Hoshizaki American, Inc. RH1-SSB-HD-J-1 User manual

Type
User manual
INSTRUCTION MANUAL
MARCH 4, 1999
ISSUED:
HOSHIZAKI
TempGuard
TM
and SafeTemp
TM
MARCH 13, 2003
REVISED:
REACH-INS
2
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: HOSHIZAKI Technical Support Department
Phone: 1-800-233-1940 Technical Service
(770) 487-2331
Fax: (770) 487-3360
NOTE: To expedite assistance, all correspondence/communication MUST include the following
information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
Only qualified service technicians should attempt to install, service or maintain this
unit. No installation, service or maintenance should be undertaken until the
technician has thoroughly read this Instruction Manual. Likewise, the owner/manager
should not proceed to operate the unit until the installer has instructed them on its
proper operation.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
installation, maintenance and service of the unit.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call or write to the HOSHIZAKI Technical Support Department for
assistance.
IMPORTANT
3
• Please review this manual. It should be read carefully before the unit is installed and
operated. Only qualified service technicians should install, service and maintain the
unit. This manual should be made available to the technician prior to installation,
maintenance or service.
• Keep this manual with the unit for later reference.
I. INSTALLATION AND OPERATING INSTRUCTIONS .............................. 13
1.
CHECKS BEFORE INSTALLATION............................................. 13
2. HOW TO REMOVE FRONT PANEL ........................................... 14
[a] -SSB MODELS ...................................................................... 14
[b] -AAC MODELS ...................................................................... 14
3. LOCATION .................................................................................. 15
4. SET UP ....................................................................................... 15
5. ELECTRICAL CONNECTION ...................................................... 16
6. OVERFLOW PAN ....................................................................... 16
7. DRAIN CONNECTION ................................................................. 16
8. ELECTRICALLY HEATED CONDENSATE PAN (RFH1-SSB-HD) 16
9.
FINAL CHECK LIST.................................................................... 17
10. START-UP................................................................................... 18
[a] -SSB MODELS...................................................................... 18
[b] -AAC MODELS...................................................................... 18
11. ELECTRONIC CONTROL OPERATION (-SSB MODELS) ......... 19
12. ELECTRONIC CONTROL OPERATION (-AAC MODELS) ......... 27
13. DOOR REVERSING ................................................................... 29
II. CLEANING AND MAINTENANCE INSTRUCTIONS .............................. 30
1. CLEANING................................................................................... 30
2. MAINTENANCE .......................................................................... 31
PAGE
CONTENTS
4
II. INSTALLATION AND OPERATING INSTRUCTIONS
1. CHECKS BEFORE INSTALLATION
IMPORTANT
Refer to the NAMEPLATE for electrical specifications. The NAMEPLATE is located
on the RIGHT side wall of the cabinet interior. We reserve the right to make specifi-
cation and design changes without prior notice.
1) All tape, packing material and shipping cartons should be removed from the machine
prior to installation. The equipment should be inspected for any damage which may
have occurred during shipment. Concealed damage claims must be filed with the carrier.
a) Visually check that the refrigerant lines do not rub or touch other lines or surfaces
and that the fan blades turn freely.
b) Check that the compressor is snug on all mounting pads.
WARNING
The compressor bolts on FH3-SSB(-HD) models have been torqued down to
completely compress the springs during shipping.
Before turning the unit on, back the bolts off of the fastening points until no spring
compression is present. This will allow the compressor to float freely.
2) Remove all accessory containers before discarding the packing materials. Dispose of all
packing materials in a proper and environmentally responsible manner.
3) To remove the unit from the skid:
a) Move as close to the final location as possible.
b) Remove the four 5/8 in. bolts that secure the cabinet to the skid.
c) Block the cabinet securely, at a height of 8 inches (203 mm.) off the floor.
d) Attach the adjustable legs (or optional casters) to the bottom of the cabinet.
5
2.HOW TO REMOVE FRONT PANEL
[a] TempGuard MODELS with “Lift-Up” style Front Panel
• Lift the panel UP approximately 1/2 inch (13 mm.) and then pull it FORWARD.
[b] TempGuard with “Hinged” style Front Panel and all SafeTemp MODELS
1. Push the Front Panel UP approximately 1/2 inch (13 mm.) until it is disengaged from
the locking collars and stops.
2. Rotate the panel UP and AWAY from the face of the unit until it stops once more.
3. Pull the Front Panel FORWARD until the hinge assembly is in the LOCKED
position.
6
3. LOCATION
CAUTION
This unit is not intended for outdoor installation. The air temperature should
be within a 45° F to 100° F range. Extended periods of operation at temperatures
exceeding these limitations may cause unsatisfactory results.
For best operating results:
• The machine should be on a flat, level and solid (firm) foundation.
• The unit should not be located in a corrosive environment.
• The air temperature range at the location should be between 45° F and 100° F.
• The unit should not be near ovens, grills or other high heat producing equipment.
• The unit should be a minimum of 4 inches (102 mm.) from all walls.
• If the unit is flush against a wall, a minimum of 10 inches (254 mm.) overhead clearance
for proper ventilation should be provided.
4. SET UP
1) Position the unit in the selected location. Level the unit in both the front-to-back and
side-to-side directions. The feet are provided with hex flats in order to facilitate
adjustment. Turn clockwise to lower each leg, and counterclockwise to raise each
leg.
2) Install the optional shelves using the shelf support clips provided in the accessory pack.
Indexing holes are provided every five positions to assist you in locating the support
clips. Two and three section units may be equipped with center shelves which should
be installed after the main shelves are in place. The center shelf kit contains additional
clip(s) which support the center shelf when the main shelves on one side of the cabinet
are not aligned with the main shelves of the other side of the cabinet.* See the
diagrams below.
CAUTION
*Without this additional support, under adverse loading conditions, the shelf assembly
could tip.
7
5. ELECTRICAL CONNECTION
1) Cord-connected units should only be plugged into a 115 volt ±10%, 60 Hz. circuit with a
national and local electrical code approved, grounded wall receptacle. A separate
circuit with its own circuit breaker (HACR type) or fuse (LP-CC type) should be
provided. Refer to the NAMEPLATE for the proper electrical specifications.
2) Hardwired units should only be wired into the proper conduit, with its own circuit
breaker (HACR type) or fuse (LP-CC type). Refer to the NAMEPLATE for the proper
electrical specifications.
WARNING
Failure to use a proper breaker or fuse can result in tripped breaker, blown fuses or
damage to existing wiring.
6.OVERFLOW PAN (if applicable)
Note: For units with an
electrically heated
condensate pan, see section “8.”)
1) Assemble the overflow pan's brackets by
engaging the tab on the bracket through
the hole in the unit bottom and securing
with the four mounting screws provided.
2) Slide the plastic pan into place under the
vinyl hose on the back of
cabinet.
7.DRAIN CONNECTION (if applicable)
1) This unit is provided with an energy efficient automatic condensate water disposal
system and normally requires no drain connection.
2) High relative humidity and frequent door openings for long periods of time could cause
excessive condensate water to form.
3) If this occurs, condensate water will drain out through the overflow drain tube located
inside the back wall of the cabinet and into the Overflow Pan.
4) In the unlikely event that water is found in the Overflow Pan, call your HOSHIZAKI
Service Representative for assistance.
OVERFLOW
BRACKET
TAB
8
8. ELECTRICALLY HEATED CONDENSATE PAN (if applicable)
WARNING
Verify that power to unit is disconnected before installing pan.
1) Remove the panel that covers the recess in the back of the unit.
2) Route the wire found in the recess in the back of the unit through the wire cover and
install the wire cover to the unit.
3) Plug the cord (wire) routed in Step 2) into the female plug of the Condensate Pan.
4) Replace the panel to cover the recess
in the back of the unit.
5) Clip the heated pan onto the
mounting plate and attach to
the panel that covers the recess
in the back of the unit using the
four screws provided.
6) Install the Plug Cover to
the rear of the unit.
9. FINAL CHECK LIST
1) Is the unit level?
2) Is the unit located in a site where the ambient temperature will be within the
+45° F to +100° F range—year round?
3) Is there at least 10 inches (254 mm.) overhead clearance for proper ventilation?
4) Have all shipping cartons, tapes and packing materials been removed from the unit?
5) Has the power supply been checked or tested against the nameplate rating?
6) Has the unit been checked for shipping damage?
7) Has the Owner's Warranty Registration been filled out and forwarded to the factory?
9
10. START UP
[a] -SSB MODELS
This unit is equipped with an electronic control which has been preset at the factory to
maintain an average cabinet storage temperature of -3° F for Freezers and 36° F for
Refrigerators. Remove the Front Panel for access to the power switch—located on the
control box front—and turn the switch on.
IMPORTANT
There is a 2 1/2 minute normal delay before the refrigeration system starts.
Allow the unit to pull down and start cycling on the controller prior to loading it with food
products.
[b] -AAC MODELS
This unit is equipped with an electronic control which has been preset at the factory to
maintain an average cabinet storage temperature of -3° F for Freezers and 36° F for
Refrigerators. Remove the Front Panel for access to the power switch—located on the
control box front—and turn the switch on.
IMPORTANT
For Refrigerators, there is a 5 minute normal delay before the refrigeration system
starts. For Freezers, Defrost is initiated when the power supply is turned on.
Allow the unit to pull down and start cycling on the controller prior to loading it with food
products.
10
The Display Board is located on the right-hand side of the painted Control Panel between the top of
the Door and the Front Panel. From this area, information regarding the functioning of the unit can
be obtained. From the Display Board, various electronic controls and functions can also be
adjusted.
1) TEMPERATURE DISPLAY
The cabinet temperature is displayed (factory set is °F, but can be changed to read °C).
The cabinet temperature is updated every 20 seconds.
• During unit defrost (Freezer only) , the cabinet temperature is not displayed, “dEF” is displayed
in its place.
2) GUARDED ACCESS MENU
Three settings can be viewed and changed from this menu:
1. Temperature Setpoint - This setpoint is the value for the average cabinet temperature.
i.e., set point = 36°F, compressor on at 39°F, compressor off at 33°F.
2. Defrost Frequency - Ex. “dF 4” = 4 defrost cycles per day. This display has no
meaning for the refrigerator; see Note under “4) DEFROST”.
3. Units of Display - F = Fahrenheit, C = Celsius
To enter this menu, press and hold the up/down arrows simultaneously for 3 seconds. The
Temperature Setpoint will be displayed first. To change a value, push the up/down arrows until
the desired value is displayed. Then push “ENTER” to set the value and view the next setting.
If no change in the value is desired, press “ENTER”, and the next setting will be displayed.
At the end of the sequence, press “ENTER”, and the unit will return to normal display mode.
IMPORTANT NOTE: For change to take effect, must cycle through all three menus, and press
“ENTER” to return to standard display.
11. ELECTRONIC CONTROL OPERATION (TempGuard MODELS)
11
ALARM
3 beeps
every ten
seconds
4 beeps
every 10
seconds
[FREEZER
ONLY]
5 beeps
every 10
seconds
PROBLEM
[FREEZERS WITH BOARD
REVISION LEVEL 10 OR
BELOW AND ALL
REFRIGERATORS]
Cabinet temp. has
exceeded set temp. by
10°F for more than 2
hours.
[FREEZERS WITH BOARD
REVISION LEVEL 11 AND
ABOVE]
Cabinet temp. has
exceeded set temp. by
25°F for more than 4
hours.
(BOARD REVISION
LEVEL CAN BE SEEN ON
DISPLAY AT POWER UP)
Cabinet temp. has
remained below setpoint
by 8°F for more than 1
hour.
Defrost has taken longer
than 1 hour. Control
Board has terminated
defrost.
ERROR
MESSAGE
“E1” every 2
seconds,
alternating
with cabinet
temp. readout
“E2” every 2
seconds,
alternating
with cabinet
temp. readout
“E3” every 2
seconds,
alternating
with “dEF” or
cabinet temp.
RESET OPTIONS
Press “RESET.” If temp. has
returned to setpoint range, alarm
will stop and “E1” will clear.
If temp. is not back in range,
“RESET” will silence the alarm for
5 minutes. “E1” will continue to
flash.
Press “RESET. If temp. has
returned to setpoint range, alarm
will stop and “E2” will clear.
If temp. is not back in range,
“RESET” will silence the alarm for
5 minutes. “E2” will continue to
flash.
Press “RESET. Alarm will stop and
“E3” will clear.
If 4 consecutive defrosts take
more than 1 hour, a qualified
service technician must be
called.
3) ALARM / ALERT SIGNALS (*EXCLUDING GLASS DOOR MODELS)
12
RESET OPTIONS
Press “RESET.” Alarm will stop
and “E4” will clear when pressure
switch closes.
If switch trips 5 times in 1 hour
compressor will be stopped, and
a service technician must be
called.
Alarm automatically resets when
acceptable voltage is detected.
Press “RESET” to silence alarm for
5 minutes.
Alarm automatically resets when
acceptable voltage is detected.
Press “RESET” to silence alarm for
5 minutes.
Clean filter. Allow time for sensor
to react, then press “RESET.”
During alarm, press “RESET” to
silence alarm for 2 hours.
If this alarm occurs frequently, it
is recommended that a qualified
service technician be called.
Replace sensor. Alarm will reset.
During alarm press “RESET” to
silence buzzer for 5 minutes.
Replace sensor. Alarm will reset.
During alarm press “RESET” to
silence buzzer for 5 minutes.
PROBLEM
Compressor
discharge pressure
is outside normal
operating range.
Pressure switch
has been triggered
3 or more times in
1 hour.
Line voltage is too
high.
Line voltage is too
low.
Condenser filter
needs cleaning.
Cabinet temp. sensor
has failed.
Defrost temp. sensor
has failed.
ALARM
6 beeps
every 10
seconds
8 beeps
every 10
seconds
9 beeps
every 10
seconds
1 beep
every 10
seconds
Continuous
buzzer
Continuous
buzzer
ERROR MESSAGE
“E4” every 2 seconds,
alternating with
cabinet temp.
“E6” every 2 seconds,
alternating with
cabinet temp.
“E7” every 2 seconds,
alternating with
cabinet temp.
“CF” every 2
seconds, alternating
with cabinet temp.;
“CLEAN FILTER”
LED lights.
“E8” every 2 seconds
“E9” every 2 seconds,
alternating with the
cabinet temp.
13
ERROR MESSAGE
*“door” every 2
seconds, alternating
with the cabinet
temp.
*“E10” every 2
seconds,
alternating with
cabinet temp.
*EXCLUDING GLASS DOOR MODELS
RESET OPTIONS
*Close door. During alarm, press
“RESET” to silence buzzer for 3
minutes.
*Call qualified service technician.
*During alarm, press “RESET” to
silence buzzer for 18 hours.
PROBLEM
*Display: Door open
Display and sound:
Door open longer than
3 minutes.
*Freezer and
Refrigerator boards
not communicating
properly to control
compressor delay
(RFH only).
ALARM
*2 beeps
every ten
seconds
*10 beeps
every 10
seconds
14
a) HIGH TEMPERATURE ALARM FUNCTION
When the cabinet temperature has exceeded the set temperature by 10°F for more than 2
hours, an alarm buzzer sounds 3 beeps every 10 seconds, and an error message “E1” flashes
every 2 seconds, alternating with the cabinet temperature readout.
Note: Refrigerator, 10°F for more than 2 hours.
Freezer R10 and below, 10°F for more than 2 hours.
Freezer R11 and above, 25°F for more than 4 hours.
Reset Options:
If temperature has returned to setpoint range, pressing “RESET” on the Display Board will stop
the buzzer and clear the “E1” message.
If temperature is not back in range, pressing “RESET” on the display board will silence the
buzzer for 5 minutes. The “E1” message will continue to flash.
b) LOW TEMPERATURE ALARM FUNCTION
When the cabinet temperature has been below the setpoint by 8°F for more than 1 hour, the
buzzer will sound 4 beeps every 10 seconds, and “E2” will flash every 2 seconds, alternating
with the cabinet temperature readout.
Reset Options:
If temperature has returned to setpoint range, pressing “RESET” on the Display Board will stop
the buzzer and clear the “E2” message.
If temperature is not back in range, pressing “RESET” on the Display Board will silence the
buzzer for 5 minutes. The “E2” message will continue to flash.
c) DEFROST ERROR ALERT FUNCTION (FREEZER ONLY)
If, for any reason, the defrost takes longer than 1 hour, the alarm buzzer will sound 5 beeps
every 10 seconds, and “E3” will flash every 2 seconds, alternating with either “dEF” or the
cabinet temperature. If this alarm activates, the control board will automatically terminate the
defrost.
Reset options:
Pressing “RESET” on the Display Board will reset the buzzer and clear the “E3” from the
display.
IMPORTANT
If 4 consecutive defrosts take more than 1 hour, pressing “RESET” will only silence the buzzer
until the next defrost that lasts more than 1 hour. A qualified service technician must be called.
d) HIGH PRESSURE ALERT FUNCTION
In order to protect the compressor if the discharge pressure reaches a preset value (outside the
normal operating range), a switch will temporarily stop the compressor. At another preset
pressure, the compressor will attempt to restart. If the switch is triggered 3 times in 1 hour, the
buzzer will sound 6 beeps every 10 seconds, and “E4” will flash every 2 seconds, alternating
with the cabinet temperature. The same sequence will occur if the switch trips the fourth time in
1 hour.
15
Reset Options:
During the third and fourth trip alarm, the buzzer can be silenced by pressing “RESET” on the
Display Board.
The buzzer and display will automatically reset when the pressure switch closes after the 3rd
and 4th reset.
IMPORTANT
If the switch trips 5 times in 1 hour, the compressor will be stopped, and a service technician
must be called.
After the 5th pressure trip, the buzzer can be silenced for 1 hour by pressing “RESET” on the
Display Board.
e) HIGH VOLTAGE ALERT FUNCTION
When the unit detects the line voltage is above a preset value for 10 seconds, to protect the
compressor, the compressor will shut down. The buzzer will sound 8 beeps every 10 seconds.
“E6” will flash every 2 seconds, alternating with the cabinet temperature.
Reset Options:
This alarm automatically resets when an acceptable voltage is detected.
The buzzer can be silenced for 5 minutes while in alarm by pressing “RESET” on the Display
Board.
f) LOW VOLTAGE ALERT FUNCTION
When the unit detects the line voltage is below a preset value for 10 seconds, to protect the
compressor, the compressor will shut down. The buzzer will sound 9 beeps every 10 seconds.
“E7” will flash every 2 seconds, alternating with cabinet temperature.
Reset Options:
This alarm automatically resets when an acceptable voltage is detected.
The buzzer can be silenced for 5 minutes while in alarm by pressing “RESET” on the Display
Board.
g) CLEAN FILTER ALERT FUNCTION
The unit is equipped with a filter for protecting the condenser from dirt, oils, grease, etc. The
unit is also equipped with a sensor to determine if this filter needs cleaning. If the unit detects
that the condenser filter needs cleaning, it will flash “CF” every 2 seconds, alternating with the
cabinet temperature. The “CLEAN FILTER” LED will light up and the alarm buzzer will sound
1 beep every 10 seconds.
After cleaning the filter, allow time for the sensor to react, then press “RESET” on the Display
Board to reset the alarm.
During the alarm, pressing “RESET” on the Display Board will silence the alarm buzzer for
2 hours.
16
IMPORTANT
If this alarm occurs frequently even though the filter has been cleaned and reinstalled, it is
recommended that a service technician be called.
h) SENSOR ERROR
This unit uses two sensors to monitor internal temperatures:
Sensor #1: Cabinet Temperature Sensor. If this sensor fails, a continuous buzzer sounds
and “E8” will flash every 2 seconds, alternating with the sensor’s interpretation of cabinet
temperature.
Sensor #2: Defrost Temperature Sensor. If this sensor fails, a continuous buzzer sounds
and “E9” will flash every 2 seconds, alternating with the cabinet temperature.
These alarms automatically reset when a functioning sensor is installed.
During the alarm, pressing “RESET” on the display board will silence the buzzer for 5 minutes.
i) DOOR AJAR (EXCLUDING GLASS DOOR MODELS)
Immediately upon door opening, unit displays “door” alternating with cabinet temperature every 2
seconds. After 3 minutes with door open, displays “door” alternating with cabinet temperature
every 2 seconds, and 2 beeps every 10 seconds. During the alarm, pressing “RESET” on the
display board will silence the buzzer for 3 minutes. To reset the alarm, close the door.
j) COMMUNICATIONS ERROR (DUAL TEMPERATURE UNITS ONLY)
Dual temperature unit fails to communicate with other board. Refrigerator board and freezer
board are not communicating properly to delay the compressor interval at start-up of one unit
to another.
Display: “E10” is displayed and alternates every two seconds with cabinet temperature.
Buzzer: Buzzer sounds 10 beeps every 10 seconds.
Reset: Resets automatically if communication is restored.
Silence: Press “RESET” on display to silence buzzer for 18 hours.
4) DEFROST
a) FOR FREEZERS
This unit is preset at the factory to defrost 4 times per day for general conditions. However, if it
is determined that this interval does not suit the actual conditions the unit is exposed to, the
interval can be altered. To make a change of this sort, enter the GUARDED ACCESS MENU
[See “2)”], press “ENTER” one time. Now “dF #” is displayed (where “#” is the number of
defrosts the unit will activate in a 24 hour period) . Use the up/down arrows to change the
number of defrosts to the desired value. The minimum number of defrosts is 1 in a 24 hour
period, the maximum number of defrosts is 8 in a 24 hour period. Please note that the defrost
17
is a heated defrost, and therefore will have a tendency to raise the cabinet temperature.
Cabinet temperature is not displayed during defrost; “dEF” is displayed in its place.
Note: The change in the defrost setting will take effect after the next defrost based
on the previous setting. If it is desired that this change in interval timing take
effect immediately, turn the unit off and back on. The next defrost will take
effect "x" hours after power is resupplied. For example, if set df 4, x=6, the
next defrost will take place 6 hours from the time that power is applied.
b) FOR REFRIGERATORS
This unit uses an off-cycle defrost. A sensor in the evaporator coil determines the need for a
defrost. When the sensor reaches the initiation setpoint, the unit enters defrost. When the unit
reaches the termination setpoint, the unit ends defrost. The off-cycle defrost requires no
programming; it automatically initiates and terminates.
Note: In the program menu (#1=T set, #2=dF set, #3=° F or °C set), dF=x has
no effect. This is displayed because the same board is used for freezer units,
which require a time-initiated defrost.
5) START-UP DELAY
The start circuit of the compressor is timed such that at power-up and during any compressor
off-time, there will be at least a 2 1/2 minute delay before the compressor will start.
Note: On Dual Temp units, there will be approximately 10 seconds delay between one
compressor start (i.e. Freezer) and the next compressor start (i.e. Refrigerator).
6) PERIMETER FRAME HEATER
This unit is equipped with a perimeter frame heater. This prevents the formation of condensate
on the front frame of the unit under high humidity conditions. If operating the unit under
conditions where condensate will not form, these heaters may be turned off using the switch
on the Control Box.
18
The Display Board for SafeTemp models is located on the face of the Refrigeration Circuit, behind
the Front Panel. Upon lifting and positioning the Front Panel in the locked position, the Display
Board can be accessed. From the Display Board, various controls and functions can be adjusted.
1) TEMPERATURE DISPLAY
The cabinet temperature is displayed in °F only.
The cabinet temperature is updated every 2 seconds.
• When the Fan, Compressor and Defrost are initiated, the corresponding indicator lights will
switch on.
2) SETTING MENU
1. Press Set
2. Display reads: SP1
3. Press Set
4. Display reads: Current Setpoint
5. Use Up/Down Arrow to change setpoint
6. Press Set to store. If no button is pressed in 15 seconds, display will go to normal, and the
setpoint will remain unchanged.
• Setpoint is the temperature that the compressor will come on.
• For Refrigerators, -5 °F is the temperature differential for the compressor to turn off.
For Freezers, the temperature differential is -6 °F.
• For Refrigerators, the Setpoint is adjustable from 37 °F to 55 °F.
For Freezers, the range is adjustable from -10 °F to 28 °F.
3) ALARM / ALERT SIGNALS
• This unit has no alarm codes.
12. ELECTRONIC CONTROL OPERATION (SafeTemp Models)
19
4) DEFROST
a) FOR FREEZERS
This unit is preset at the factory to defrost 4 times per day for general conditions. Please note
that the defrost is a heated defrost, and therefore will have a tendency to raise the cabinet
temperature. Cabinet temperature is not displayed during defrost; “dEF” is displayed in its
place.
b) FOR REFRIGERATORS
This unit uses an off-cycle defrost. A sensor in the evaporator coil determines the need for a
defrost. When the sensor reaches the initiation setpoint, the unit enters defrost. When the unit
reaches the termination setpoint, the unit ends defrost. The off-cycle defrost requires no
programming; it automatically initiates and terminates.
5) DEFAULT FACTORY SETTINGS
The SafeTemp Freezer has a default setpoint of 0° F. The Automatic Defrost is Time
initiated every 6 hours and Temperature terminated.
The SafeTemp Refrigerator has a default setpoint of 39° F and an Automatic (Temperature
initiated/terminated) Defrost.
6) START-UP DELAY
For both Refrigerators and Freezers, the start circuit of the compressor is timed such that at
power-up and during any compressor off-time, there will be at least a 2 minute delay before the
compressor will start. In addition, for Freezers, Defrost will be initiated at power-up.
7) COMPRESSOR SHORT CYCLE TIMER
There is a 2 minute minimum off-time and on-time for the compressor.
• Any time the compressor is started, it will keep running for a minimum of 2 minutes.
• Any time the compressor is turned off, it will stay off for a minimum of 2 minutes.
Note: Time may vary with Pressure Switch activation.
20
13. DOOR REVERSING (EXCLUDING GLASS DOOR MODELS)
This unit is provided with a cabinet design which, after being delivered to the
installation location, permits changing the door swing from left to right or right to left.
To change door swing, special accessories are required. If installed improperly, the
doors will not close and seal correctly. Contact your local HOSHIZAKI distributor if door
reversing is desired.
8) SAFETY DEVICES
a) Pressure Switch
• When pressure on the high-side of the unit is detected to be above a preset limit
(determined by Hoshizaki Specifications), a Pressure Switch will activate causing
power to be interrupted to the compressor relay. This power interruption will shut
down the compressor.
• Pressure Switch will reset automatically.
When the Pressure Switch resets, power will be resupplied to the compressor.
Note: Time may vary with Pressure Switch activation.
b) Compressor Protector
• When a combined temperature/amperage value is above the limit specified by the
compressor manufacturer, a Protector will operate independently, turning off the
compressor. The compressor will restart when this protector has reset.
• Compressor Protector resets automatically.
• If the Condenser Fan is operating and the compressor is off, it is most likely that the
protector has operated.
c) Defrost Protection
For Freezers, primary Defrost Termination is controlled by the Defrost Thermistor. However, two
additional safeties are also present.
1. Time Termination - 1 hour maximum
2. Temperature Termination - Measured by a separate device that is in-line with the heaters
and independent of the Control Board.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22

Hoshizaki American, Inc. RH1-SSB-HD-J-1 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI