Optimus WINCONTROL SER. User manual

Type
User manual
JBL Professional
8500 Balboa Boulevard
Northridge, CA 91329
U.S.A.
Phone: (818) 894 8850
Web: www.jblpro.com
Technical development by:
Duran Audio BV
Koxkampseweg 10
5301 KK Zaltbommel
The Netherlands
Phone: 31(0)418-515583
Web: www.duran-audio.com
GvB February 2015
WinControl External Control
API
v2.11
Doc type
WinControl External Control API v2.11 2
Contents.
1. OBJECTIVE. ...............................................................................................................5
2. GENERAL. .................................................................................................................7
2.1 SERIAL PORT SETTINGS ............................................................................................................ 7
2.2 PROTOCOL OPTIONS............................................................................................................... 8
2.3 TRANSMIT DELIMITERS............................................................................................................ 8
2.4 MONITORING OF THE CONNECTION. .......................................................................................... 9
2.5 REDUNDANT HOST............................................................................................................... 10
2.6 REDUNDANT AMPLIFIERS....................................................................................................... 12
3. COMMANDS...........................................................................................................13
3.1 GENERAL. .......................................................................................................................... 13
3.1.1 Command structure. ................................................................................................ 13
3.1.2 Little endian coding. ................................................................................................ 14
3.1.3 PC response.............................................................................................................. 15
3.2 ADDRESS. .......................................................................................................................... 16
3.2.1 Address specifier format convention. ...................................................................... 16
3.2.2 Master and slave devices......................................................................................... 18
3.2.3 Address translation for redundant amplifier control............................................... 18
3.3 COMMAND ID AND VALUE.................................................................................................... 19
3.3.1 Failure & status request........................................................................................... 19
3.3.2 Select a section. ....................................................................................................... 48
3.3.3 Select a combination of sections. ............................................................................ 50
3.3.4 Un-mute a section. .................................................................................................. 51
3.3.5 Mute a section. ........................................................................................................ 53
3.3.6 Duck a section.......................................................................................................... 55
3.3.7 Duck a combination of sections............................................................................... 57
3.3.8 Pre-recorded message control................................................................................. 59
3.3.9 Autogain control. ..................................................................................................... 64
3.3.10 Mute/ducking control........................................................................................... 64
3.3.11 Output mute control............................................................................................. 66
3.3.12 Output ducking control......................................................................................... 67
3.3.13 Select preset. ........................................................................................................ 69
3.3.14 Input mute control................................................................................................ 70
3.3.15 Redundant host control........................................................................................ 71
3.4 TERMINATOR...................................................................................................................... 72
3.4.1 Terminator code. ..................................................................................................... 72
3.4.2 Terminator value. .................................................................................................... 76
WinControl External Control API v2.11 3
Figures list.
FIG 1 GENERAL EXTERNAL CONTROL PORT CONFIGURATION OPTIONS IN WINCONTROL............................ 7
FIG 2 EXTERNAL CONTROL WATCHDOG TIMER CONFIGURATION IN WINCONTROL. .................................. 9
FIG 3 AVAILABILITY SCORE CALCULATION CONFIGURATION IN WINCONTROL. ....................................... 31
FIG 4 SECTION EDITING EXAMPLE FROM WINCONTROL.................................................................... 49
FIG 5 DEVICE WITH OUTPUT DUCKING SUPPORT (L) AND WITHOUT OUTPUT DUCKING SUPPORT (R)........... 56
FIG 6 WAVE PLAYER RELATED EXTERNAL CONTROL OPTIONS............................................................. 59
WinControl External Control API v2.11 4
Tables list.
TABLE 1 DOCUMENT REVISIONS. ...................................................................................................... 6
TABLE 2 RS-232 PIN DESCRIPTION. .................................................................................................. 8
TABLE 3 GENERAL COMMAND STRUCTURE OF INCOMING PACKET - BINARY PROTOCOL............................... 13
TABLE 4 GENERAL COMMAND STRUCTURE OF INCOMING PACKET - ASCII HEX PROTOCOL. ......................... 13
TABLE 5 ADDRESS SPECIFIER FORMAT............................................................................................... 17
TABLE 6 COMMAND ID - FAILURE & STATUS REQUEST, OVERVIEW OF BIT MAPPING. ................................ 19
TABLE 7 COMMAND ID - FAILURE & STATUS REQUEST, VALID VALUE PARAMETERS.................................. 23
TABLE 8 COMBINED FAILURE REQUEST FORMAT - BINARY PROTOCOL..................................................... 24
TABLE 9 GENERAL FAILURE REQUEST RESPONSE MAPPING. ................................................................... 27
TABLE 10 DETAILED FAILURE REQUEST RESPONSE FORMAT - BINARY PROTOCOL. ....................................... 29
TABLE 11 CONTROLLER AVAILABILITY SCORE RESPONSE FORMAT - BINARY PROTOCOL................................. 31
TABLE 12 REDUNDANT AMPLIFIER SYSTEM 'TAKEN OVER' RESPONSE FORMAT - BINARY PROTOCOL............... 33
TABLE 13 REDUNDANT AMPLIFIER 'DISABLED' RESPONSE FORMAT - BINARY PROTOCOL.............................. 34
TABLE 14 COMBINED GENERAL STATUS REQUEST FORMAT - BINARY PROTOCOL......................................... 35
TABLE 15 GENERAL STATUS REQUEST RESPONSE MAPPING. ................................................................... 37
TABLE 16 DETAILED GENERAL STATUS REQUEST RESPONSE FORMAT - BINARY PROTOCOL. ........................... 38
TABLE 17 AUXILIARY STATUS REQUEST RESPONSE FORMAT - BINARY PROTOCOL. ....................................... 40
TABLE 18 AUXILIARY STATUS REQUEST RESPONSE MAPPING (STATUS WORD1). ......................................... 41
TABLE 19 AUXILIARY STATUS REQUEST RESPONSE MAPPING (STATUS WORD2). ......................................... 42
TABLE 20 DETAILED INPUT/OUTPUT MUTE STATUS REQUEST RESPONSE FORMAT - BINARY PROTOCOL. .......... 44
TABLE 21 DETAILED LOGIC I/O STATUS FOR CERBERUS REQUEST RESPONSE - BINARY PROTOCOL.................. 46
TABLE 22 COMMAND ID - SELECT A SECTION. .................................................................................... 48
TABLE 23 COMMAND ID - SELECT A COMBINATION OF SECTIONS. .......................................................... 50
TABLE 24 COMMAND ID - UN-MUTE A SECTION................................................................................. 51
TABLE 25 COMMAND ID - MUTE A SECTION...................................................................................... 53
TABLE 26 COMMAND ID - DUCK A SECTION....................................................................................... 55
TABLE 27 COMMAND ID - DUCK A COMBINATION OF SECTIONS............................................................. 57
TABLE 28 COMMAND ID - PLAY PRE-RECORDED MESSAGE.................................................................... 60
TABLE 29 COMMAND ID - STOP PRE-RECORDED MESSAGE. .................................................................. 62
TABLE 30 COMMAND ID - GET WAVE PLAYER STATUS.......................................................................... 63
TABLE 31 GET WAVE PLAYER STATUS RESPONSE FORMAT - BINARY PROTOCOL. ......................................... 63
TABLE 32 WAVE PLAYER STATUS WORD RESPONSE MAPPING. ................................................................ 63
TABLE 33 COMMAND ID - AUTOGAIN CONTROL. ................................................................................ 64
TABLE 34 COMMAND ID - MUTE/DUCKING CONTROL. ........................................................................ 64
TABLE 35 COMMAND ID - OUTPUT MUTE CONTROL............................................................................ 66
TABLE 36 COMMAND ID - OUTPUT DUCKING CONTROL. ...................................................................... 67
TABLE 37 COMMAND ID - SELECT PRESET. ........................................................................................ 69
TABLE 38 COMMAND ID - INPUT MUTE CONTROL............................................................................... 70
TABLE 39 COMMAND ID - REDUNDANT HOST CONTROL....................................................................... 71
TABLE 40 TERMINATOR CODE - BIT MAPPING..................................................................................... 73
TABLE 41 SIZE/STATUS HEADER - BIT MAPPING. ................................................................................. 75
TABLE 42 TERMINATOR VALUE. ....................................................................................................... 76
TABLE 43 CRC CALCULATION CODE. ................................................................................................. 76
Objective.
WinControl External Control API v2.11 5
1. Objective.
The objective of this document is to describe the Application Programmer’s Interface (API)
for remote control of the WinControl software through an auxiliary serial port (COM port or
virtual COM port). This document focuses on the interface format which is described in
section 3. Refer to the External Control related topics in the WinControl help file for detailed
information regarding the WinControl related configuration options.
This document is written for WinControl revision 2.72.0.0.
Terminology:
PC or Controller
PC running the WinControl software (must be at least the Service version of WinControl).
Front-end
External machine controlling the PC (e.g. a PLC).
Network or Net
RS-485 or Ethernet network with JBL Intellivox or JBL AXYS devices controlled by the PC. It
may consist of multiple subnets.
Subnet
Section of the complete Net. All units that are connected to a single COM port make up one
subnet connected to this port (in case of an RS-485 network). The number of subnets can be
configured in WinControl.
MaxInt
Maximum 32 bit integer value (2
32-1
- 1).
MaxWord
Maximum 32 bit word value (2
32
- 1).
Conventions:
- Hex values are indicated with a 0x prefix.
- Bit 0 indicates the LSB (Least Significant Bit).
Objective.
WinControl External Control API v2.11 6
Revision history:
Revision Date Description
1.91 22122009 Start of revision control.
2.00 03102011 Various additions for redundant amplifier control (section 2.6).
2.01 21112011 Minor changes.
2.02 03052012 CRC calculation procedure added.
2.03 06062012 Minor changes.
2.04 30052013 Duck a section (3.3.6) and Duck a combination of sections
(3.3.7) command descriptions added.
2.05 06062013 Output ducking control (3.3.12) command description added.
2.06 07052014 Changes for maximum number of subnets increased from 16 to
20 for WinControl v2.70 and up.
2.10 20102014 Re-branded and small changes.
2.11 18022015 Additions for terminator code.
Front-end ID specifier field and additional response
SizeandStatus header specifier added (see 3.4.1).
Table 1 Document revisions.
General.
WinControl External Control API v2.11 7
2. General.
2.1 Serial port settings
Default baud-rates from 1200 to 115k2 bits/s are supported, the connection can be set-up
for 5 to 8 data bits, 1 or 2 stop bits can be used and various parity related options are
available. Refer to Fig 1 for a WinControl configuration example. Note that at least the
Service version of WinControl is required for any External Control related editing.
Fig 1 General External Control port configuration options in WinControl.
Table 2 shows the RS-232 connection on the PC side (9p male d-Sub connector). For an un-
balanced serial connection only RX, TX and GND are required.
A balanced serial connection is advised for cable lengths exceeding a few meters. If a
balanced connection has to be made, the modem control signals (DTR, DSR, RTS and CTS)
can be used to power a RS-232 to RS-422/RS-485 converter on the PC side. In this case the
serial connection must support full-duplex mode.
General.
WinControl External Control API v2.11 8
RS-232
mnemonic
RS-232 pin #
Description (PC)
CD 1 Carrier Detect
RX 2 Data received by the PC
TX 3 Data transmitted by the
PC
DTR 4 Data Terminal Ready
GND 5 Ground
DSR 6 Data Set Ready
RTS 7 Request to Send
CTS 8 Clear to Send
RI 9 Ring Indicator
Table 2 RS-232 pin description.
If communication over Ethernet is required, a 3
rd
party Ethernet to Serial device (which
registers itself as a virtual COM port) can be used.
2.2 Protocol options.
Since WinControl v2.6.0.5 two protocols are supported, the required protocol can be set in
WinControl (see Protocol field in Fig 1).
Binary
This is the default protocol, unless specified otherwise all information is this document
refers to the Binary protocol. The Binary protocol is always used internally, any other
protocol (currently only ASCII hex) is supported by software protocol conversion
immediately after receive and directly before transmission.
ASCII hex
This protocol can be used if the Front-end is not capable of sending packets with arbitrary
binary content. In this case the hexadecimal value of each byte is represented by two ASCII
characters (each 4-bit nibble in the binary byte maps to one ASCII character).
Section 3.1.1 describes the details related to the supported protocols.
2.3 Transmit delimiters.
Since WinControl v2.12.0.0 arbitrary start and end delimiter strings can be added to the
response (i.e. the packet that is sent from controller PC to Front-end) if the Protocol is set to
ASCII hex. The start and end delimiter can be defined in WinControl (see Fig 1).
General.
WinControl External Control API v2.11 9
2.4 Monitoring of the connection.
The External Control connection to the Front-end can be monitored by a software watchdog
timer. Any of the available commands (which will be described in section 3) can serve as a
watchdog trigger command. An example of the configuration options provided by
WinControl is shown in Fig 2.
Fig 2 External Control watchdog timer configuration in WinControl.
General.
WinControl External Control API v2.11 10
2.5 Redundant host.
For redundancy purposes it might be required to have 2 PCs controlling and monitoring the
same network. The following has been implemented in order to achieve synchronized
network access for a fully redundant 'hot system' controller pair arrangement:
- Parameters related to redundant host configuration can be set-up from within
WinControl.
- The Front-end can request the 'health status' of a controller PC (Availability score,
section 3.3.1.4).
- The Front-end can switch a controller to Master or Standby (see section 3.3.15). The
current controller status (Master or Standby) can also be requested (see Table 15).
- An additional Ethernet link between the 2 controllers is required (TCP/IP), the related
parameters can be edited from within WinControl. The link is used to synchronize the
controller status and the network access. A link failure can also be monitored by the
Front-end (see Table 9).
- Commands that write to devices on the network can be discarded if the current
controller status is Standby. This can be decided by the Front-end on a 'command-by-
command' basis (see section 3.4.1).
- All commands that access devices on the network will be discarded if the current
controller status is Standby and there is no link to the remote Master controller.
- A Standby controller has less rights compared to a Master controller:
o If the Standby controller times out during claiming of the network ownership, it
will not access the devices.
o After device access the Standby controller tries to grant the ownership of the
network to the Master controller.
o If WinControl is in Scanning mode (it is polling the status of connected devices)
the scan speed is reduced for the Standby controller.
o The Standby controller is never allowed to access devices if there is no link to the
Master.
o The Standby controller will not re-configure any redundant amplifiers (see
section 2.6).
- A controller will always start-up as a Standby controller. Secondary tasks like the initial
Netscan, loading of the WinControl Scene etc. will be delayed until the link between the
controllers has been established. Which controller will become the preferred Master can
be configured from within WinControl (this request can of course only be honoured if
both controllers are Standby during establishing of the link). If the Front-end switches a
controller to Master (see section 3.3.15), the secondary tasks as referred to above will
be scheduled for execution.
- On time-out of the external control watchdog timer (which can be used to monitor the
integrity of the connection from the Front-end, see section 2.4) the local controller will
be switched to Standby if required (and the remote to Master) after all pending
commands have been processed. Depending on the configuration of the watchdog
timer, additional commands (e.g. Un-mute all output channels) might need to be
executed before the local controller is switched from Master to Standby. Note that the
controller status is not switched if it is already Standby. In the situation where the link
between the Front-end and a single controller is interrupted, the Front-end will normally
notice this before the watchdog timer times-out because the controller does not
General.
WinControl External Control API v2.11 11
respond on a command sent by the Front-end. If the Front-end notices that the link is
broken, it will normally set the other controller to Master. The controller with broken
link then automatically becomes Standby (if the Ethernet link is established). So usually
the controller will be Standby when it's watchdog timer times out, unless the Front-end
has no connection to both controllers.
Redundant host related support is implemented for WinControl >= v2.6.0.0.
General.
WinControl External Control API v2.11 12
2.6 Redundant amplifiers.
Some installations require the application of redundant/spare amplifiers that can
automatically replace/'take over' a 'faulty' amplifier. WinControl Service version allows the
configuration and control of redundant amplifiers.
Redundant amplifier control operates on 'systems', each system consists of:
- A redundant amplifier.
- Up to 8 normal amplifiers.
- A control device (Cerberus) that senses the failure relays of the amplifiers and
autonomously controls external relays to replace a 'faulty' amplifier with the redundant
amplifier.
- External (loudspeaker) relays with power supply and redundant amplifier dummy loads.
The following has been added to the External Control interface in order to support the
monitoring/control of redundant amplifier systems:
- Automatic re-mapping of addressed devices (address 'translation') to ensure that the
proper commands are sent to the redundant amplifier in case it has replaced a 'faulty'
amplifier, see section 3.2.3.
- Automatic preset re-mapping for the redundant amplifier. If a Select preset command is
received (see section 3.3.13) for a device that is currently 'taken over' by a redundant
device (amplifier), this preset command will be re-mapped in order to select the preset
of the redundant amplifier as configured in WinControl's Redundant amplifier
configuration GUI. This preset re-mapping is dependent on the redundant amplifier re-
configuration options (see WinControl help file). The associated redundant amplifier
system must be enabled in order for preset re-mapping to take place.
- Redundant amplifier related system combined failure flags (see Table 9), these indicate
for example if at least one of the available systems has it's redundant amplifier activated
or if there are errors related to the configuration (e.g. missing files that are required to
re-configure a redundant amplifier after 'take over').
- Failure request command values for 64 bit general failure word (in order to
accommodate the additional redundant amplifier system related failure flags), see Table
6 and Table 7.
- Detailed redundant amplifier related failure request commands, e.g. to indicate for
which system(s) the redundant amplifier has 'taken over' an amplifier, see section
3.3.1.5 and 3.3.1.6.
- Added status information to check if redundant amplifier control is enabled in
WinControl, see Table 15.
- Added status request commands to obtain the status of the digital inputs and outputs of
Cerberus devices (to check which amplifier in a system has been replaced/'taken over'
by the redundant amplifier. See section 3.3.1.14 and 3.3.1.15.
Note that the re-configuration process (e.g. uploading settings and/or selecting presets after
the redundant amplifier has 'taken over') is controlled from WinControl, as configured in the
Redundant amplifier configuration GUI.
Redundant amplifiers related support is implemented for WinControl >= v2.45.0.1.
Commands.
WinControl External Control API v2.11 13
3. Commands.
3.1 General.
3.1.1 Command structure.
All commands that the Front-end should send, consist of a packet with fixed length. This
length should be 16 bytes (Binary protocol) or 32 characters (ASCII hex protocol). The packet
should be formatted according to the structures represented in Table 3 and Table 4, see
also section 2.2.
Parameter <Address> <Command
ID>
<Value> <Terminator
code>
<Terminator
value>
Nof bytes 4 4 4 2 2
Table 3 General command structure of incoming packet - Binary protocol.
Parameter <Address> <Command
ID>
<Value> <Terminator
code>
<Terminator
value>
Nof chars 8 8 8 4 4
Table 4 General command structure of incoming packet - ASCII hex protocol.
Address
The Address is used to directly access specific subnets, units and/or groups on the Network,
refer to section 3.2.
Command ID
Each command has a unique Command ID, described in section 3.3.
Value
The Value parameter is used to further characterize the Command ID, described in section
3.3.
Terminator code and value
The Terminator code and Terminator value are used for packet integrity checking and
response formatting, they are described in section 3.4.
Commands.
WinControl External Control API v2.11 14
3.1.2 Little endian coding.
All multiple byte values are ‘Little Endian’ coded. This means that if, for example, the 4 bytes
of an identifier together represent a 32-bit integer or word value (e.g. Address, Command
ID), the Least Significant Byte occurs first in the structure.
Note that for the ASCII hex protocol (see section 2.2), ‘Little Endian’ coding is not applied to
the 4-bit nibble level; only the bytes of the binary words are ‘Little Endian’ coded. For
example a binary value of 250 (0xFA) will be represented as 2 ASCII characters FA in ASCII
hex.
The example below clarifies this, note that all implemented commands are described in the
following sections.
Example:
Address = 0x0000 0000 Global addressing
Command ID = 0x0000 00C0 Autogain control
Value = 0x0000 0001 Enable autogain
Terminator code = 0x0001 Checksum enabled
Terminator value = 0x00C2 Checksum value
Binary protocol:
Resulting packet formatted according to Table 3 (16 bytes shown as hex values):
[0x00, 0x00, 0x00, 0x00, 0xC0, 0x00, 0x00, 0x00, 0x01, 0x00, 0x00, 0x00, 0x01, 0x00, 0xC2,
0x00]
Note that each individual byte value is indicated with the 0x prefix. The total command
length is 16 bytes.
ASCII hex protocol:
Resulting packet formatted according to Table 4 (32 characters shown as ASCII string):
[00000000C0000000010000000100C200]
Note that the hexadecimal value of each individual byte value is represented by 2 characters
in the string. The total string length is 32 characters. The [ and ] characters are not a part of
the actual command string. The WinControl Command/Log window (bottom pane) contains
a tab labelled External Control, this tab shows information regarding the parsed External
Control commands.
Commands.
WinControl External Control API v2.11 15
3.1.3 PC response.
Following holds with respect to the PC response (i.e. packet that is sent to the Front-end):
- Any response is initiated by a packet that is sent by the Front-end (incoming packet).
- WinControl is able to respond to all incoming packets.
- This response can be enabled or disabled for each incoming packet individually by
setting the proper bit in the Terminator code (see section 3.4.1).
- A terminator can be added to the response for each packet individually by setting the
proper bit in the Terminator code (see section 3.4.1). The length of the terminator will
be 4 bytes (Binary protocol) or 8 characters (ASCII hex protocol). The Front-end may use
the Terminator value for integrity checking of the response.
- The Address and Command ID header can be pre-pended to the response for each
packet individually by setting the proper bit in the Terminator code (see section 3.4.1).
This will increase the response length by 8 bytes (Binary protocol) or 16 characters (ASCII
hex protocol).
- The response size can be pre-pended for each packet (Size/Status header). This is also
controlled by the Terminator code (see section 3.4.1 for further details).
- The response packet is ‘Little Endian’ coded.
- Unless stated otherwise, the incoming command Value is responded after the command
has been successfully handled.
- By default 0xFFFF FFFF (-1) is responded if the incoming command could not be properly
executed. For WinControl >= v1.98.0.22 this is also the case for an unknown command
ID, lower revisions did not respond for unknown commands.
- Since WinControl v2.12.0.0 the response packet for the ASCII hex protocol can be
wrapped between arbitrary start and end delimiter strings. The delimiter strings are fully
configurable from WinControl (see also section 2.3).
- For commands that access devices on the network the total response time is depending
on:
o The baud-rate of the External Control port.
o The number of devices and number of subnets on the network for which the
command is intended.
o The complexity of the command.
o The actual baud-rate set for each of the subnets (configurable in WinControl).
o The actual configuration of WinControl’s retry scheme (in case of net access
errors).
o The setting of 'Refresh device status if not scanning' (available in WinControl
External control options on the General tab), if WinControl is not in Scanning
mode.
- A simple Front-end emulator software is available on request in order to evaluate the
response time in a specific set-up.
Commands.
WinControl External Control API v2.11 16
3.2 Address.
3.2.1 Address specifier format convention.
The 32 bits Address specifier is reserved to directly access specific subnets, devices and/or
groups on the Network. Table 5 describes the Address specifier format. Note that some
commands (e.g. Play pre-recorded message command described in chapter 3.3.8) do not use
the contents from the Address specifier. Refer to each of the command descriptions in
section 3.3 for details.
Address Description
NO DIRECT ADDRESSING
0x0000 0000
Use 0 for commands that require no direct addressing or to access all
detected devices.
DIRECT ADDRESSING
Device address (single) / device low address (range)
0 Generic (all addresses).
For generic addressing byte 0 and byte 1 must be set to 0.
1..126 Single address:
If byte 1 <= byte 0, byte 0 fully represents the single address.
Range address:
If byte 1 > byte 0 the range defined by [byte 0 .. byte 1] is
addressed (if both bytes contain a valid address).
Byte 0 (LSB)
127..255 Reserved, this represents a non-valid address.
Device high address (range)
Range addressing is added for WinControl >= v1.98.0.18.
0 The addressing is defined by byte 0.
For generic addressing byte 0 and byte 1 must be set to 0.
1..126 Single address:
If byte 1 <= byte 0, byte 0 fully represents the single address.
Range address:
If byte 1 > byte 0 the range defined by [byte 0 .. byte 1] is
addressed (if both bytes contain a valid address).
Byte 1
127..255 Reserved, this represents a non-valid address.
Commands.
WinControl External Control API v2.11 17
Subnet related
0 Generic (all subnets).
1..20 Specific subnet. This subnet must be present in WinControl else
the address is not valid. For WinControl v2.70 and up the
maximum is 20.
Byte 2
21..255 Reserved.
Byte 3 (MSB)
Reserved for groups, must be 0.
Table 5 Address specifier format.
Following notes hold for commands that use direct addressing, commands that do not use
direct addressing should set the Address specifier to 0.
Notes:
- The maximum number of supported subnets depends on the WinControl version; for
version >= v2.70.0.0 a maximum of 20 subnets is supported, for lower revisions this
maximum is 16.
- Range addressing is added for WinControl >= v1.98.0.18. For lower WinControl revisions
the value of byte 1 should be set to 0.
- Address 'translation' may occur for redundant amplifier systems (see section 3.2.3).
- Some addressing examples are listed hereafter:
o Address 0x0000 0000 accesses all devices on all available subnets.
o Address 0x0001 0000 accesses all devices on the first available subnet (note that
the subnet numbering in WinControl is 0-based by convention, i.e. the first
subnet is referred to as SubNet 00 in WinControl).
o Address 0x0001 000A (specifically) accesses device with address 10 (= 0x0A) on
the first available subnet (the device address numbering in WinControl is 1-
based).
o Address 0x0001 090A also (specifically) accesses device with address 10 (= 0x0A)
on the first available subnet, the upper range address is smaller than the lower
range address so the lower range address prevails.
o Address 0x0001 0E0A (specifically) accesses devices with addresses 10..14 (=
0x0A .. 0x0E) on the first available subnet.
o Address 0x0001 0E00 is an example of an invalid address.
o Address 0x0000 000A (specifically) accesses all devices that have unit address 10
(= 0xA) on all available subnets.
o Address 0x0000 0E0A (specifically) accesses all devices with addresses 10..14 (=
0x0A .. 0x0E) on all available subnets.
o Address 0x0000 xxxx and 0x0001 xxxx are equivalent if the network contains only
one subnet.
Commands.
WinControl External Control API v2.11 18
3.2.2 Master and slave devices.
Most commands that are described in section 3.3 which use the Address specifier, perform
no action if only a slave unit is specifically addressed (for a device that contains master and
slave DSP, e.g. an IntelliDisc-DS90). An exception to this rule are the Failure & status request
related commands described in section 3.3.1. This means that it is for example possible to
request the status properties of a single slave device, however it is not possible to mute a
single slave device.
If a master unit is specifically addressed, the corresponding slave unit (if existing) is
automatically taken into account. An exception to this rule are the Failure & status request
related commands described in section 3.3.1.
3.2.3 Address translation for redundant amplifier control.
Address 'translation' may occur in case of activated Redundant amplifier control (see section
2.6). If an amplifier in a redundant system has been 'taken over' by it's associated redundant
amplifier, the address of the 'faulty' amplifier will be automatically translated into the
address of the redundant amplifier. The front-end does not need to care about changing
command addresses in case of a 'faulty' amplifier in a redundant system.
The redundant amplifier can still be accessed (e.g. by Single device addressing) however if it
is detected that both the redundant as well as the 'faulty' amplifier are accessed by the
received command packet (which may for example occur if the Address specifier indicates a
Range address as indicated in Table 5), the command intended for the redundant amplifier
is discarded and the command intended for the 'faulty' amplifier is translated to the
redundant amplifier. The only exceptions to this rule are the Failure & status request related
commands with Address specifier that accesses all devices on the network or on a specific
subnet (in this case the redundant amplifier is also accessed, however this is a 'request only'
command so it cannot result in conflicting situations). Note that redundant amplifier control
and re-configuration can be configured within WinControl (see section 2.6 and the
WinControl help file for details). Address translation will not occur if Redundant amplifier
control is disabled (or if the associated redundant amplifier system is disabled).
In this respect it is important to observe that device network addresses in WinControl are
not affected by the status of a redundant amplifier system, only the incoming External
Control commands are automatically re-mapped to the redundant amplifier if it has taken
over a 'faulty' amplifier.
Commands.
WinControl External Control API v2.11 19
3.3 Command ID and Value.
Each command is characterized by a unique 32 bits Command ID and a 32 bits Value,
described in the following sections.
3.3.1 Failure & status request.
The Front-end can use this command to obtain failure or status information about the net
and all connected units. The Value parameter is used to specify the request (see Table 6).
Front-end command:
Command ID
Value Description
Bit 0 and 1 define the response formatting as
described below:
00
Combined request.
01
Detailed request.
Response only contains addressed devices
that currently show a failure (or are
'missing').
10
Full detailed request.
Response contains all addressed devices
Value bit 0 and
1 (0 = LSB)
11
Reserved.
Value bit 2 Bit 2 defines the request type; status or
failure:
0 Failure related request.
1 Status related request.
Value bit 3 Bit 3 defines the length of the General
failure/status word (see for example Table 9):
0 32 bit (4 bytes) length.
1 64 bit (8 bytes) length.
This was added for WinControl v2.45.0.1.
Earlier revisions only support 32 bit.
Value bit 4..7 Reserved, must be 0.
Value bit 8..15 Bit 8..15 define the request index. This should
be used to further specify the failure or status
info that is required.
0x0000 0000
0..MaxInt
Value bit
16..31
Reserved, must be 0.
Table 6 Command ID - Failure & status request, overview of bit mapping.
Commands.
WinControl External Control API v2.11 20
All valid Value parameters that are currently implemented are listed in Table 7. If a Failure &
status request command with a Value that is not listed in Table 7 is received, the response
might not be predictable. Only use the documented Values listed in Table 7.
Value Description Details
General failure related, request index = 0
0x00000000 Combined failure request
(32 bit general failure
word).
All failures are combined in a 4 byte failure
word.
See section 3.3.1.1.
0x00000008 Combined failure request
(64 bit general failure
word).
All failures are combined in a 8 byte failure
word.
See section 3.3.1.1.
Supported for WinControl >= v2.45.0.1.
0x00000001 Detailed failure request
(32 bit general failure
word).
Failure information of individual devices is
responded according to Table 10. Only
addressed devices that have a failure (or are
'missing') are included in the response. See
section 3.3.1.2.
0x00000009 Detailed failure request
(64 bit general failure
word).
As above with 8 byte general failure word.
Supported for WinControl >= v2.45.0.1.
0x00000002 Full detailed failure
request
(32 bit general failure
word).
Failure information of individual devices is
responded according to Table 10. All addressed
devices are included in the response,
regardless if they exhibit a failure or not. See
section 3.3.1.3.
0x0000000A Full detailed failure
request
(64 bit general failure
word).
As above with 8 byte general failure word.
Supported for WinControl >= v2.45.0.1.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75