rain, humidity and all
types of liquids or condensate contain corrosive minerals that may damage
the electronic circuits. In any case, the product should be used or stored
in environments that comply with the temperature and humidity limits
specied in the manual;
do not install the device in particularly hot environments. Too high
temperatures may reduce the life of electronic devices, damage them and
deform or melt the plastic parts. In any case, the product should be used
or stored in environments that comply with the temperature and humidity
limits specied in the manual;
do not attempt to open the device in any way other than described in the
manual;
do not drop, hit or shake the device, as the internal circuits and mechanisms
may be irreparably damaged;
do not use corrosive chemicals, solvents or aggressive detergents to clean
the device;
do not use the product for applications other than those specied in the
technical manual.
All of the above suggestions likewise apply to the controllers, serial boards,
programming keys or any other accessory in the CAREL product portfolio.
CAREL adopts a policy of continual development. Consequently, CAREL
reserves the right to make changes and improvements to any product
described in this document without prior warning.
The technical specications shown in the manual may be changed without
prior warning.
The liability of CAREL in relation to its products is specied in the CAREL general
contract conditions, available on the website www.carel.com and/or by
specic agreements with customers; specically, to the extent where allowed
by applicable legislation, in no case will CAREL, its employees or subsidiaries
be liable for any lost earnings or sales, losses of data and information, costs of
replacement goods or services, damage to things or people, downtime or any
direct, indirect, incidental, actual, punitive, exemplary, special or consequential
damage of any kind whatsoever, whether contractual, extra-contractual or
due to negligence, or any other liabilities deriving from the installation, use or
impossibility to use the product, even if CAREL or its subsidiaries are warned
of the possibility of such damage.
DISPOSAL
INFORMATION FOR USERS ON THE CORRECT
HANDLING OF WASTE ELECTRICAL AND ELEC-
TRONIC EQUIPMENT (WEEE)
In reference to European Union directive 2002/96/EC issued on 27 January
2003 and the related national legislation, please note that:
1. WEEE cannot be disposed of as municipal waste and such waste must be
collected and disposed of separately;
2. the public or private waste collection systems dened by local legislation must
be used. In addition, the equipment can be returned to the distributor at
the end of its working life when buying new equipment;
3. the equipment may contain hazardous substances: the improper use or
incorrect disposal of such may have negative eects on human health
and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or on the
packaging and on the instruction sheet indicates that the equipment has
been introduced onto the market after 13 August 2005 and that it must
be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the penalties
are specied by local waste disposal legislation.
Warranty on the materials: 2 years (from the date of production, excluding
consumables).
Approval: the quality and safety of CAREL INDUSTRIES products are
guaranteed by the ISO 9001 certied design and production system, as well
as by the marks (*).
CAUTION: separate as much as possible the probe and digital input signal
cables from the cables carrying inductive loads and power cables to avoid
possible electromagnetic disturbance.
Never run power cables (including the electrical panel wiring) and signal
cables in the same conduits.
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
5
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
Content
1. INTRODUCTION 7
1.1 Models ............................................................................................................ 7
1.2 Functions and main characteristics ............................................................. 7
1.3 Accessories ....................................................................................................... 7
2. INSTALLATION 8
2.1 Dimensions - mm (in) ................................................................................... 8
2.2 Assembly on the evaporator ........................................................................ 8
2.3 Application diagrams ...................................................................................... 9
2.4 Wiring description ......................................................................................... 10
2.5 Wiring .............................................................................................................. 10
3. USER INTERFACE 11
3.1 Keypad............................................................................................................. 11
3.2 Display and visualisation ............................................................................ 11
3.3 Programming mode ..................................................................................... 11
3.4 Restore default parameters (factory) ........................................................ 11
4. COMMISSIONING 12
4.1 Commissioning procedure ......................................................................... 12
4.2 Parameters first configuration .................................................................... 12
5. FUNCTIONS 13
5.1 Control ............................................................................................................. 13
5.2 Special control function: smooth lines ..................................................... 14
5.3 Service parameters ....................................................................................... 14
6. PROTECTORS 15
6.1 Protectors ........................................................................................................ 15
7. PARAMETERS TABLE 17
8. NETWORK CONNECTION 18
8.1 RS485 serial configuration .......................................................................... 18
8.2 Network connection for commissioning via PC .................................... 18
8.3 Visual parameter manager .......................................................................... 18
8.4 Restore default parameters ......................................................................... 19
8.5 Setup by direct copy ..................................................................................... 19
8.6 Setup using configuration file ....................................................................20
8.7 Read the configuration file on the controller ........................................20
8.8 Variables accessible via serial connection .............................................. 21
8.9 Control states ................................................................................................. 22
8.10 Special control states ....................................................................................23
9. ALARMS 24
9.1 Types of alarms ..............................................................................................24
9.2 Probe alarms .................................................................................................. 24
9.3 Control alarms ...............................................................................................24
9.4 Valve emergency closing procedure .........................................................24
9.5 Network alarm ............................................................................................... 24
9.6 Alarm table .................................................................................................... 25
10. TROUBLESHOOTING 25
11. TECHNICAL SPECIFICATIONS 26
7
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
1. INTRODUCTION
EVD ice is an electronic superheat controller for Carel unipolar expansion
valves. EVD ice has been specially designed to be installed near the valve,
directly on the refrigerant circuit, simplifying installation and making
electronic expansion valve technology available directly on board the
unit.
The plastic cover material on EVD ice guarantees total protection,
allowing the controller to operate in particularly dicult environmental
conditions, such as low temperatures and high humidity (condensation).
EVD ice can be installed directly on a unit cooler/evaporator inside a cold
room.
The controller is already tted with sensors, signal and power cables:
to complete the system, simply select the most suitable valve body
and pressure transducer for the required cooling capacity from the
compatible Carel product range.
EVD ice controls refrigerant superheat and optimises refrigerant circuit
eciency. It allows considerable system exibility, being compatible
with various types of refrigerants, in applications with refrigerators and
chiller/air-conditioners. It features low superheat protection (LowSH),
high evaporation pressure (MOP) and low evaporation pressure (LOP)
functions.
The device also has a user interface that displays the instant superheat
value at all times, signals any alarms, and above all can be used to set the
operating parameters.
When installing the controller, only three initial parameters are required
to start controlling the valve in the system:
- type of refrigerant
- operating mode (cold room, showcase, etc.)
- superheat set point.
EVD ice can easily be accessed via an RS485 serial connection (Modbus
protocol), for supervision of operating parameters and alarms in real time.
The serial connection can also be used to set the operating parameters
over a remote connection; in this case, combination with other Carel
controllers is recommended (supervisors and cold room controllers).
1.1 Models
P/N Description
EVDM011R3* EVD ice 115/230 V, E2V stator, display
EVDM011R1* EVD ice 115/230 V, E2V stator, display, Ultracap module
connector
EVDM011R4* EVD ice 115/230 V, E3V stator, display
EVDM011R2* EVD ice 115/230 V, E3V stator, display, Ultracap module
connector
(*): 0/1=single/multiple package (10 pcs)
Tab. 1.a
1.2 Functions and main characteristics
In summary:
superheat control with LowSH, MOP, LOP functions;
compatibility with various types of refrigerants;
guided setup procedures rst, entering just three parameters on the
user interface: refrigerant (Gas), type of control (Mode) and superheat
set point (Superheat);
activation/deactivation of control via digital input or remote control
via serial connection;
controller and valve power supply incorporated (230 V/115 V);
RS485 serial communication incorporated (Modbus protocol);
IP65/IP67;
operating conditions: -30T40C° (-22T104°F);
compatible with Carel E2V and E3V single-pole valves.
From the software revision 1.7 the Smooth lines function has been
introduced.
1.3 Accessories
Ratiometric pressure probe P/N SPKT0013P0 (-1 to 9.3 bars)
The ratiometric pressure probe specied as default for assembly is P/N
SPKT0013P0, with an operating range from -1 to 9.3 barg. Alternatively,
other probes can be installed, setting the corresponding parameter
accordingly. See the “Functions” chapter.
Fig. 1.a
P/N Type Photo nr.
SPKT0053P0 -1…4.2 barg 1
SPKT0013P0 -1…9.3 barg
SPKT0043P0 0…17.3 barg
SPKT0033P0 0…34.5 barg
SPKT00B6P0 0…45 barg
SPKT00E3P0 -1…12.8 barg
SPKT00F3P0 0…20.7 barg
SPKT00G1S0 0…60 barg 2
SPKT00L1S0 0…90 barg
Tab. 1.b
Unipolar valve body
The valve body, to be purchased separately, is assembled using the stator
supplied with EVD ice. For the part numbers, see the CAREL product
catalogue.
Fig. 1.b
Ultracap module (P/N EVDMU**R**)
The module guarantees temporary power to the driver in the event of
power failures, for enough time to immediately close the connected
electronic valve. It avoids the need to install a solenoid valve. The module
is made using Ultracap storage capacitors, which ensure reliability in
terms of much longer component life than a module made with lead
batteries.
Fig. 1.c
1 2
8
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
2. INSTALLATION
2.1 Dimensions - mm (in)
79.4 (3.1)
92.4 (3.6)
4.5 (0.2)
170 (6.7)
45.5 (1.8)
61.3 (2.4)
40.7(1.6)
19.6 (0.8)
~230 (9.1)
Cable (*) Length (±5%)
Power supply 500 (19.7)
RS485 500 (19.7)
Pressure probe 800 (31.5) --> E2V
1800 (70.9) --> E3V
NTC probe 1800 (70.9)
E2V/ E3V valve 600 (23.6)
Ultracap 100 (3.9)
(*)= for standard CAREL part numbers
Fig. 2.a
2.2 Assembly on the evaporator
Important:
install EVD ice on the evaporator away from the places where
ice forms;
connect the power and serial cables in the IP65 junction box;
for assembly of the E2V/ E3V valve, see the “ ExV system” guide
(+030220810).
Ratiometric pressure transducer
Evaporator
Solenoid
valve
Liquid
indicator
Filter
Liquid
separator
M
Condenser
EVD ice
E2V/ E3V Unipolar
expansion valve
Evaporator unit
NTC temp. probe
Compressor
P T
WALL
Fig. 2.b
EVD ice can be installed directly on the evaporator. Mark the position and
drill the holes (Ø <4.5 mm). Then tighten the fastening screws.
GAS Type
Mode
Super Heat
Fig. 2.c
9
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
2.3 Application diagrams
WITH SOLENOID VALVE
COLD ROOM
IN
COLD ROOM
OUT
COLD ROOM
OUT
Evaporator
L
N
ON / OFF
EVD ICE
driver
230 V
230 V input
Regulator
P T
EEV
M
Condenser
Electrical panel
Compressor
Condenser
unit
Evaporator
unit
Solenoid
valve
IP65
L
N
Fig. 2.d
WITHOUT SOLENOID VALVE, WITH ULTRACAP MODULE
COLD ROOM
IN
COLD ROOM
OUT
COLD ROOM
OUT
Evaporator
L
N
ON / OFF
EVD ICE
driver
230 V
230 V input
Regulator
P T
EEV
Condenser
Electrical panel
Compressor
Condenser
unit
Evaporator
unit
IP65
L
N
EVD ICE
ULTRACAP
Fig. 2.e
10
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
2.4 Wiring description
The driver for superheat control requires the use of an evaporation pressure
probe S1 and suction temperature probe S2, which will be tted downstream
of the evaporator, and a digital input to trigger control. Alternatively, the signal
to trigger control can be sent via a remote serial connection.
Note: input S1 is programmable. See the “Functions” chapter
The following are already wired on EVD ice:
pressure probe and temperature probe cables;
electronic expansion valve stator;
Ultracap module connection cable (on models where featured);
power and serial line cables.
The power and serial line connections are identied by the colours of
the wires.
Note: for probe installation see “Guide to EEV system, (+03022811).
RS485
Modbus®
CVSTDUM0R0
pCO
shield shield
PC
VPM
digital input to start
the regulation
230 Vac
ratiometric
pressure
transducer
Valve stator
0,3 Nm
CAREL E V/ E V
² ³
unipolar valve
NTC
bianco/ white - Tx/Rx+
nero/ black - Tx/Rx-
marrone/ brown - L
blu/ blue - N
nero/ black - DI
S2
ULTRACAP
Module
S1
Non rimuovere
il cappuccio
di protezione A!
Do not remove
the protection cap A!
A
verde/ green - GND
GAS Type
Mode
Super Heat
fascia elastica/ elastic band
fascetta di ssaggio/ fastening band
pasta conduttiva/ conductive cream
B
A
D
1
2
EF
C
Fig. 0.a
Rif Cable Description
A ExV Unipolar electronic valve connection
B Ultracap Ultracap module connection (accessory)
C Probe S2 NTC temperature probe
D probe S1 Ratiometric pressure probe
E Power supply
L: brown Phase 230 V
N: blue Neutral 230 V
DI: black 230 V digital input to enable control
F Serial
Tx/ Rx +: white RS485 connection
Tx/ Rx -: black
GND: green
1 - Computer for conguration
2 - USB– RS485 converter (for computer)
Tab. 0.a
2.5 Wiring
For installation, proceed as shown below, with reference to the wiring
diagrams and the technical specications table:
1. connect the pressure probe that suits the refrigerant. For details on
refrigerant ---> suggested pressure probe, see the chapter on
“Commissioning”;
2. connect the power cable and the digital input cable: for the maximum
length, see the technical specications;
3. power on the driver: the display will light up, and the driver will await the
commissioning parameters. See the chapter on “Commissioning”;
4. program the driver, if necessary: see the “User interface chapter.
Note: if connecting to a serial network, see the previous diagram for
details on connecting the shield to earth.
Installation environment
Important: avoid installing the drivers in environments with the
following characteristics:
strong vibrations or knocks;
exposure to aggressive and polluting atmospheres (e.g.: sulphur
and ammonia fumes, saline mist, smoke) to avoid corrosion and/or
oxidation;
strong magnetic and/or radio frequency interference (therefore avoid
installing the devices near transmitting antennae);
exposure of the drivers to direct sunlight and to the elements in
general.
Important: the following warnings must be observed when
connecting the drivers:
if the driver is used in a way that is not specied in this user manual,
protection cannot be guaranteed;
incorrect power connections may seriously damage the driver;
separate as much as possible (at least 3 cm) the probe and digital input
cables from cables to electrical loads, to avoid possible electromagnetic
disturbance. Never run power cables (including the electrical panel
cables) and probe signal cables in the same conduits;
do not run probe signal cables in the immediate vicinity of power
devices (contactors, circuit breakers, etc.). Reduce the path of probe
cables as much as possible, and avoid spiral paths that enclose power
devices;
*EVD ice is a controller to be incorporated into the nal equipment; it
must not be wall-mounted;
* DIN VDE 0100: protective separation must be guaranteed between
the SELV circuits (Safety Extra Low Voltage) and the other circuits. The
requirements of DIN VDE 0100 must be complied with. To prevent
disruption of the protective separation (between the SELV circuits and
the other circuits) ensure additional fastening near the terminations.
This additional fastening must secure the insulation and not the wires.
11
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
3. USER INTERFACE
The user interface comprises the two-digit display and keypad with three
buttons that, pressed alone or in combination, are used to perform all the
conguration and programming operations on the driver.
GAS Type
Mode
Super Heat
1
3
2
1 2
4
Fig. 3.a
Key
1 Parameter label (for commissioning/setup)
2 Keypad
3 LED status digital input start/stop control
blink/OFF = DI closed/open
4 Two-digit display
(*) when digital input is closed the LED blinks and control is active.
During commissioning/setup, the parameter label shows the meaning
of the segments displayed in the rst digit, corresponding to the three
parameters being set:
A. GAS Type: type of refrigerant;
B. Mode: operating mode;
C. Superheat: superheat set point.
See the “
Commissioning
chapter.
GAS Type
Mode
Super Heat
GAS Type
Mode
Super Heat
GAS Type
Mode
Super Heat
A. Refrigerant B. Mode (operating mode) C. Superheat set point
3.1 Keypad
Key Description
UP / DOWN
Increases/decreases the value of the set point or
other selected parameter
PRG/Set
At the end of the commissioning procedure, if
pressed for 2 s, exits the menu and control starts;
Enter/ exit programming mode, saving the
parameters;
Reset E8 alarm.
Tab. 2.a
3.2 Display and visualisation
During normal operation, the two-digit display shows the superheat
measure and any alarms.
The display interval for the superheat value is -5 to 55 K (-9 to 99 °F).
In general, values between -99 and 999 are displayed as follows:
1. values from 0 to 10 are displayed with decimal point and decimals;
2. values greater than 99 are displayed in two steps:
- rst, the hundreds, followed by “H”
- then the tens and units.
3. values less than -9 are displayed in two steps:
- rst the “-“sign;
- then the tens and units.
GAS Type
Mode
Super Heat
GAS Type
Mode
Super Heat
123 --->
GAS Type
Mode
Super Heat
GAS Type
Mode
Super Heat
-99 --->
Fig. 3.b
Note: the decimal point in the digit on the right indicates the status
of the digital start/stop adjustment input. With the input closed the dot
is lit ashing.
3.3 Programming mode
The parameters can be modied using the front keypad.
Important: modify the control parameters, ONLY AFTER having
completed the guided commissioning procedure, described in chapter 4.
Modifying the Service parameters
The Service parameters include, in addition to the parameters for the
conguration of input S1, those corresponding to the network address,
probe readings, protectors and manual positioning. See the parameter
table.
Procedure:
1. press UP and DOWN together and hold for more than 5 s: the rst
parameter is displayed: P1 = probe S1 reading;
2. press UP/ DOWN until reaching the desired parameter;
3. press PRG/ Set to display the value;
4. press UP/ DOWN to modify the value;
5. press PRG/ Set to conrm and return to the parameter code;
6. repeat steps 2 to 5 to modify other parameters;
7. (when the parameter code is displayed) press PRG/Set and hold for more
than 2 s to exit the parameter setting procedure.
GAS Type
Mode
Super Heat
Fig. 3.c
Note: if no button is pressed, after around 30 s the display
automatically returns to standard visualisation.
3.4 Restore default parameters (factory)
The driver can be reset to the default parameter values.
Procedure:
when the display is on standby, press all three buttons together . After
5 seconds, the display shows “rS”. The reset procedure can be conrmed
within 10 seconds, by pressing PRG/SET for 3 seconds. If no button is
pressed during this time, the procedure will be cancelled.
At the end the display shows two hyphens and then awaits the
commissioning parameters.
12
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
4. COMMISSIONING
Important: if the refrigerant is not available among the refrigerant
parameter options, contact CAREL service to:
1. conrm that the system: (c.pCO/Ultracella,...)+ EVD ice + CAREL electronic
expansion valve is compatible with the desired refrigerant (Gas
type=custom);
2. identify the values that dene the custom refrigerant and enter them for
parameters: “Dew a…f high/low” . See the variables accessible via
serial connection.
4.1 Commissioning procedure
Once the electrical connections have been completed (see the chapter
“Installation”) and the power supply has been connected, the operations
required for commissioning the driver depend on the type of interface
used, however essentially involve setting just 3 parameters: refrigerant,
functioning mode, superheat setpoint.
Important:
until the commissioning procedure has been completed, control
will not be active;
(only during commissioning) changing the gas involves changing
the value of the ratiometric probe parameter.
After powering up the driver, the display lights and the driver waits the
control parameters, indicated by the hyphens. The default parameters
are:
1. Refrigerant = R404A;
2. Type of control = multiplexed showcase/cold room
3. Superheat set point = 11 K.
Procedure:
GAS Type
Mode
Super Heat
1. The controller displays the bar at the top: refrigerant (GAS Type);
GAS Type
Mode
Super Heat
2. Press PRG/Set: the refrigerant setting is shown = 3: R404A
GAS Type
Mode
Super Heat
3. Press UP/Down to change the value
GAS Type
Mode
Super Heat
4. Press PRG/Set to save and return to the refrigerant parameter code
(bar at the top)
GAS Type
Mode
Super Heat
5. Press Down to move to the next parameter: Mode, indicated by the
bar in the middle;
6. Repeat steps 2,3,4,5, to set the values of the other parameters: Mode,
Superheat set point;
GAS Type
Mode
Super Heat
7. Press PRG/Set for 2 seconds to exit the commissioning procedure
and start control. The standard display is shown.
4.2 Parameters rst conguration
Important: ONLY DURING commissioning, changing the gas
involves changing the value of the ratiometric probe parameter; if not
specied in the table, the type of ratiometric probe is -1...9.3 barg.
Parameter/ description Def.
Gas Type = refrigerant
0 Custom
1 R22 15 R422D 28 R1234ze(-1...4.2 barg)
2 R134a 16 R413A 29 R455A (-1...12.8 barg)
3 R404A 17 R422A 30 R170 (0...17.3 barg)
4 R407C 18 R423A 31 R442A (-1...12.8 barg)
5 R410A 19 R407A 32 R447A (-1...12.8 barg)
6 R507A 20 R427A 33 R448A
7 R290 21 R245FA 34 R449A
8 R600(-1...4.2 barg) 22 R407F 35 R450A (-1...4.2 barg)
9 R600a (-1...4.2 barg) 23 R32 (0...17.3 barg) 36 R452A (-1...12.8 barg)
10 R717 24 HTR01 37 R508B (-1...4.2 barg)
11 R744 (0...45 barg) 25 HTR02 38 R452B
12 R728 26 R23 39 R513A (-1...4.2 barg)
13 R1270 27 R1234yf 40 R454B
14 R417A 41 R458A
3 =
R404A
Tab. 4.a
Note: if the refrigerant is not available among the refrigerant
options, “GAS Type=refrigerant”:
1. set any refrigerant (for example R404);
2. select the type of operating mode (Mode), the superheat set point
and complete the commissioning procedure;
3. use the VPM program (Visual Parameter Manager, see the chapter
“Network connection” ) and set the refrigerant type “0= Custom and
the parameters “Dew a...f high/low” which dene the refrigerant (see
variables accessible via serial connection);
4. start control, for example by closing the digital input contact to
enable operation.
Mode = operating mode
1 Multiplexed cabinet/cold room
2 Air-conditioner/chiller with plate heat exchanger
3 Air-conditioner/chiller with tube bundle heat exchanger
4 Air-conditioner/chiller with nned coil heat exchanger
5 Reserved
6 Reserved
7 Cabinet/cold room with subcritical (R744) CO2
1 = Mul-
tiplexed
cabinet/
cold room
Superheat setpoint 11 K(20°F)
Tab. 4.b
Note: consider the unit of measure (°C/°F) when setting the
superheat setpoint (Si parameter).
13
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
5. FUNCTIONS
A low superheat temperature in fact corresponds to a situation of probable
instability due to the turbulent evaporation process approaching the
measurement point of the probes. The expansion valve must therefore
be controlled with extreme precision and a reaction capacity around
the superheat set point, which will almost always vary from 3 to 14 K.
Set point values outside of this range are quite infrequent and relate to
special applications.
P
E
V
S
F
L
M
T
CP
C
EEV
S1
S2
Fig. 5.a
Key
CP compressor EEV electronic expansion valve
C condenser V solenoid valve
L liquid receiver E evaporator
F dewatering lter P pressure probe (transducer)
S liquid indicator T temperature probe
For the wiring, see
“Wiring description
.
5.1 Control
EVD ice is a superheat controller. The type of refrigeration unit can be
selected using the “Operating mode parameter.
Parameter/description Def.
Operating mode
1 Multiplexed cabinet/cold room
2 Air-conditioner/chiller with plate heat exchanger
3 Air-conditioner/chiller with tube bundle heat exchanger
4 Air-conditioner/chiller with nned coil heat exchanger
5 Reserved
6 Reserved
7 Banco frigo/cella con CO2 (R744) sub-critica
1 = multiple-
xed cabinet/
cold room
Tab. 5.a
Based on the operating mode setting , the driver automatically sets a
series of control parameters.
Operating mode PID: pro-
port. gain
PID: integra-
tion time
Superheat
set point
LowSH protection LOP protection MOP protection
threshold Integra-
tion time
threshold Integra-
tion time
thre-
shold
Integra-
tion time
1 Multiplexed cabinet/cold room 15 150 11 5 15 -50 0 50 20
2 Air-conditioner/chiller with plate heat exchanger 3 40 6 2 2,5 -50 4 50 10
3 Air-conditioner/chiller with tube bundle heat exchanger 5 60 6 2 2,5 -50 4 50 10
4 Air-conditioner/chiller with nned coil heat exchanger 10 100 6 2 10 -50 10 50 20
5 Reserved - - - - - - - - -
6 Reserved - - - - - - - - -
7 Banco frigo/cella con CO2 (R744) sub-critica
20 400 13 7 15 -50 0 50 20
Tab. 5.b
Superheat
The primary purpose of the electronic valve is ensure that the ow-rate
of refrigerant that ows through the nozzle corresponds to the ow-rate
required by the compressor. In this way, the evaporation process will take
place along the entire length of the evaporator and there will be no liquid
at the outlet (consequently in the branch that runs to the compressor). As
liquid is not compressible, it may cause damage to the compressor and even
breakage if the quantity is considerable and the situation lasts some time.
Superheat control
The parameter that the control of the electronic valve is based on is
the superheat temperature, which eectively tells whether or not there
is liquid at the end of the evaporator. The superheat temperature is
calculated as the dierence between: superheated gas temperature
(measured by a temperature probe located at the end of the evaporator)
and the saturated evaporation temperature (calculated based on the
reading of a pressure transducer located at the end of the evaporator and
using the Tsat(P) conversion curve for each refrigerant).
Superheat =
Superheated gas
temperature
(*)
Saturated evaporation
temperature
(*) suction
If the superheat temperature is high it means that the evaporation
process is completed well before the end of the evaporator, and therefore
ow-rate of refrigerant through the valve is insucient. This causes a
reduction in cooling eciency due to the failure to exploit part of the
evaporator. The valve must therefore be opened further. Vice-versa, if
the superheat temperature is low it means that the evaporation process
has not concluded at the end of the evaporator and a certain quantity
of liquid will still be present at the inlet to the compressor. The valve
must therefore be closed further. The operating range of the superheat
temperature is limited at the lower end: if the ow-rate through the valve
is excessive the superheat measured will be near 0 K. This indicates the
presence of liquid, even if the percentage of this relative to the gas cannot
be quantied. There is therefore un undetermined risk to the compressor
that must be avoided. Moreover, a high superheat temperature as
mentioned corresponds to an insucient ow-rate of refrigerant. The
superheat temperature must therefore always be greater than 0 K and
have a minimum stable value allowed by the valve-unit system.
14
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
PID parameters
Superheat control uses a PID algorithm. The control output is calculated
as the sum of separate contributions: proportional and integral.
the proportional action opens or closes the valve proportionally to
the variation in the superheat temperature. Thus the greater the K
(proportional gain) the higher the response speed of the valve. The
proportional action does not consider the superheat set point, but
rather only reacts to variations. Therefore if the superheat value does
not vary signicantly, the valve will essentially remain stationary and
the set point cannot be reached;
the integral action is linked to time and moves the valve in proportion
to the deviation of the superheat value from the set point. The greater
the deviations, the more intense the integral action; in addition, the
lower the value of Ti (integral time), the more intense the action
will be. The integral time, in summary, represents the intensity of the
reaction of the valve, especially when the superheat value is not near
the set point.
See the “EEV system guide” +030220810 for further information on
calibrating PID control.
Par. Description Def. Min. Max. UoM
- Superheat set point
11(20)
LowSH: threshold 55 (99) K(°F)
CP
PID proport. gain 15 0 800 -
ti
PID integral time 150 0 999 s
Note: when selecting the type of Mode, the PID control values
suggested by CAREL will be automatically set for each application.
Protector control parameters
See the chapter “Protectors”.
5.2 Special control function: smooth lines
Note: the Smooth_line parameter is only accessible via the
supervisor.
The smooth lines function optimises evaporator capacity based on actual
cooling demand, allowing more eective and stable control. The function
completely eliminates traditional on/o control cycles, modulating
the temperature exclusively using the electronic valve; superheat set
point is controlled through a precise PI control algorithm based on
the actual control temperature. The master controller (connected via
serial to EVD mini), through dynamic management of the Smooth_line
parameter, modies the superheat set point for management of the
electronic expansion valve, from a minimum (SH_SET) to a maximum
(SH_SET + Smooth_line): this consequently acts directly on the PID
control algorithm that modies the valve position. This is useful when
the control temperature approaches the set point; the Smooth_line
parameter is used to prevent the valve from closing, by reducing the
evaporators cooling capacity. In order to use this function, the digital
input must be congured as BACKUP. The Smooth_line parameter thus
allows the control set point to be adjusted instantly. In the event where
there is no network connection, the Smooth_line parameter is reset so as
to resume normal control (START/STOP from digital input and SH_SET as
the superheat set point). The main eects are:
no swings in temperature and superheat due to the set point being
reached;
stable temperature and superheat control;
maximum energy savings due to load stabilisation.
Par. Description Def. Min. Max. U.M.
di
DI conguration
1=start/stop
2=control backup
1 1 2 -
Smooth_line
A: superheat set point
oset for smooth lines
0 -99(-55) 99(55) K/°F
t
Temp. set
SH set
SH_set+
Smooth_line
t
Fig. 5.b
Key
SH set Superheat set point t time
Temp.set Temperature set point
Note: the temperature setting based on the corresponding set
point is managed by the master controller, while superheat control is
managed by the EVD ice.
5.3 Service parameters
The other conguration parameters, to be set where necessary before
starting the controller, concern :
the type of ratiometric pressure probe;
the serial address for network connection;
the type of unit of measure;
enabling change in type of control (Mode);
the number of steps (480/960) to control valve position.
Type of pressure probe (par. S1)
S1 is used to select the type of ratiometric pressure probe.
Par. Description Def. Min. Max. UoM
S1
type of probe S1
1 = -1…4.2 barg
2 = 0.4…9.3 barg
3 = -1…9.3 barg
4 = 0…17.3 barg
5 = 0.85…34.2 barg
6 = 0…34.5 barg
7 = 0…45 barg
8 = -1…12.8 barg
9 = 0…20.7 barg
10 = 1.86…43.0 barg
11 = Reserved
12 = 0...60 barg
13 = 0...90 barg
3 1 13 -
Note: when setting the probe type, the maximum and minimum
limits for the pressure alarm are automatically dened. See Variables
aaccessible via serial connection”.
Network address (par. n1)
See the “Network connection” chapter.
Unit of measure (par. Si)
It is possible to select the measure system of the driver:
international (°C, K, barg);
imperial (°F, psig).
Par. Description Def. Min. Max. UoM
Si Unit of measure: 1=°C/K/barg; 2=°F/psig 1 1 2 -
Note: the unit of measure K relates to degrees Kelvin adopted for
measuring the superheat and the related parameters.
When changing the unit of measure, all the values of the parameters
saved on the driver and all the measurements read by the probes will
be recalculated. This means that when changing the units of measure,
control remains unaltered.
15
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
Example 1: The pressure read is 20 barg this will be immediately
converted to the corresponding value of 290 psig.
Example 2: The superheat set point parameter set to 10 K will be
immediately converted to the corresponding value of 18 °F.
Access to the Mode (operating mode) parameter (par. IA)
To avoid accidental modication of the controller’s operating mode, it is
possible to disable the access to the corresponding parameter.
Par. Description Def. Min. Max. UoM
IA Enable operating mode modication
0/1 = yes/ no
0 0 1 -
Number of control steps (par. U3)
Total number of steps between the valve fully closed and fully open
position
Par. Description Def. Min. Max. UoM
U3 Number of valve control steps
1 / 2 = 480/960 steps
1 1 2 -
Digital input
The function of the digital input can be set by parameter:
Par. Description Def. Min. Max. UoM
di DI conguration
1=Start/Stop regulation
2=Regulation backup
1 1 2 -
Start/stop regulation:
digital input closed: control active;
digital input open: control in standby (see the paragraph “Control
states”).
Important: this setting excludes activation/deactivation of control
via the network. See the following function.
Regulation backup: if there is a network connection and communication
fails, the driver checks the status of the digital input to determine whether
control is active or in standby.
6. PROTECTORS
These are additional functions that are activated in specic situations that
are potentially dangerous for the unit being controlled. They feature an
integral action, that is, the action increases gradually when moving away
from the activation threshold. They may add to or overlap (disabling)
normal PID superheat control. By separating the management of these
functions from PID control, the parameters can be set separately, allowing,
for example, normal control that is less reactive yet much faster in
responding when exceeding the activation limits of one of the protectors.
6.1 Protectors
The protectors are 3:
LowSH, low superheat;
LOP, low evaporation temperature;
MOP, high evaporation temperature;
The protectors have the following main features:
activation threshold: depending on the operating conditions of the
controlled unit, this is set in Service programming mode;
integration time, which determines the intensity (if set to 0, the
protector is disabled): set automatically based on the type of main
control;
alarm, with activation threshold (the same as the protector) and
timeout (if set to 0 disables the alarm signal).
Note: The alarm signal is independent from the eectiveness of
the protector, and only signals that the corresponding threshold has
been exceeded. If a protector is disabled (null integration time), the
relative alarm signal is also disabled.
Each protector is inuenced by the proportional gain parameter (CP) of
PID superheat control. The higher is the value of CP, the more intensely
the protection will react.
Characteristics of the protectors
Protection Reaction Reset
LowSH Intense closing Immediate
LOP Intense opening Immediate
MOP Moderate closing Controlled
Tab. 6.a
Reaction: summary description of the type of action in controlling the
valve.
Reset: summary description of the type of reset following the activation
of the protector. Reset is controlled to avoid swings around the activation
threshold or immediate reactivation of the protector.
Note: all alarms are generated after a xed delay, as shown in the table:
Protectors Delay (s)
LowSH 300
LOP 300
MOP 600
LowSH (low superheat)
The protector is activated so as to prevent the low superheat from
causing the return of liquid to the compressor.
Par. Description Def. Min. Max. U.M.
C1 LowSH protection: threshold 5(9) -5(-9) Set point
superheat
K(°F)
C2 LowSH protection: integration time 15 0 800 s
When the superheat value falls below the threshold, the system enters low
superheat status, and the intensity with which the valve is closed is increased:
the more the superheat falls below the threshold, the more intensely the
valve will close. The LowSH threshold must be less than or equal to the
superheat set point. The low superheat integration time indicates the
intensity of the action: the lower the value, the more intense the action.
The integration time is set automatically based on the type of main
control.
t
t
t
OFF
ON
A
OFF
ON
Low_SH
Low_SH_TH
SH
D
B
Fig. 6.a
key:
SH Superheat A Alarm
Low_SH_TH Low_SH protection threshold D Alarm delay
Low_SH Low_SH protection t Time
B Alarm automatic reset
16
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
LOP (low evaporation pressure)
LOP= Low Operating Pressure
The LOP protection threshold is applied as a saturated evaporation
temperature value so that it can be easily compared against the technical
specications supplied by the manufacturers of the compressors. The
protector is activated so as to prevent too low evaporation temperatures
from stopping the compressor due to the activation of the low pressure
switch. The protector is very useful in units with compressors on board
(especially multi-stage), where when starting or increasing capacity the
evaporation temperature tends to drop suddenly. When the evaporation
temperature falls below the low evaporation temperature threshold,
the system enters LOP status and is the intensity with which the valve is
opened is increased. The further the temperature falls below the threshold,
the more intensely the valve will open. The integration time indicates the
intensity of the action: the lower the value, the more intense the action.
Par. Description Def. Min. Max. U.M.
C3 LOP protection: threshold -50
(-58)
-85
(-121)
MOP protec.:
threshold
C(°F)
C4 LOP protection: integration time 0 0 800 s
The integration time is set automatically based on the type of main
control.
Note:
the LOP threshold must be lower then the rated evaporation
temperature of the unit, otherwise it would be activated unnecessarily,
and greater than the calibration of the low pressure switch, otherwise
it would be useless. As an initial approximation it can be set to a value
exactly half-way between the two limits indicated;
the protector has no purpose in multiplexed systems (showcases)
where the evaporation is kept constant and the status of the individual
electronic valve does not aect the pressure value;
the LOP alarm can be used as an alarm to highlight refrigerant leaks by
the circuit. A refrigerant leak in fact causes an abnormal lowering of the
evaporation temperature that is proportional, in terms of speed and
extent, to the amount of refrigerant dispersed.
t
t
t
OFF
ON
ALARM
OFF
ON
LOP
LOP_TH
T_EVAP
D
B
Fig. 6.b
Key:
T_EVAP Evaporation temperature D Alarm timeout
LOP_TH Low evaporation temperature protection ALARM Alarm
LOP LOP protection t Time
B Automatic alarm reset
MOP (high evaporation pressure)
MOP= Maximum Operating Pressure.
The MOP protection threshold is applied as a saturated evaporation
temperature value so that it can be easily compared against the technical
specications supplied by the manufacturers of the compressors. The
protector is activated so as to prevent too high evaporation temperatures
from causing an excessive workload for the compressor, with consequent
overheating of the motor and possible activation of the thermal protector.
The protector is very useful in self-contained units if starting with a high
refrigerant charge or when there are sudden variations in the load. The
protector is also useful in multiplexed systems (showcases), as allows all
the utilities to be enabled at the same time without causing problems
of high pressure for the compressors. To reduce the evaporation
temperature, the output of the refrigeration unit needs to be decreased.
This can be done by controlled closing of the electronic valve, implying
superheat is no longer controlled, and an increase in the superheat
temperature. The protector will thus have a moderate reaction that tends
to limit the increase in the evaporation temperature, keeping it below the
activation threshold while trying to stop the superheat from increasing
as much as possible. Normal operating conditions will not resume based
on the activation of the protector, but rather on the reduction in the
refrigerant charge that caused the increase in temperature. The system
will therefore remain in the best operating conditions (a little below the
threshold) until the load conditions change.
Par. Description Def. Min. Max. U.M.
C5 MOP protection threshold 50
(122)
Protection LOP:
threshold
200
(392)
C(°F)
C6 MOP protection integration time 20 0 800 s
The integration time is set automatically based on the type of main
control.
When the evaporation temperature rises above the MOP threshold, the
system enters MOP status, superheat control is interrupted to allow the
pressure to be controlled, and the valve closes slowly, trying to limit the
evaporation temperature. As the action is integral, it depends directly on
the dierence between the evaporation temperature and the activation
threshold. The more the evaporation temperature increases with
reference to the MOP threshold, the more intensely the valve will close.
The integration time indicates the intensity of the action: the lower the
value, the more intense the action.
t
t
t
t
OFF
ON
ALARM
OFF
ON
PID
OFF
ON
MOP
MOP_TH - 1
MOP_TH
T_EVAP
D
Fig. 6.c
Key:
T_EVAP Evaporation temperature MOP_TH MOP threshold
PID PID superheat control ALARM Alarm
MOP MOP protection t Time
D Alarm timeout
Important: the MOP threshold must be greater than the rated
evaporation temperature of the unit, otherwise it would be activated
unnecessarily. The MOP threshold is often supplied by the manufacturer
of the compressor. It is usually between 10 °C and 15 °C.
If the closing of the valve also causes an excessive increase in the suction
temperature (S2) above the set threshold – set via parameter (C7), not
on the display - the valve will be stopped to prevent overheating the
compressor windings, awaiting a reduction in the refrigerant charge. If
the MOP protection function is disabled by setting the integral time to
zero, the maximum suction temperature control is also deactivated.
Par. Description Def. Min. Max. U.M.
C7 MOP protection: disabling threshold
30
(86)
-85
(-121)
200
(392)
°C (°F)
At the end of the MOP protection function, superheat control restarts
in a controlled manner to prevent the evaporation temperature from
exceeding the threshold again.
17
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
7. PARAMETERS TABLE
Par. Description Def. Min. Max. UoM Type Carel Modbus® R/W Note
BASED (FISRT CONFIGURATION)
GAS
Type
Refrigerant 3 0 40 - I 12 139 R/W
Gas Type = Refrigerant
0 Custom
1 R22 15 R422D 28 R1234ze(-1...4.2 barg)
2 R134a 16 R413A 29 R455A (-1...12.8 barg)
3 R404A 17 R422A 30 R170 (0...17.3 barg)
4 R407C 18 R423A 31 R442A (-1...12.8 barg)
5 R410A 19 R407A 32 R447A (-1...12.8 barg)
6 R507A 20 R427A 33 R448A
7 R290 21 R245FA 34 R449A
8 R600 (-1...4.2 barg) 22 R407F 35 R450A (-1...4.2 barg)
9 R600a (-1...4.2 barg) 23 R32 (0...17.3 barg) 36 R452A (-1...12.8 barg)
10 R717 24 HTR01 37 R508B (-1...4.2 barg)
11 R744 (0...45 barg) 25 HTR02 38 R452B
12 R728 26 R23 39 R513A (-1...4.2 barg)
13 R1270 27 R1234yf 40 R454B
14 R417A 41 R458A
3 = R404A
Mode Operating mode
1 Multiplexed cabinet/cold room
2 Air-conditioner/chiller with plate heat exchanger
3 Air-conditioner/chiller with tube bundle heat exchanger
4 Air-conditioner/chiller with nned coil heat exchanger
5 Reserved
6 Reserved
7 Cabinet/cold room with subcritical (R744) CO2
1 1 7 - I 13 140 R/W
Super
Heat
Superheat set point 11
(20)
LowSH:
protection
threshold
55
(99)
K
(°F)
A 10 9 R/W
SERVICE
P1 S1 probe measurement - -85
(-290)
200
(2900)
barg (psig) A 6 5 R
P2 S2 probe measurement - -85
(-121)
200
(392)
°C(°F) A 7 6 R
tE Evaporation temperature (converted) - -85 (-121) 200 (392) °C(°F) A 4 3 R
tS Suction temperature - -85 (-121) 200 (392) °C(°F) A 3 2 R
Po Valve opening - 0 100 % A 1 0 R
CP PID proportional gain 15 0 800 - A 11 10 R/W
ti PID integral time 150 0 999 s I 17 144 R/W
C1 LowSH protection: threshold 5(9) -5
(-9)
Superheat
set point
K
(°F)
A 12 11 R/W
C2 LowSH protection: integral time 15 0 800 s A 13 12 R/W
C3 LOP protection: threshold -50(-
58)
-85(-121) MOP
protection
threshold
°C(°F) A 14 13 R/W
C4 LOP protection: integral time 0 0 800 s A 15 14 R/W
C5 MOP protection: threshold 50
(122)
LOP pro-
tection:
threshold
200
(392)
°C(°F) A 16 15 R/W
C6 MOP protection: integral time 20 0 800 s A 17 16 R/W
C7 MOP protection: disabling threshold 30
(86)
-85
(-121)
200
(392)
°C(°F) A 19 18 R/W
C8 Low suction temperature alarm threshold -50
(-58)
-85
(-121)
200
(392)
°C(°F) A 18 17 R/W
S1 S1 probe type
Ratiometric (OUT=0…5V)
1 = -1…4.2 barg 8 = -1…12.8 barg
2 = 0.4…9.3 barg 9 = 0…20.7 barg
3 = -1…9.3 barg 10 = 1.86…43.0 barg
4 = 0…17.3 barg 11 = Reserved
5 = 0.85…34.2 barg 12 = 0…60 barg
6 = 0…34.5 barg 13 = 0…90 barg
7 = 0…45 barg
3 1 11 - I 14 141 R/W
n1 Network address 99 1 99 - I 10 137 R/W
n2 Baud rate (bit/s)
0 4800, 2 stop bit, parity none 9 4800, 1 stop bit, parity even
1 9600, 2 stop bit, parity none 10 9600, 1 stop bit, parity even
2 19200, 2 stop bit, parity none 11 19200, 1 stop bit, parity even
3 4800, 1 stop bit, parity none 12 4800, 2 stop bit, parity odd
4 9600, 1 stop bit, parity none 13 9600, 2 stop bit, parity odd
5 19200, 1 stop bit, parity none 14 19200, 2 stop bit, parity odd
6 4800, 2 stop bit, parity even 15 4800, 1 stop bit, parity odd
7 9600, 2 stop bit, parity even 16 9600, 1 stop bit, parity odd
8 19200, 2 stop bit, parity even 17 19200, 1 stop bit, parity odd
2 0 17 - I 20 147 R/W
18
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
Par. Description Def. Min. Max. UoM Type Carel Modbus® R/W Note
Si Unit of measure 1=°C/K/barg ¦ 2=°F/psig 1 1 2 - I 16 143 R/W
IA Enable operating mode modication 0/1 = yes/ no 0 0 1 - I 15 142 R/W
U1 Enable manual valve positioning 0/1 = no/ yes 0 0 1 - D 11 10 R/W
U2 Manual valve position 0 0 999 step I 7 134 R/W
U3 Valve control steps: 1/2 = 480/960 steps 1 1 2 - I 11 138 R/W
U4 Valve opening at start-up (evaporator/valve capacity ratio) 50 0 100 % I 19 146 R/W
Fr Firmware release - - - - A 9 8 R
di DI conguration: 1=start/stop regulation; 2=backup regulation 1 1 2 - I 18 145 R/W
rt Reserved 1 1 1 -
L1 S1 alarm: Minimum pressure -1 -85(-121) S1 alarm:
Max pressure
barg (psig) A 20 19 R/W
H1 S1 alarm: Maximum pressure - S1 alarm:
Min press.
200 (392) barg (psig) A 21 20 R/W
Tab. 7.a
8. NETWORK CONNECTION
The driver can be connected via a network connection to:
1. a computer running the VPM software, for setting the parameters
before commissioning;
2. a pCO controller, loaded with the application program;
3. a PlantVisor/PlantVisorPRO supervisor, for remote monitoring and
alarm detection.
8.1 RS485 serial conguration
n1 assigns to the controller an address for serial connection to a
supervisory and/or telemaintenance system.
Par. Description Def. Min. Max. UoM
n1 Network address 1 1 99 -
n2 Baud rate (bit/s)
0 4800, 2 stop bit, parity none
1 9600, 2 stop bit, parity none
2 19200, 2 stop bit, parity none
3 4800, 1 stop bit, parity none
4 9600, 1 stop bit, parity none
5 19200, 1 stop bit, parity none
6 4800, 2 stop bit, parity even
7 9600, 2 stop bit, parity even
8 19200, 2 stop bit, parity even
9 4800, 1 stop bit, parity even
10 9600, 1 stop bit, parity even
11 19200, 1 stop bit, parity even
12 4800, 2 stop bit, parity odd
13 9600, 2 stop bit, parity odd
14 19200, 2 stop bit, parity odd
15 4800, 1 stop bit, parity odd
16 9600, 1 stop bit, parity odd
17 19200, 1 stop bit, parity odd
2 0 17 -
Important: all controllers connected in a serial network need to be
set with the same communication parameters.
8.2 Network connection for commissioning
via PC
Warnings:
fasten the converter properly so as to prevent disconnection;
complete the wiring without power connected;
keep the CVSTDUMOR0 interface cables separate from the power
cables (power supply);
in compliance with standards on electromagnetic compatibility, a
shielded cable suitable for RS485 data transmission is used.
The RS485 converter is used to connect a computer running the VPM
software to the EVD ice driver via a serial network, for commissioning the
controllers. The system allows a maximum of 99 units, with a maximum
network length of 500 m. Connection requires the standard accessories
(RS485-USB converter, CAREL P/N CVSTDUMOR0) and a 120 Ω terminating
resistor to be installed on the terminals of the last connected controller.
Connect the RS485 converter to controllers and make the connections
as shown in the gure. To assign the serial address, see parameter n1. See
the converter technical leaets for further information.
GND
USB-485
Converter
CVSTDUMOR0
USB
T+
T -
shield
shield
shield
shield
*
*
EVD ice 1
EVD ice 2
EVD ice ...n
VPM
Fig. 8.a
8.3 Visual parameter manager
Go to http://ksa.carel.com and follow the instructions below. Select in
sequence:
1. “Software & Support
2. “Conguration & Updating Softwares
3. “Parametric Controller Software
4. Visual Parametric Manager”
A window will open with the possibility to download two les:
1. VPM_setup_X.Y.Z.W_full.zip: complete program;
2. X.Y.Z.W_VPM_Devices_Upgrade.zip: upgrade for supported devices;
If this is the rst installation, select Setup full, otherwise Upgrade. The
program installs automatically by running setup.exe.
Note: if choosing complete installation (Setup full), uninstall any
previous versions of VPM.
19
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
Programming
When opening the program, the device to be congured needs to be
selected: EVD mini. The Home page then opens, oering the choice
between starting a new project or opening an existing project. If using
the program for the rst time, choose new project.
Fig. 8.b
The following options are then available:
1. Directly access the list of parameters saved in EEPROM: select “RS485”;
The operations are performed in real time (ONLINE mode), at the top
right set network address 1 and choose the guided procedure for USB
port recognition, then go to “Device setup”;
Fig. 8.c
2. Selec t the model from the range based on the rmware version and list of
conguration parameters (EVDMINI0000E0X_R*.*). These operations
are performed in OFFLINE mode.
Menu
The pages marked 1) can be accessed wither Online or Oine, while
those marked 2) are Online only.
1
2
Fig. 8.d
The operations that can be performed on the pages marked 1) depend
on the rst selection made.
Note: to access the Online help press F1.
Ref. Description
Home Select operating mode
Online à RS485 (rear connector)
Oine à Device model
Online Oine
Device setup Read instant values of control
parameters
Select Load to load a list of
project parameters (.hex), modify
and save a new project.
Setup summary Display the default values for the current list of parameters
Custom setup See online help.
Update device Select list of parameters and
then Upload to controller
-
Upload
rmware
Select rmware and Upload -
Synoptic and
graphs
Overview with position of
probes and probe and su-
perheat readings in real time
-
Tab. 8.a
8.4 Restore default parameters
To restore the default parameter values on the controller:
1. Establish an RS485 serial connection between the computer and the
driver. The LEDs on the USB/RS485 converter will ash;
Fig. 8.e
2. Select “Update device” and:
a. Click button (A) to open the drop-down menu;
b. Select the list of parameters corresponding to the controller’s
rmware version: “EVDMINI***.hex”;
c. Click “Update to load the parameters to the list and immediately
after restore the controller parameters to the default value.
C
B
A
Fig. 8.f
3. Go to “Device setup”: the program automatically reads the default
parameters saved on the controller.
8.5 Setup by direct copy
1. On the Home page select RS485 (rear connector);
Fig. 8.g
2. Go to “Device setup”;
Fig. 8.h
20
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
a. on the “Rapid conguration page, set parameters “p_GAS_TYPE” =
refrigerant and p_SUPER_MAIN_REGULATION”= type of control;
Fig. 8.i
b. on the “Conguration page, set parameter “p_SH_SET.
Fig. 8.j
3. Check whether there are other parameters that need to be set (see the
“Functions” chapter);
4. Finally, select Write to copy the parameters to the controller.
Fig. 8.k
8.6 Setup using conguration le
On the Home page select “Device model”.
Fig. 8.l
The setup procedure comprises three steps:
1. Create the conguration le;
2. Copy the conguration le to the controller;
3. Read the conguration le on the controller.
Create the conguration le
1. Select the “Device setup page;
2. Set the parameters by double clicking, as shown in the gure:
a. on the “Rapid conguration” page, parameters “p_GAS_TYPE” =
refrigerant and p_SUPER_MAIN_REGULATION”= type of control;
b. on the “Conguration page, parameter “p_SH_SET.
Fig. 8.m
3. Save the list of parameters with a new name, for example “NEW_NAME.
hex. To load and display a list saved by the user, select “Load” and
navigate to the path where the le is saved. On the other hand,
to load a list of parameters supplied by CAREL, select “Load” and
navigate the following path:
LoadàPluginsàCommissioning EVD mini àTXTàTXT32.
Save Load
Copy the conguration le to the controller
Select “Update device” and:
a. Click button (A) to open the drop-down menu;
NEW_NAME.hex
C
B
A
Fig. 8.n
b. Select the list of parameters corresponding to the project le
created: “NEW_NAME.hex”;
c. Click “Update to UPLOAD the parameters to the controller.
8.7 Read the conguration le on the
controller
1. Go to the “Home” page and select RS485 (rear connector);
2. Go to “Device setup” to read the list of parameters on the controller and
make sure the settings are correct.
/