Teletek electronics MAG4 User manual

Category
Fire protection
Type
User manual
English
MAG2
MAG4
FIRE CONTROL PANEL
User Manual
/metal and plastic box/
2 Fire Control Panel MAG2/4 - User Manual
CONTENTS
Guarantee ...................................................................................................................3
1. Using the MAG2/4 controls ...................................................................................4
1.1 Operation modes ...........................................................................................5
1.2 LED indication for zones status ...................................................................5
1.3 LED indication for the technical troubles ....................................................5
1.4 LED indication for the system status ..........................................................6
1.5 Buttons for programming and operation ....................................................6
1.6 Switch for changing over between Access Levels 1 and 3 .......................6
1.7 Sound signalization .......................................................................................7
2. Installing the MAG2/4 re panels .........................................................................7
3. Testing the MAG2/4 re panels ............................................................................8
4. Connecting the zone circuits ...............................................................................8
5. Connecting the sounders circuits .......................................................................9
6. Connecting the FAULT and FIRE relays ..............................................................9
7. Class Change Function .........................................................................................9
8. Operation instructions ........................................................................................10
8.1 Zone Enabling/ Disabling ...........................................................................10
8.2 Sounders Enabling/ Disabling ....................................................................10
8.3 “One man” zone testing ..............................................................................11
9. Technical specications .....................................................................................12
10. Connection diagrams ........................................................................................13
11. Fire alarm record ...............................................................................................14
12. Service record....................................................................................................14
13. Fire alarm event LOG ........................................................................................15
14. Spare parts kits..................................................................................................15
1293
16
DoP No: 075
1293 - CPR - 0510
Teletek Electronics JSC, 14 Srebarna Str., 1407 Soa, Bulgaria
EN 54-2:1997/A1:2006/AC:1999; EN 54-4:1997/A2:2006/AC:1999
MAG2/4
Intended for use in re detection and re alarm systems in and around buildings.
Essential Characteristics Performance
Performance under re conditions Pass
Response delay (response time to re) Pass
Operational reliability Pass
Durability of operational reliability and response delay: temperature resistance Pass
Durability of operational reliability: humidity resistance Pass
Durability of operational reliability: vibration resistance Pass
Durability of operational reliability: electrical resistance Pass
Fire Control Panel MAG2/4 - User Manual 3
GUARANTEE
The guarantee terms are determined by the serial number (barcode) of the electronic device!
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective product when it is returned
to the factory. All parts replaced and/or repaired shall be covered for the remainder of the original guarantee, or 6 months, whichever
period is longer. The original purchaser shall immediately send manufacturer a written notice of the defective parts or workman-
ship.
International Guarantee
Foreign customers shall possess the same guarantee rights as those any customer in Bulgaria, except that manufacturer shall not
be liable for any related customs duties, taxes or VAT, which may be payable.
Guarantee Procedure
The guarantee will be granted when the appliance in question is returned. The guarantee period and the period for repair are deter-
mined in advance. The manufacturer shall not accept any product, of which no prior notice has been received via the RAN form at:
http://www.teletek-electronics.com/en/support/Service
The setup and programming included in the technical documentation shall not be regarded as defects. Teletek Electronics bears no
responsibility for the loss of programming information in the device being serviced.
Conditions for waiving the guarantee
This guarantee shall apply to defects in products resulting only from improper materials or workmanship, related to its normal use.
It shall not cover:
• Devices with destroyed serial number (barcode);
• Damages resulting from improper transportation and handling;
• Damages caused by natural calamities, such as re, oods, storms, earthquakes or lightning;
• Damages caused by incorrect voltage, accidental breakage or water; beyond the control of the manufacturer;
• Damages caused by unauthorized system incorporation, changes, modications or surrounding objects:
• Damages caused by peripheral appliances (unless such peripheral appliances have been supplied by the manufacturer:
• Defects caused by inappropriate surrounding of installed products;
• Damages caused by failure to use the product for its normal purpose; Damages caused by improper maintenance;
• Damages resulting from any other cause, bad maintenance or product misuse.
In the case of a reasonable number of unsuccessful attempts to repair the product, covered by this guarantee, the manufacturer’s
liability shall be limited to the replacement of the product as sole compensation for breach of the guarantee. Under no circumstances
shall the manufacturer be liable for any special, accidental or consequential damages, on the grounds of breach of guarantee, breach
of agreement, negligence, or any other legal notion.
Waiver
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other guarantees, explicit or implicit (in-
cluding any implicit guarantees on behalf of the dealer, or adaptability to specic purposes), and over any other responsibilities or
liabilities on behalf of the manufacturer. The manufacturer does neither agree, nor empower, any person, acting on his own behalf, to
modify, service or alter this Guarantee, nor to replace it with another guarantee, or another liability with regard to this product.
Unwarranted Services
The manufacturer shall repair or replace unwarranted products, which have been returned to its factory, at its sole discretion under
the conditions below. The manufacturer shall accept no products for which no prior notice has been received via the RAN form at:
http://www.teletek-electronics.com/en/support/Service
The products, which the manufacturer deems repairable, will be repaired and returned. The manufacturer has prepared a price
list and those products, which can be repaired, shall be paid for by the Customer. The devices with unwarranted services carry 6
month guarantee for the replaced parts.
The closest equivalent product, available at the time, shall replace the products, the manufacturer deems un-repairable. The cur-
rent market price shall be charged for every replaced product.
!
This manual contains information on limitations regarding product use and function and
information on the limitations as to liability of the manufacturer.
The entire manual should be carefully read!
WARNING
The system is to be installed by a qualied person to the latest Fire Alarm and Installation Regulations which
are mandatory in the applicable country of installation.
Before commencing the installation of this Fire Alarm Panel, ensure it is sited in a position, which is visible
to the Fire Brigade when entering the premises, and where ease of access is provided for users and service
engineers. Space must be available to easily open external and internal doors.
The Electrical Supply to the panel must be isolated and must not be capable of being accidentally switched
off. A ‘Lockable Switch fuse Unit’ positioned within 2 meters of the panel should be clearly labelled FIRE
ALARM - DO NOT SWITCH OFF.
EN 54-2 compatible panels.
All specications are subject to change without notice.
Technical Support help:
+359 (2) 9694 800
4 Fire Control Panel MAG2/4 - User Manual
1. Using the MAG2/4 control
Description of the front panels elements:
LED indication for the zones status:
MAG2 - 2 zones
MAG4 - 4 zones
Buttons for programming and operation, see item 1.5.
LED indication for the system status, see item 1.4.
LED indication for the technical troubles - see item 1.3.
Note: This indication is not visible for the user. To examine the technical
troubles in the system, the engineer has to remove the front cover of the
box.
Switch for changing over between Access Levels 1 and 2 - see item 1.6.
Front view MAG2 Front view MAG4
 
 
 
 
 
Fire Control Panel MAG2/4 - User Manual 5
1.1 Operation modes:
MODE Indication
Normal • The green LED next to the ‘power Supply 230V AC’ will be illuminated.
Fire
The integrated red status FIRE LED and a zone identication LED will
ash together on receipt of a FIRE condition and become steady after the
SILENCE ALARM button is pressed.
An internal buzzer will operate until silenced with SILENCE BUZZER
button.
• The external sounders will operate.
• The FIRE relay on the main board will energize.
Fault
The yellow GENERAL FAULT LED will always illuminate together with
an external or internal identication LED.
An internal buzzer will sound.
The FAULT relay on the main will de-energize.
1.2 LED indication for the zones status:
ZONE LED Indication
Red • Fire alarm in the zone.
Yellow • Zone fault - open or short circuit. Detector head removed.
• Zone test - the LED is blinking during the test procedure.
1.3 LED indication for the technical faults:
FAULT Fault description
○ µP Processor break down.
○ Sounder 1 Sounder Circuit One fault - open or short circuit, reverse
connected sounder, or bad sounder parameters.
○ Sounder 2 Sounder Circuit Two fault - open or short circuit, reverse
connected sounder, or bad sounder parameters.
○ +24V DC Overload Overload of “+24” VDC power supply.
○ +24V DC Failed Absence of “+24” VDC power supply.
○ Battery Low Low battery condition.
○ Battery Lost Battery loss.
AC Mains Supply loss.
○ Charger Battery charger fault.
AUX Auxiliary supply fault.
○ Earth Short circuit to earth.
Battery Low, Battery Lost and Charger LEDs are lighting up together in case of
overload of the battery charger output.
6 Fire Control Panel MAG2/4 - User Manual
1.4 LED indication for the system status:
LED Indication
FIRE
(red) Fire in the premises.
GENERAL FAULT*
(yellow) Main Fault indicator.
SOUNDER FAULT/DISABLE*
(yellow)
Trouble in the sounder circuit - open or short circuit;
reverse connected sounder.
ENABLE / DISABLE
(yellow)
Lights permanently at disabled zones/sounders.
Blinks during enabling/disabling of zones or
sounders.
TEST
(yellow)
Blinks during “One Man” Test together with the LED
of the tested zone.
POWER SUPPLY 230V
(green)
Lights on permanently in normal operating mode,
indicates presence of main power supply 230V.
1.5 Buttons for programming and operation:
Button Description
SILENCE BUZZER Deactivating the internal buzzer.
SILENCE ALARM Deactivating sounders.
ENABLE / DISABLE Enabling / Disabling of Zones / Sounders.
TEST / SCROLL Test mode; Scroll forward zones.
RESET Initialization; Conrm the introduced changes.
SOUND ALARM Activating sounders.
1.6 Switch for changing over between Access Levels 1 and 2:
Position Description
OFF Access Level 1 - only the “SILENCE BUZZER” button is active.
ON Access Level 2 - all buttons at the front panel are active.
* NOTE: Fault conditions will not be announced instantly. There will be a short delay
which will vary from condition to condition. Faults when cleared will automatically reset
at the panel.
Fire Control Panel MAG2/4 - User Manual 7
1.7 Sound signalization
Signal Description
Short beeps After pressing the “RESET” button and upon the initial start-up of the
panel.
Continuous
beep
Fire and/ or Fault operating mode. The signal can be stopped by
pressing the “SILENCE BUZZER” button, but the LED indication
remains.
Interrupted
beep
After pressing the “ENABLE/DISABLE” button to enable/disable zones/
sounders and the “TEST/SCROLL” button to access “One Man” test
mode of zones. The signal can be stopped by pressing the “SILENCE
BUZZER” button, but the LED indication remains.
2. Installing the MAG2/4 re panels
• Choose the best location for the panel position, with an ambient temperature between
-5°C and 40°C, away from heating sources, environmental dust and potential water
ingress.
• Remove all packaging and inspect visually the panel for any damage.
• Remove the outer cover. Stow the cover in a safe position.
• Inspect the internal PCB and make sure the internal components are rmly in place.
• Remove the PCB from the metal / plastic box. Stow in a safe location.
• Choose which cable entry points to knock out and carefully remove the knock-outs.
Drill the wall to suit the back box centre xing position, plug and insert a xing screw.
Note: If you are installing MAG 2/4 in plastic box use the template on the back side of
the packaging box to drill the mounting holes on the wall.
• Fix the metal / plastic housing into mounting position and insert xing screws.
• Tighten all the xing screws.
Route the external cables onto the back box, make off connection glands etc., DO NOT
make any connections at this stage. ENTER THE MAINS CABLE THROUGH ITS
OWN CABLE ENTRY POINT AND KEEP MAINS WIRING AWAY FROM SYSTEM AND
OTHER LOW VOLTAGE WIRING.
Fit the EOL modules from the supplied additional parts one-by-one to every zone
terminal. ATTENTION: Observe the polarity - the red wire to “+” point and the black
wire to “-” point.
Fit the EOL resistors from the supplied additional parts one-by-one to the sounders
terminal.
• Re-t the PCB to the metal / plastic box.
• Place the temperature sensor behind or under the accumulator battery.
• Connect the mains supply and earth to the main terminal block. DO NOT switch on the
main electrical supply at this stage.
• Position the battery in an upright position and place the temperature sensor behind it.
• Close the outer cover using the nuts and screws from the spare parts kit:
8 Fire Control Panel MAG2/4 - User Manual
3. Testing the MAG2/4 re panels
!
ATTENTION: It has been assumed that prior to making the connection
at the panel, the integrity of the system ALL wiring has been
comprehensively tested, including insulation to earth.
• Switch on the mains power supply.
• Connect the battery leads from the black power supply box to the positive and
negative battery terminals.
• If the buzzer and indicator LED’s are operating, press the RESET button.
In Normal Operating Mode only POWER SUPPLY 230V will be illuminated.
NOTE: The battery might show a ‘Low Battery Fault’ initially until it has had time to
charge up to the required level.
If other LEDs are illuminated and the buzzer is sounding, carefully check all
fuses and connections. Refer to the page 7 for the associated yellow LED’s
apply to. The connection diagram on the inside of the external cover will assist
in identifying the LED.
!
ATTENTION: Do not short out the battery terminals because an internal
protection will switch on and the panel will stop function!
If by some chance the fault will not cancel, and only on the advice of our Technical
Support Department, return the PCB CHASSIS ONLY to your supplier. DO NOT
return the metal / plastic box.
4. Connecting the zones circuits
• Disconnect the mains power supply and the battery connection.
• Remove the EOL-module from the zone 1 terminal on the main module and t it to the
last detector of the zone 1 circuit as observe the polarity:
Ensure all terminations are made correctly and all detector heads are plugged into their
bases.
• Connect Detector circuit ONE to the panel terminal block.
• Power up the panel with the mains and battery.
• Press RESET button.
The panel should be in the ‘NORMAL MODE’.
If General Fault and zone 1 FAULT LED’s illuminate, there is a wiring/
connection problem. Check the polarity of the connection, the connection of
the devices and whether a head is removed. Check the EOL proper polarity
and position.
Fire Control Panel MAG2/4 - User Manual 9
Operate ALL detection devices applicable to this zone, to ensure correct receipt of a re
signal and the correct operation of the panel controls. Refer to the User Instructions on
the inside of the panel.
• Repeat the connection process for the other zones stated above. ENSURE the supply
voltages are initially disconnected prior to each stage.
!
Once the connection of the zones is completed, connect and test any
of the other auxiliary circuits BEFORE connecting the external sounder
circuits.
5. Connecting the sounders circuits
• Disconnect the mains power supply and the battery connection.
• Remove the EOL-Resistor from the terminal block of sounder circuit 1 (SND 1) and t
to the last sounder of circuit one:
brown
black red
10K
LEGEND
Sounders
S1 S2 SN
• Check all sounder connections are made.
• Connect sounder circuit ONE to the panel terminal block.
Apply mains and battery power.
• Press RESET.
The panel should be in the ‘NORMAL MODE’.
Activate a zone Call Point. The sounders should operate. Press the RESET button.
Repeat the connection process for the second external sounder circuit, as stated above.
ENSURE the supply voltages are initially disconnected prior to each stage.
If General Fault and SOUNDER FAULT / DISABLE LED’s illuminate, there is
a wiring / connection problem. Check the polarity of the connection of each of
the devices, the polarity of the connection of the devices to the Panel terminal
block or whether an earth fault exists.
6. Connecting the FAULT and FIRE relay circuits
FAULT and FIRE Relays - The on board relays volt free change over terminals are
for low voltage use only. Attention: Mains supply MUST NOT BE APPLIED to these
terminals.
7. Class Change Function
To use the class change function connect the terminals of a switch with normally open
contacts to the CC (Class Change) clamps of the main module terminal. The working
mode of the sounders will be:
- when the switch is pressed - one second sounder on, one second sounder off;
- when the switch is depressed - the sounder is off.
10 Fire Control Panel MAG2/4 - User Manual
8. Operation instructions
8.1 Zone Enabling/ Disabling
Z To disable a zone:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/ SCROLL, until
you reach the zone which has to
be disabled:
The respective zone yellow LED blinks.
• Press ENABLE/ DISABLE: The yellow LED of the disabled zone lights up per-
manently.
• Press RESET: At this step the zone is disabled.
Z To enable a zone:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/SCROLL, until you
reach the zone which has to en-
able:
The yellow LED of the disabled zone lights up per-
manently.
• Press ENABLE/ DISABLE: The yellow LED of the enabled zone blinks.
• Press RESET: At this step the zone is enabled.
8.2 Sounders Enabling/ Disabling
!
A sound signalization is activated at every Service Mode entering. The
signalization is off by pressing “SILENCE BUZZER button.
Z To disable the sounders:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/ SCROLL, until
you reach the last zone in the
system:
The SOUNDER FAULT/DISABLE LED will start
blinking.
• Press ENABLE/ DISABLE: The SOUNDER FAULT/DISABLE LED lights up
permanently.
Fire Control Panel MAG2/4 - User Manual 11
• Press RESET:
The SOUNDER FAULT/DISABLE and ENABLE/
DISABLE LEDs light up permanently.
At this step the sounders are disabled.
You can exit the sounder disabling mode also by pressing theTEST/ SCROLL” button,
as in that case the you reject the procedure.
Z To enable the sounders:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/ SCROLL, until
you reach the last zone in the
system:
The SOUNDER FAULT/DISABLE LED lights up
permanently.
• Press ENABLE/ DISABLE: The SOUNDER FAULT/DISABLE LED will start
blinking.
• Press RESET: At this step the sounders are enabled.
You can exit the sounder enabling mode also by pressing theTEST/ SCROLL” button,
as in that case the you reject the procedure.
8.2 “One man” Zone Testing
The “One Man” Test mode gives the installer the possibility to test the efciency of the
system - whether the detectors react to smoke, heat, etc.
Z To do “One Man” Test of a zone:
• Press TEST/ SCROLL: µP Fault and General Fault LEDs light off. All other
system indication LEDs light on permanently.
• Press TEST/ SCROLL again:
The TEST LED and ZONE 1 yellow LED start
blinking.
ZONE 1 is in test mode. Test a detector from this
zone whether it react to smoke, heat, etc.
Press TEST/ SCROLL again to
continue with the system testing:
TEST LED will continue blinking.
The ZONE 1 yellow LED lights out (the zone is
not longer in test mode). The ZONE 2 yellow LED
blinks in yellow.
ZONE 2 is in test mode. Test a detector from this
zone whether it react to smoke, heat, etc.
Continue the system testing by pressing the “TEST/ SCROLL” button. The exit from the
“One Man” Test mode is automatic after the end of the test procedure in the last Zone 4,
or at any time by pressing “RESET” button.
12 Fire Control Panel MAG2/4 - User Manual
9. Technical Specications of MAG2 and MAG4
Zones:
• MAG 2 - 2 xed zones
• MAG 4 - 4 xed zones
Maximum number of detectors per zone:
Up to 20 (or 32 SensoMAG series) conventional detectors and unlimited number of
manual call points.
Thresholds for zone conditions:
• 0 ÷ 2 mA - Open circuit fault condition
• 2 ÷ 10 mA - Normal condition
• 10 ÷ 110 mA - Fire Alarm condition
• 110 mA - Short circuit condition
Power Supply:
• Main Power supply: 230V AC ±10%; 0.315A fuse
• Standby Power supply: 1 x 12V / 7Ah; 2A fuse
• Internal resistance of accumulator battery: Ri < 1.6Ω
Maximum current available for system devices (with fully charged battery):
0.7 A
Current consumption - mains failure:
• 50 mA
Outputs:
• Sounder Circuit 1: 24V / 0.3A; 0.3A fuse (PTC)
• Sounder Circuit 2: 24V / 0.3A; 0.3A fuse (PTC)
• Fault Relay, volt free changeover contacts*: 3A @ 120V AC; 3A @ 60V DC
• Fire Relay, volt free changeover contacts*: 3A @ 120V AC; 3A @ 60V DC
* Note: These functions may not be used to provide any “Options with requirements” as specied
in EN 54-2.
Auxiliary output:
• 24V DC, 0.3A fuse (PTC)
Cabling:
• Maximum 2.5mm diameter
Environment:
• Working temperature: -5 to 40°C
• Storage temperature: -20 to 60°C
• Humidity: 0 to 95%
Temperature sensor:
The temperature sensor is used for measurement of the battery temperature. The sensor
is mounted at the end of the wired y lead, factory connected to “Temperature sensor”
terminal on the panel’s PCB.
The temperature sensor should be placed behind or under the battery.
Fire Control Panel MAG2/4 - User Manual 13
10. Connection Diagrams
Connection circuit MAG2/4 metal box
Connection circuit MAG2/4 plastic box
14 Fire Control Panel MAG2/4 - User Manual
11. Fire Alarm Record
Installation Address: .......................................................................................................
.......................................................................................................
.......................................................................................................
.......................................................................................................
.......................................................................................................
Contact Person: .......................................................................................................
Telephone: .......................................................................................................
Fax: .......................................................................................................
Date Completed: .......................................................................................................
Commissioned By: .......................................................................................................
Contract Reference: .......................................................................................................
Service Intervals: Monthly / Quarterly / Half Yearly / Annually
ZONE
No LOCATION
DETECTOR TYPE and
QUANTITY PER ZONE
SOUNDERS
(Zone Quantity and
Related Circuit )
Ion* Ph RoR F/T CP Circuit1 Circuit2
1
2
3
4
TOTALS:
* Ion - Ionisation sensor, Ph - Photoelectric sensor, RoR - Rate of Rise sensor, F/T - Fixed
Temperature sensor, CP - Call Point
System Installed By: .........................................................................................................
Telephone / Fax: ................................................................................................................
12. Service Record
Date Visit
Completed
Zones
Tested
Faults
Rectied
Signature of
Engineer
Next Due
1 2 3 4 Name:
1 2 3 4 Name:
1 2 3 4 Name:
1 2 3 4 Name:
Fire Control Panel MAG2/4 - User Manual 15
13. Fire Alarm Event LOG
DATE TIME FIRE
yes / no
ZONE
number
FAULT
yes/no and
TYPE
ACTION
TAKEN Name
14. Spare Part Kits
www.teletek-electronics.com
Address: 14A Srebarna Str., 1407 Soa, Bulgaria
tel.: (+359 2) 9694 800, fax: (+359 2) 962 52 13
18020244, Rev.B, 02/2016
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Teletek electronics MAG4 User manual

Category
Fire protection
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI