VDH LNG EXT RS D/N User manual

Type
User manual
Description: LNG EXT RS D/N
4-Keys Control panel Day/Night general (bticino/Playbus/Vimar/..) Doc.nr.: 110882
Type: USER MANUAL Number of pages: 6Version: V1.0
File: Do110882 LNG EXT RS Vimar Eikon 3M D_N User v10 EN.wpd
Software: 110338 LNG EXT RS VIMAR Version: V1.00 By: BJB Date: 14-10-2011
VDH Products BV - Roden - Holland Signed: File: Doc'11
Vimar Eikon 3M
User manual
Controller LNG EXT RS D/N
4-Keys Control panel LNG Day/Night
with external sensor and RS485
User manual Document no. : 110882 Version: V1.0
LNG EXT RS D/N Control panel general Client: Heinen & Hopman Page: 2 of 6
Disclaimer:
The information contained in this document is assumed to be accurate. However, VDH Products BV accepts
no liability for mistakes or errors and retains the right to change this document without notice.
Copyright Notice
Copyright 2011 VDH Products BV, Roden the Netherlands.
No part of this document may be reproduced without obtaining the prior written consent of VDH Products BV.
Publication
1st publication, 14-10-2011
TABLE OF CONTENTS:
Disclaimer ........................................................................2
TABLE OF CONTENTS .............................................................2
TECHNICAL DATA ................................................................3
FACTORY SETTINGS ..............................................................3
Adjusting potentiometers .......................................................3
CONTROL .......................................................................3
Adjusting the setpoint ..........................................................3
Switching display on / off .......................................................3
Switching day/night mode ......................................................3
PROGRAMMABLE FUNCTIONS .....................................................4
Programming parameters in general ..............................................4
Parameter table ..............................................................4
CONNECTION DATA ..............................................................5
User manual Document no. : 110882 Version: V1.0
LNG EXT RS D/N Control panel general Client: Heinen & Hopman Page: 3 of 6
TECHNICAL DATA:
Type :Controller panel LNG EXT RS D/N 3M/4-Keys (SET, DOWN, UP,D/N)
Type numbers :944.801679 Vimar Eikon, front black (without coverplate)
Method of mounting : Panel mounting on f.i. bticino/Playbus/Vimar/.. 3M(3-Modules) systems
Connections : At rear side
Cable fitting : screws
Dimension housing :Depends on Cover/Frame with maximum depth 50mm
Power supply : 24Vac G/Go (Go is internal connected to Gnd)
Power supply tol. : +/-10%
Input temperature sensor : KTY81 2-wire bn/wh (external)
Measuring system :2-wire
Measuring range :0/+30°C
Accuracy : 0.5°C
Readout :Digital 3-digit
Output signals : Measuring signal B1/M1 9°C = 2,6V (-50mV/°C),
Comp. setpoint signal Z1/M8 9°C/29°C = +1,0/+9,0V
Communication :RS485 network A/B/Gnd (2xTwisted-pair shielded min.0,5mm2)
Storage temp. : -20/+40°C
Working temp. : -5/+35°C
FACTORY SETTINGS:
Adjusting potentiometers;
There is an adjusting screw (set-screw) on the side with which the measured value can be
adjusted. The output power appropriate to the measuring value can be measured between the
screws B1 and M (19°C = 2,60V (-50mV/°C) f.i. 20°C = 2,55V).
CONTROL:
Adjusting the setpoint:
Hold down the SET key and set the desired value using the UP or DOWN keys
(adjustment per 0.1°C).
Switching display on / off:
By pressing the UP key and the DOWN key simultaneously the display can be turned off.
Press any key and the display will come on again.
Switching day/night mode:
By pressing the DAY/NIGHT key the controller can be switched to day or night mode.
The current day/night mode of the controller is shown on the front of the controller by two LED’s
(DAY and NIGHT) next to the display.
The controller starts at power-up always in day mode.
User manual Document no. : 110882 Version: V1.0
LNG EXT RS D/N Control panel general Client: Heinen & Hopman Page: 4 of 6
PROGRAMMABLE FUNCTIONS:
Programming parameters in general:
*The limits in which the setpoint can be set, depends on the settings of parameter 01
(Minimum value of setpoint) and parameter 02 (Maximum value of setpoint). Default these
values are set at respectively +9°C and +29°C.
*The temperature value shown in the display can be given an display_offset (parameter
03) in respect of the actually measured temperature value. This means that the output
value (the output voltage between the screws B1 and M) corresponds to the actually
measured value, while a different value can be shown in the display (measured_value +
display_offset). Default the display_offset value is 0.0°C.
The network number (parameter 04) has a range of 0 to 99. The value 0 means that this
controller is not active on the network. If the controller is connected to a network set
parameter 04 to an unique network number. So that every controller on the network has a
unique network number. Default the network-function is non-active (parameter 04 = 0).
Setting the parameters:
Press the DOWN key for more than 10 seconds to enter the programming mode. A blinking ‘P’
and parameter (number) ‘01' will appear in the display, to indicate this mode.
By pressing the UP or DOWN keys the desired parameter number can now be selected (see
Parameter table). When the desired parameter has been selected, the value of the parameter
can be read by pressing the SET key. This parameter value can now be changed by keeping the
SET key pressed while using the UP or DOWN key to change the value.
By releasing the SET key another parameter can be selected with the UP or DOWN keys.
If no key is pressed for 20 seconds, controller returns to its normal mode, and the measured
value is shown again in the display.
Parameter table:
Parameter Description Range default
1 Minimum value of setpoint +9°C ... +29°C +9°C
2 Maximum value of setpoint +9°C ... +29°C +29°C
3Display offset -9°C ... +9°C 0.0°C
4Network-number 0 ... 99 0
6 Illumination percentage display 0 ... 30 30
7 Maximal display on-time (0 = continuous) 0 ... 900 seconds 0 sec.
8Readout in Celsius or Fahrenheit 0 = Celsius
1 = Fahrenheit 0
95 Software version not adjustable 0 ... 255 xxx
96 Production year not adjustable 00 ... 99 xx
97 Production week not adjustable 1 ... 53 xx
98 Series number (x1000) not adjustable 0 ... 255 xxx
99 Series number (units) not adjustable 0 ... 999 xxx
Parameters 95 - 99 can only be readout
User manual Document no. : 110882 Version: V1.0
LNG EXT RS D/N Control panel general Client: Heinen & Hopman Page: 5 of 6
CONNECTION DATA:
Connection data LNG EXT RS (D/N) general drawing 072307w0:
User manual Document no. : 110882 Version: V1.0
LNG EXT RS D/N Control panel general Client: Heinen & Hopman Page: 6 of 6
Connection data CONTROL PANEL LNG EXT RS (D/N) drawing 071861w1:
BEWARE: GND and G0 are connected internally!!
Connection data LNG RS485 network drawing 030268w1:
Beware!! Every unit on the RS485 network must have a unique network number (parameter 04)..
-.-.-.-.-.-.-.-.-.-
@
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6