Page 3 of 48
Simpo Addressable Panel
• Access level 4 is only for authorized personal, which has knowledge to update the
panel’s software. Access can be obtained by means of special tool (screwdriver,
mechanical key-switch or external programmer).
Inputs:
• Input 1 – Alarm Confirmation - meets VdS 2540
• Input 2 – Protection Alarm Confirmation - meets VdS 2540
• Input 3 – Fault Protection Panel - meets VdS 2540
Outputs:
• Fire - 1 Relay contact (Potential, Monitored) output - 24 VDC - 300 mA, with auto
resettable PTC fuse. EN54-2-7.9
• Fault - 1 Relay contact (Potential, Monitored) output - 24 VDC - 300 mA, with auto
resettable PTC fuse. EN-54-2-8.9
• EXT - 1 Relay contact (Potential, Monitored) output - 24 VDC - 300 mA, with auto
resettable PTC fuse. EN54-2-7.10
• Sirens - 2 Relay contacts (Potential, Monitored) outputs - 24 VDC - 500 mA, with
auto resettable PTC fuses. EN54-2-7.8
• AUX – Potential for powering up of external devices - 24 VDC - 500 mA, with auto
resettable PTC fuse.
• Programmable – 4 Relay contact (Dry contact, not monitored) – 250VAC, 10A and
24 VDC, 15A.
Real time clock:
• Appears on the LCD screen.
• Battery back-up
Possibility of DAY and NIGHT mode:
• DAY mode – the delays for outputs Fire, Sirens, Addressable Sounders and
MOUT modules are active.
• NIGHT mode – the delays for outputs Fire, Sirens, Addressable Sounders and
MOUT modules are not active.
• The switching between both modes can be manual (Access level 2) or automatic
with software assigned schedule (Access level 3 - by days and hours). For both
modes different sensitivity of the detectors will be applied. This function can be
manually adjusted from the panel for each detector.
Thermal printer:
• Possibility of connecting external printer to the Main PCB via RS232 port.
• Supports different paper width. Selectable from the panel (Software).
Languages support:
• The panel supports Bulgarian, English, Spanish, Portuguese, Italian, French,
Turkish, Polish and Russian languages.