User manual Document no. : 110882 Version: V1.0
LNG EXT RS D/N Control panel general Client: Heinen & Hopman Page: 4 of 6
PROGRAMMABLE FUNCTIONS:
Programming parameters in general:
*The limits in which the setpoint can be set, depends on the settings of parameter 01
(Minimum value of setpoint) and parameter 02 (Maximum value of setpoint). Default these
values are set at respectively +9°C and +29°C.
*The temperature value shown in the display can be given an display_offset (parameter
03) in respect of the actually measured temperature value. This means that the output
value (the output voltage between the screws B1 and M) corresponds to the actually
measured value, while a different value can be shown in the display (measured_value +
display_offset). Default the display_offset value is 0.0°C.
The network number (parameter 04) has a range of 0 to 99. The value 0 means that this
controller is not active on the network. If the controller is connected to a network set
parameter 04 to an unique network number. So that every controller on the network has a
unique network number. Default the network-function is non-active (parameter 04 = 0).
Setting the parameters:
Press the DOWN key for more than 10 seconds to enter the programming mode. A blinking ‘P’
and parameter (number) ‘01' will appear in the display, to indicate this mode.
By pressing the UP or DOWN keys the desired parameter number can now be selected (see
Parameter table). When the desired parameter has been selected, the value of the parameter
can be read by pressing the SET key. This parameter value can now be changed by keeping the
SET key pressed while using the UP or DOWN key to change the value.
By releasing the SET key another parameter can be selected with the UP or DOWN keys.
If no key is pressed for 20 seconds, controller returns to its normal mode, and the measured
value is shown again in the display.
Parameter table:
Parameter Description Range default
1 Minimum value of setpoint +9°C ... +29°C +9°C
2 Maximum value of setpoint +9°C ... +29°C +29°C
3Display offset -9°C ... +9°C 0.0°C
4Network-number 0 ... 99 0
6 Illumination percentage display 0 ... 30 30
7 Maximal display on-time (0 = continuous) 0 ... 900 seconds 0 sec.
8Readout in Celsius or Fahrenheit 0 = Celsius
1 = Fahrenheit 0
95 Software version not adjustable 0 ... 255 xxx
96 Production year not adjustable 00 ... 99 xx
97 Production week not adjustable 1 ... 53 xx
98 Series number (x1000) not adjustable 0 ... 255 xxx
99 Series number (units) not adjustable 0 ... 999 xxx
Parameters 95 - 99 can only be readout