Hytronik HEC6028 Tri-level Control User manual

Category
Motion detectors
Type
User manual
Instruction Manual for Integrated SensorDIM LED Driver
Tri-level Dimming Version, Model No.:HEC6028
Technical Specifications
IMPORTANT
PLEASE READ THESE INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND RETAIN THIS
LEAFLET IN A KNOWN AND SAFE PLACE FOR FUTURE REFERENCE.
Section 1 Installation and Wiring
1.1 Ensure that the electricity supply is switched off before installing or servicing this product.
1.2 Wiring diagram
101.1
35.5 4.1
110
49.5
32.2
23.7 27.3
29
This is a smart integration of microwave motion sensor LED driver. Designed
in the software and thanks to our worldwide patented circuit, the built-in
daylight sensor is prior to motion sensor so as to achieve utmost energy
saving purpose.
Note: the high-frequency output of this sensor is <0.2mW; approximately just 1‰ of the transmission power of a mobile telephone.
PRODUCTTYPE: Integrated sensorDIM LED driver
OPERATING VOLTAGE: 220-240VAC 50Hz/60Hz
INPUT: 150~140mA / 220~240V / 32.5W
OUTPUT: 700mA / 23~40V / 16~28W
HF SYSTEM: 5.8GHz CW radar
TRANSMISSION POWER: <0.2mW
DETECTION ANGLE: 30O ~ 150O
DETECTION RANGE: Max. 8 x 5 (DxH)
TIME SETTING: 5s~10min.
DAYLIGHT SENSOR: 2~50Lux; disable
STAND-BY PERIOD: 0s, 30s ~ 10min, +∞
STAND-BY DIMMING LEVEL: 10% ~30%
MOUNTING: Indoors,ceiling&wall mounted
WORKING TEMP.: -20OC ~ +50OC
Daylight sensor
Stand-by period
Stand-by dimming level
Daylight sensor
Hold-time
LED
LED
Detection range
Sensor antenna
Installation hole (4.1mm)
Installation hole
(screw D x L: 3 x 10mm)
L (Blue)
N (Brown)
Cut-out size:
(L x D: 36 x 29.5mm) LED indication
Stranded wire: 0.5~1.5mm2 American wire gauge: 18AWG Wire stripping length: 9~10mm
3rd Floor, block C, complex building, 155#, Bai'gang road south,
Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel:86-752-2772020 F:86-752-2777877
E: [email protected] W:www.hytronik.com
CHINA FACTORY
Room D, 10/f, Tower A, Billion Center, 1 wang Kwong Road,
Kowloon Bay, Kowloon, Hongkong
T: 00852-35197525 F: 00852-30116936
HYTRONIK INDUSTRIAL LIMITED
Section 2 SETTINGS
SECTION 3 FUNCTION
Detection range can be tuned by selecting the combination on the DIP switches to fit precisely for each specific application.
Detection range
I – 100%
II – 50%
1
50%
100 %
This setting determines the time period the lamp will remain at 100% upon detection.
Note: the timer is reset upon each motion detection.
Hold-time
I – 5s
II – 30s
III – 3min
IV – 10min
30s
5s
10min
32
3min
I – 0s
II – 30s
III – 10min
IV – +∞
This is the time period setting to keep at the low light output level before it is completely switched off in the long absence of
people.
Stand-by period (corridor function)
Note: “0s” means on/off control; “+∞” means bi-level dimming control, fixture never switch off. (i.e. the light remains at the
stand-by dimming level until motion is detected.)
I – Disable
II – 50Lux
III – 10Lux
IV – 2Lux
Daylight sensor
The daylight threshold can be set on the DIP switches suit to the particular application. 54
50Lux
10Lux
2Lux
Disable
30s
0s
+∞
76
10min
I – 10%
II – 30%
8
30%
10%
This is the dimmed low light output level setting after the hold-time has expired.
Stand-by dimming level
3.1 Assembly
Note: end-user can also scan the QR
code on the housing for checking settings.
The sensor antenna features the DIP
switches and protrudes the LED panel.
This feature enables the end user to
access the sensor settings without
removing the gear tray / LED board.
Cut-out size: 36 x 29.5 (mm)
Sensor antenna
SECTION 4 TROUBLE SHOOTING
MALFUNCTION CAUSE REMEDY CAUSE REMEDY
The light will not come on
The lamp is always on
The lamp will not work
despite movement Check detection area setting
The lamp is on without any
identifiable movement
Incorrect light-control setting selected
Continuous movement in the detection zone
The sensor is not mounted for reliably
detecting movement
Movement occurred, but not identified by the
sensor (Movement behind wall, movement of
small object in immediate lamp vicinity etc.)
Rapid movements are being suppressed to
minimize malfunctioning or the detection
radius is too small.
Faulty lamp
No power supply
Adjust daylight threshold setting
Replace lamp
Check power to sensor
Check detection area setting
Securely mount enclosure
1. Reduce sensitivity.
2. Check the movement behind
walls to avoid facilities such as
water pipe, fan, which may
mis-trigger the sensor.
  • Page 1 1
  • Page 2 2
  • Page 3 3

Hytronik HEC6028 Tri-level Control User manual

Category
Motion detectors
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI