Oliver IGD TOCSIN 700 Installation And User Instructions Manual

Category
Carbon monoxide (CO) detectors
Type
Installation And User Instructions Manual

Oliver IGD TOCSIN 700 is a powerful and versatile gas detector control panel designed to monitor for a wide range of gases in various industrial and commercial settings. It features 8 configurable 4-20mA loop inputs, allowing you to connect and monitor multiple gas sensors simultaneously. The large 2x16 backlit LCD display provides clear and concise information, including real-time gas readings, alarm status, and system configuration.

Oliver IGD TOCSIN 700 is a powerful and versatile gas detector control panel designed to monitor for a wide range of gases in various industrial and commercial settings. It features 8 configurable 4-20mA loop inputs, allowing you to connect and monitor multiple gas sensors simultaneously. The large 2x16 backlit LCD display provides clear and concise information, including real-time gas readings, alarm status, and system configuration.

Tel:
Fax:
Email:
Web Site:
+44(0)161 483 1415
+44(0)161 484 2345
www.oliver-igd.co.uk
IGD
OLIVER
4a Pepper Road
Stockport
SK7 5BW
England
Oliver IGD Limited V16
TOCSIN 700
INSTALLATION
AND
USER INSTRUCTIONS
OLIVER IGD
INSTRUCTION DATA SHEET
This product must be earthed in accordance with local safety regulations.
The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
Standard voltage and frequency range is:-
AC Mains Powered 85 to 264 VAC 40 to 400 Hz
DC Low Voltage Powered 18 to 30V DC
Should the control panel be used in conjunction with portable generating equipment, care should be
taken to ensure that the electrical supply is within the tolerance band described above.
The control panel may be stored at temperatures between 0 C and 40 C. If stored at low temperatures
and then brought into a warmer environment, condensation may form on some components. In such a
situation , this condensation should be allowed to evaporate prior to use of the equipment. If stored at
high temperature, care should be taken to ensure that humidity condensation does not enter critical
electrical components, for example the power connector.
The Control Panel is designed to operate within specification for ambient temperature between 5 C
and 40 C, relative humidity up to 90% ( non-condensing ).
Do not use a Control Panel for protection applications that has not been calibrated. If calibration seals
are missing from the control panel or have been tampered with or broken, then the control panel must
be re-calibrated and sealed by a trained engineer..
Power Source 85 to 264 VAC (18 to 30V DC Option)
Power Consumption 40 Watts
Display 2 x 16 backlit LCD
Operating temperature 0 Deg C to 50 Deg C
Operating Humidity up to 95% Non Condensing
Accuracy +/-0.5% FSD
Resolution 1% of FSD
Response Time T90 in under 2.5s
Update Rate 1 Second
Size 255H x 265W x 100D mm
Weight 5.1Kg
Inputs 8 of 4-20mALoops
1 of RS 485 Comms Port
1 of RS 232 Comms Port
1 of RS 485 Detector Data Highway (Addressable Versions)
Outputs 3 off Configuable SPCO Relays 7ANon Inductive Load
1 off Fault Relay 7ANon Inductive Load
1 offAudio/Sounder Output SS 24V DC
1 Off Visual/Flasher Output SS 24V DC
CE Declaration Conforms to the requirements of the CE and low voltage
equipment directive. See declaration CE-700-03
00
o
o
warning !
OLIVER IGD
INSTRUCTION DATA SHEET
Tocsin 700 Panel Overview
2 x 16 LCD Display
22V DC Panel Power
Digital Inputs
Jog Wheel
3 off Configurable Relay Outputs
With Activation Indication Lamps
Sounder/Flasher
Outputs
Fault Relay Outputs
RS 485 Detector
Data Highway
Connector
(Addressable Versions)
Expansion
Connector
8 off 4-20mA Loop Inputs
Mains/DC Input
(Check Supply Option Before Use) Grounding Points
L N E 110/230V AC 50/60Hz
OLIVER IGD
Tocsin 700 Interface wiring
Sounder Alarm
Max Current
150mA 24V DC
These 3 relays can be assigned,
named, zoned etc using the Tocsin
700 operating software.
Dedicated fault relay output, this output
is energised in normal operation
In all Cases:
Relay contact ratings.
7A @ 250V AC Non-Inductive
7A @ 30V DC Non-Inductive
Spike suppression must be fitted
Note that FAULT relays are normally
energised on power up.
Addressable control panel versions only.
See 'Addressable Sensors' Section
24V DC
SOUNDER O/P
WARNING LAMP O/P
Enclosure
Ground
Enclosure
Ground
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 500M.
2.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 500M.
Blue
Red
Black
Red
Blue
TOCSIN 102/A
TOXIC GAS
DETECTORS
TOCSIN 102IR
FLAMMABLE GAS/
CO DETECTORS
2
+24V DC
B
A
GND
Note Flasher on
with alarm level 1.
Buzzer on with
alarm level 2.
NO NC
COM
AL1
AL2
AL3
0V DC
4-20mA IN
+24V DC
GND
GND
OLIVER IGD
OLIVER IGD
Tocsin 700 Interface wiring...continued
Enclosure
Ground
T103P Pellistor
Flammable Gas
Detectors
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 500M.
24V DC
4-20 OUT
0V DC
0V DC
4-20mA IN
+24V DC
GND
0V DC
4-20mA IN
+24V DC
GND
OLIVER IGD
OLIVER IGD
Tocsin 700 Interface wiring...continued
Tocsin 700 to Tocsin 103 2 wire Detector Series
Enclosure
Ground
4-20mA Toxic
And Oxygen Gas
Detectors
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 500M.
24V DC
SCREEN
4-20mA
0V DC
4-20mA IN
+24V DC
GND
OLIVER IGD
OLIVER IGD
Tocsin 700 Interface wiring...continued
Tocsin 700 to Tocsin 103 3 wire Detector Series
Enclosure
Ground
4-20mA Flammable
And CO Gas
Detectors
2
Cable Guidance Panel
It is imperative to use cabling which suits
the environment in which the T700 and its
sensors are to be used. The following is intended
as a guide.
Fit 1.5mm SQ cable for analogue systems
Fit 2.5mm SQ cable for addressable systems
Use
Pirelli LSX type cable for office/light commercial
un-zoned installations
Steel Wire Armored or CY cable for medium/heavy
industrial un-zoned installations
Mineral Insulated Pyro cable for all hazardous
area zoned installations.
Note in all cases the T700 Panel must be installed outside
of any hazardous area and must be supplied via
a fused spur.
2.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 500M.
Screen
0V DC
24V DC
4-20mA
GND
OLIVER IGD
OLIVER IGD
Tocsin 700 Interface wiring...continued, Addressable Systems.
120 Ohm Termination
Resistor on the Last
Detector in Line
2.5mm SQ Cable See Previous Note
Use Junction Boxes Suitable for Area Classification
24V
SCREEN
SCREEN
Rx
24V
24V
Tx
4-20
B
B
A
A
0V
0V
0V
Tocsin 102 Addressable
Series Detector Head
Red
White
Yellow
Blue
Black
Local Comms
Connector For
Palm Connection
24V
SCREEN
SCREEN
Rx
24V
24V
Tx
4-20
B
B
A
A
0V
0V
0V
Tocsin 102 Addressable
Series Detector Head
Red
White
Yellow
Blue
Black
Local Comms
Connector For
Palm Connection
+24V DC
B
A
GND
GND
OLIVER IGD
OLIVER IGD
Operating System
Operating System Overview
2 Line x 16 Character LCD Display
Output Relay 1 Lamp
Output Relay 2 Lamp
Output Relay 3 Lamp
System Fault Lamp
Power On
Jog Wheel Rotate the jog wheel to move
up and down the system
menus.
Press the jog wheel to make
a selection or to accept/silence
an alarm
The Tocsin 700 series gas detector control panels are designed to be as flexible in operation as
possible. The system software allows the owner/installer to configure the following functions:-
Configure input type, not only the selection of pre-programmed input gases but also the option
to define an input type and scale the incoming 4-20mA signal to match. For example,
pressure, temperature, distance etc
Decide alarm levels for each input and decide, rising,falling or latching alarms and which relay
to asign to which inputs to allow, zoning etc
Logical naming of inputs, for example 'boiler room 1'
Set the display scan rate
Zero and calibrate each channel from the control panel.
In addition the Tocsin 700 control panel can be 'hooked up' to a PC or PALM device via its serial
programming link to allow system configuration using Oliver IGD software. This allows not only pre-
configuration of the panel prior to commissioning but also a record of how the system was set up.
+Always refer to the shipping manifest and test schedule for confirmation of the shipped
configuration.
OLIVER IGD
OLIVER IGD
Accepting and Reseting Alarms
For most of its operating life the Tocsin 700 control panel and associated sensors will monitor for
whichever hazard it is configured for. The only requirement from the plant operator is to have the
system regularly calibrated, typically every 3 or 6 months depending on the nature of the gas
hazard. This section describes what happens at the control panel should the system detect a hazard
and go into alarm and how to accept the alarm and reset the control panel.
CH1 AL 1 TOTAL 2 OF 4
CH1 AL 1 TOTAL 2
CH1 AL 1
CH1 AL 1 TOTAL 2
BOILER 1 AREA 3
PRESS RESET ALL
BOILER 1 AREA 3
Step 1. The panel detects a gas hazard
Step 2. Operator Accepts The Alarms
Panel indicates which channel is in alarm
Panel indicates which alarm level has tripped
Panel indicates how many alarms in total have tripped
Relay outputs will activate dependant on the
system configuration
Alarm outputs (beacons and sounders) are active
if fitted.
The user programmed description for the sensor is displayed
Pressing the jog wheel will accept the indicated alarm. If there is more than one alarm tripped then
the next alarm is indicated on the display. Note that the total number of active alarms is indicated in
the top right of the display.
Once all alarms have been accepted the sounder output from the panel is de-activated, if a sounder
has been fitted it will silence. The relay outputs associated with the active alarms will still be
energised until the gas hazard has been cleared and the panel reset.
Once all active alarms have been accepted the display will read as follows:
Pressing the jog wheel at this stage will reset the system. This de-activates any energised alarm relays
depending on the panel user alarm programming and the 'beacon' output. If the gas hazard is still present
then the panel will go back into its alarm state after a few seconds otherwise the system reverts to normal
operation.
WARNING
It is important to have a site health and safety
response in place in the event of alarm activation.
Gas detection systems are an indication that a
problem may exist but should not be relied on as a
failsafe system. .
OLIVER IGD
OLIVER IGD
Tocsin 700 Menu System
1. Start up
Time in 24 hour format.
Company name is programmable in
EPROM Memory.
12:23:01
OLIVER IGD LTD
12:23:01
1 FLAM 0 % LEL
WARMING UP
BOILER ROOM 1
2. Warming Up
3. Normal Display Mode
Normal display mode.
In normal display mode the display will
auto scroll through all installed channels
at a user settable time. The time is
settable from 1 to 255 seconds.
Time is user programmable in seconds
and is programmed in the engineering
mode.
Normal display shows current channel in top left corner. Current channels measurement gas, reading
and measurement units.
The gas types are stored in EEPROM and can be reconfigured with the aid of a computer to display
any gas with up to four characters. There are 14 pre-configured gas types. The unit can store up to
sixteen different gas types.
FLAM CO NO NO2 CL2
HCL HCN NH3 O2 H2S
SO2 H2 FIRE CO2
There are three pre-configured measurement types.
%LEL PPM %VOL.
The unit can store up to four measurement types. Again these can be reconfigured with the computer
link software.
Warmup is displayed for thirty
seconds.
OLIVER IGD
OLIVER IGD
4. Pre-configured Measurement Types
1 FLAM 0 % LEL
1 O2 0 % VOL
1 CO 12 PPM
BOILER ROOM 1
NITROGEN STORE 1
CAR PARK LEVEL 1
Display with %LEL (Lower Explosive Limit) Display
Display with %VOL (% by Volume) Display
Display with ppm (Parts Per Million) Display
The second line displays the channels
description, up to sixteen characters long this is
editable using the Tocsin 700 menu system.
5. Menu System
The menu system is accessed by firstly selecting a channel. This is done by rotating the Jog Wheel.
Clockwise increases the channel indicated. Anti clockwise decreases the channel indicated. When the
switch is rotated the back light illuminates and the unit stops it's auto scrolling function. If no channel is
selected or if the button is not rotated within a minute then the unit returns to it's normal auto scrolling
mode. In auto scrolling mode each channel fitted to the control panel is sequentially displayed for a
fixed time period.
To select a channel to work on the Jog Wheel is pressed. This takes the user into the main menu.
The channel selected is shown on the top line. This information updates with the users commands.
The gas concentration also updates in this mode, this aids the user in calibration.
1 O2 0 % VOL
ZERO
Channel Number
Note configuration
menu’s are
password protected
Gas Type
Units
Current Reading
Current Command Option
Pressing the jog wheel will
activate this command.
`
OLIVER IGD
OLIVER IGD
1 O2 0 % VOL
1 O2 0 % VOL
1 O2 0 % VOL
1 O2 0 % VOL
ZERO
CALIBRATE
SET CAL BOTTLE
100
The bottom line of the display shows the command available for selection and is altered by
rotating the jog wheel.
5.1 The Zero Command
5.2 The Calibrate Command
1 O2 0 % VOL
ZEROING
With the panel in normal display mode,
rotate the jog wheel to the desired
channel and press the jog wheel. Now
rotate the jog wheel until the bottom line
of the display reads zero. At this stage
apply zero gas to the gas head and allow
the reading to stabilise.
Once the reading has stabilised
press the jog wheel and the bottom
line will change to read zeroing. The
Tocsin 700 now averages the
incoming signal for a few seconds
before applying any necessary zero
correction. Once complete the
bottom line of the display changes to
read zero and the current reading
will shift as the zero correction is
applied.
1 O2 0 % VOL
CALIBRATING
This function allows the user to calibrate a channel.
As in the case of the zero function, select a channel to
be calibrated and rotate the jog wheel until the
'Calibrate' option appears on the bottom line of the
display.
The display set bottle will appear
for a few seconds to prompt the
input of the calibration gas set
point.
The bottom line of the display now changes to
allow the input of the calibration gas value. The
display will indicate the last value used to
calibrate the channel. Rotate the jog wheel:
Clockwise to increase the value.
Anticlockwise to decrease the value.
With the calibration gas applied to the gas head allow the reading
to stabilise then press the jog wheel. The display will change to
'calibrating' for a few seconds as the reading is averaged and new
calibration constants calculated. Once complete the display will
return to step A, the and another menu option can be selected
OLIVER IGD
OLIVER IGD
5.3 Set Alarm Level 1
5.4 Set Alarm Level 1 Type
1 O2 0 % VOL
1 O2 0 % VOL
SET ALARM LEVEL 1
SET ALARM 1 TYPE
1 O2 0 % VOL
1 O2 0 % VOL
20.9
RISING LATCHING
Allows the user to set the first alarm level
for this channel. Factory default is 20% of
range. Again this uses the current alarm
level and is adjusted using the rotation of
the switch.
This menu option sets the alarm type for
alarm level 1.
Change the set point by rotating the
jog wheel. Press the jog wheel to
update the set point.
Change the type by rotating the jog
wheel. Press the jog wheel to
update the alarm type.
Options are
RISING
RISING LATCHING
FALLING
FALLING LATCHING
OLIVER IGD
OLIVER IGD
5.5 Set Alarm 1 Relay
1 O2 0 % VOL
SET ALARM 1 RELAY1
1 O2 0 % VOL
3
Allows the user to set which relay is
activated in the event of an alarm1 being
breached on this channel. The main board
has three built in alarm relays. To set one
of these the Relay is set to 1,2 or 3. 1 being
the top relay on the right of the display.
If the user has additional relay boards
installed then the user can select one of
these relays as alarm output. One
additional relay board gives Relays 4 to 11
a second relay board gives relays 12 to 19.
Change the relay to be activated in
the event of an alarm by rotating
the jog wheel. Press the jog wheel
Note that any number of channels can be assigned to the same relay output thus providing for
common alarm output.
The user can set many different relay schemes for each channel.
Alarm if out of band (windowed). O2 depletion / enrichment.
Nominal O2 value 20.9
Setting Alarm 1 as falling with a value of 18 and Alarm 2 as rising with a value of 22. Setting
Alarm 1 relay to the same as Alarm 2 relay the user can wire one input to show out of band.
5.6 Editing The Channel Description
5.7 Change Channel
5.8 Engineer Mode
5.9 EXIT
1 O2 0 % VOL
1 O2 0 % VOL
DESCRIPTION
ENGINEER
1 O2 0 % VOL
1 O2 0 % VOL
NITROG N STOREE
NITROGEN STORE
Rotating the jog wheel causes the current
character to change. Once the desired
character is displayed press the jog wheel
to accept it and move on to the next
character to be edited. Once the desired
text string is complete press and hold in the
jog wheel. The display will flash to indicate
the end of text edit mode. Release the jog
wheel and the newly edited text string is
accepted.
Note that to delete text part way
through a text string hold down the jog
wheel until the display flashes.
Everything past the edit cursor will be
erased.
OLIVER IGD
OLIVER IGD
This allows the user to edit the description shown
when the unit is in normal display mode. This
description is also used in Alarm indication to
show alarm locations.
Allows the user to change channel being edited. This allows the user to stay in the menu system
rather than going out and coming back in.
A single button press will increment to the next channel. A press and hold will flip through all the
channels and rotate to the beginning when the last channel has been reached.
Allows the user to set channel properties. See
engineering menus.
Returns user to normal display. Auto scrolling initiates and back light turns off.
OLIVER IGD
OLIVER IGD
6. Engineers Menu
The engineers menu allows the user to access engineering functions.
Item 1 Range
Allows the engineer to change the range of the channel. This item has ten pre-set ranges, 1, 5,
10,25, 50, 100, 200, 500, 1000, 2000 and 3000. These should cover 90% of the ranges required
and are selected by using the rotation of the switch. For the ranges these do not cover there is a
custom range editor. This is accessed by selecting CUSTOM from the ranges menu. On selecting
CUSTOM the editor will display the channels current range. This is edited by rotating the switch.
Once settle at the value required a button press stores this value to memory.
Item 2 Measurement.
Allows the engineer to set the units of measurement for the channel. These select the four types
from memory %LEL, PPM, %VOL being the three defaults. The fourth gas type is configurable
using the editor. Displaying the current reading and rotating the switch allows the value to be
changed. These units displayed are the units from EEPROM memory. So if they are edited using
the EEPROM memory editor which is a computer based program they will be displayed in this menu
item.
Item 4 Address.
Allows the engineer to select which physical channel the sensor is connected to. The channels in
the system are arranged logically i.e. in a four channel system these are labelled 1, 2, 3 and 4.
However these could be physically on channel 1, 3, 5, and 7. Install analogue sensors first and then
detect any sensors connected to the RS485 addressable channel. These then follow on sequentially
from the analogue channels. You cannot exceed 16 sensors.
Item 6 Gas Type.
Allows the engineer to change the displayed gas type for the channel. As shown in the explanation
of the display mode, these values are stored in EEPROM and are editable using the EEPROM
memory editor.
Item 3 Custom Measure
This menu item allows the user to set a custom measurement type. Once set up the custom measurement
type can be selected in the Measurement Menu.
Item 5. Sensor Type
Allows selection of the three basic types of detector, T102A for toxic gases and Oxygen, T102P for pellistor
detectors and T102IR for Infra Red detectors. This menu item must be correctly set if the detector is an
addressable unit on the RS485 input. This option makes no difference for standard analogue 4-20mA input
detectors.
Item 7 Custom Gas Type
This menu item allows the user to set a custom gas type. Once set up the custom gas type can be selected
in theGas Typet Menu.
OLIVER IGD
OLIVER IGD
Item 8 420 Out Zero
Allows the 4-20mA Output signal from the external add on card to be zeroed, see later
information.
Item 9 420 Out Cal
Allows the 4-20mA Output signal from the external add on card to be calibrated, see later
information.
Item 10 420 Out Address
Select the output on the 420 output add on card to be active for the current channel.
Item 11 420 Out Channels
Set how many 420 add on card channels are active (fitted to the system). Options are 4,8,12,16
(4 channels per add on card)
Item 12 Out Test
Select to test the card output, use the jog wheel to change the displayed 4-20mA output for the
channel output. Note a terminating resistor will be required (typically 220 Ohms) with a meter in
series in order to test the output.
Item 13 Change Channel
As in the Base Menu select to swap to the next sequential channel
Item 14 Set Time
Set the displayed time, uses 24 hour clock
Item 15 Set Date
Set the displayed Date, uses 24 hour clock
Item 16 Add Channels
Used to add extra analogue or addressable channels. This is a factory set option used to limit
the number of channels that are active, i.e 2,3,4,5,6,7 .....16 active channels
Item 17 Language
Select to toggle language from the list available.
Item 18 All Alarms
Select to enable of disable common alarm outputs across channels Item 10 Reset
Select to reset the control panel cancelling all current alarms and going back through warm up
Item 19 Reset
Reset the panel back to warm up mode.
Item 20 Find
Use this option to search the RS485 link if addressable detectors are fitted. You are first prompted
to enter the lowest detector address then the highest detector address. The Tocsin 700 then
searches for addresses between the lowest and highest address numbers installing each detector
it finds. Addresses can be in the range 0 to 65535. It takes approximately 5 seconds to search for
each address hence making it desirable to narrow the search range to save time.
Note that for the addressable detectors once the addresses have been found n the loop by the
Tocsin 700 you will then have to go through the channel set up on each address at the control
panel to set Range,Units and Gas Type. At this time you can also add logical name tags to match
the detectors.
Item 21 Upload Events
Select to upload events stored in memory via the RS232 port on the control panel (J1).
Note that the port must be selected as an RS232 output (see Item 21)
Typically a user could use a program such as Microsoft Hyperterminal to capture the transmitted
data. See later chapter on data capture for further information.
Item 22 Remote Port
Use this menu item to switch the control of the multifunction I/O port to either operate in RS232
mode using connector J1 (9 pin D) or RS485 on J19 (Screw terminal).
Item 23 Return
Select to return to the Base Menu.
OLIVER IGD
OLIVER IGD
OLIVER IGD
OLIVER IGD
BASE MENU
ZERO ZEROING Abort Continue
CALIBRATE SET CAL BOTTLE 3000 Abort Continue
SET ALARM LEVEL 1 600
SET LEVEL 1 TYPE RISING
RISING LATCHING
FALLING
FALLING LATCHING
SET ALARM LEVEL 2 1500
SET LEVEL 2 TYPE RISING
RISING LATCHING
FALLING
FALLING LATCHING
SET ALARM LEVEL 3 2000
SET ALARM LEVEL 3 TYPE RISING
RISING LATCHING
FALLING
FALLING LATCHING
SET ALARM 1 RELAY 1
SET ALARM 2 RELAY 2
SET ALARM 3 RELAY 3
DISABLE CHANNEL ENABLED
DESCRIPTION
CHANGE CHANNEL
ENGINEER
EXIT
BASE MENU
ZERO ZEROING Abort Continue
CALIBRATE SET CAL BOTTLE 3000 Abort Continue
SET ALARM LEVEL 1 600
SET LEVEL 1 TYPE RISING
RISING LATCHING
FALLING
FALLING LATCHING
SET ALARM LEVEL 2 1500
SET LEVEL 2 TYPE RISING
RISING LATCHING
FALLING
FALLING LATCHING
SET ALARM LEVEL 3 2000
SET ALARM LEVEL 3 TYPE RISING
RISING LATCHING
FALLING
FALLING LATCHING
SET ALARM 1 RELAY 1
SET ALARM 2 RELAY 2
SET ALARM 3 RELAY 3
DISABLE CHANNEL ENABLED
DESCRIPTION
CHANGE CHANNEL
ENGINEER
EXIT
1 O2 0 % VOL
NITROGEN STORE
Rotate to move down a menu. Pressing the button selects the sub menu one column
to the right
7. Menu System Overview Setup Menu’s
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27

Oliver IGD TOCSIN 700 Installation And User Instructions Manual

Category
Carbon monoxide (CO) detectors
Type
Installation And User Instructions Manual

Oliver IGD TOCSIN 700 is a powerful and versatile gas detector control panel designed to monitor for a wide range of gases in various industrial and commercial settings. It features 8 configurable 4-20mA loop inputs, allowing you to connect and monitor multiple gas sensors simultaneously. The large 2x16 backlit LCD display provides clear and concise information, including real-time gas readings, alarm status, and system configuration.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI