Proton EX70 Operating instructions

Type
Operating instructions

This manual is also suitable for

www.protongroup.org
Взрывозащищенный
АС-двигатель
PROTON EX
OPERATIONS MANUAL
FOR AIR HEATER PROTON EX
Safety precautions
Technical parameters
Installation
Construction and dimensions
05010416
Air Heater with the
explosion proof AC-motor
PROTON EX
RU
EN
Operations manual for air heater with the explosion proof motor PROTON EX:
1. Introduction ............................................................................................................................................................
.
2. Safety precautions ..............................................................................................................................................
3. General information ............................................................................................................................................
9. Control elements ................................................................................................................................................
3
4
5
4. Dimensions .............................................................................................................................................................
6
5. Construction ..........................................................................................................................................................
7
6. Technical characteristics ..................................................................................................................................
8
11
9
12
7. Installation .............................................................................................................................................................
8. Connection of heat medium ...........................................................................................................................
10. Wiring control elements ...................................................................................................................................
13
11. Reference information .....................................................................................................................................
14
2
CONTENTS
1. INTRODUCTION
The company PROTON GROUP LLC thanks you for choosing
air heaters PROTON.
3
Обращение
This manual is an integral part of the product and must
always accompany it, and should be transferred to the user.
The user should strictly follow safety instructions while
installing, using and servicing the unit.
The manufacturer disclaims any responsibility for damages
caused by wrong installation and misuse of the unit.
The manufacturer disclaims any responsibility for damages
done by people who didn’t study the manual.
The manufacturer preserves the right to introduce any
amendments to the manual without prior notification.
The manufacturer preserves the right to alter the
construction which doesn’t impact its functioning and basic
technical parameters.
The air heater is intended only and exclusively to be installed
and used for purposes which it has been designed. Any
misuse or noncompliance with the manufacturer’s
instructions may lead to property damages, personnel injuries
or death. The user has to take measures to eliminate
possibilities of misuse of the unit.
The access to the unit must be restricted for unauthorized
and unqualified personnel. The appropriate training of the
maintenance sta should be provided.
To provide proper wiring and application of the unit, please,
study this manual thoroughly before installation.
We recommend keeping the manual safe in order to address
it during operation.
3
2. SAFETY PRECAUTIONS
55
Обращение
Current network which feeds the unit’s motor and controls
must be additionally protected by a fuse to prevent
consequences of shunt fault.
Check compliance of parameters of the electrical supply
network to the ones indicated on the unit’s rating plate
before connecting to the power supply.
Check grounding. Prohibit the use of the unit without
grounding as it may cause property damages, personnel
injuries and death.
Check correctness of connections of the system, accordance
of the heat medium parameters to the parameters indicated
on the rating plate as well as leak proof of joints before filling
in the heat medium.
Before any actions connected with the air heater, please, study
this manual to provide safety.
Installation and connection of the equipment to pipelines and
networks must be performed by qualified personnel only,
having appropriate access.
During installation, start-up, repair and maintenance of the
air heater follow the safety rules.
Use screws appropriate for the material which the base is
made of.
While the air heater is operating under low temperatures, the
user must provide protection of the water heat exchanger or
use heat medium with special additives preventing copper
corrosion.
-t
Avoid substances and impurities in the heat medium causing
copper corrosion.
Install the unit on a firm base or surface, which can stand its
weight filled with water.
4
Проверьте наличие заземления. Не допускается
использование щита управления без заземления, это
может привести к повреждению имущества, травмам и
гибели персонала.
Во время монтажа, запуска, ремонта и обслуживания щита
управления соблюдайте все правила и нормы
безопасности.
To prevent defrosting of the air heater’s heat exchanger
when circulation of the heat medium is stopped during a
heating period under outdoor temperatures lower than 0°C,
you need to drain the heat medium from the heat exchanger
and blow it o by compressed air.
NEW
Provide protection of a fan against overheat by connecting
protection devices to contacts of fan temperature sensor.
Обращение
5
It is designed to heat industrial premises and warehouses under conditions of extra explosion safety.
This equipment is to be mounted in buildings with increased probability of explosion as a result of
interaction with dangerous materials as well as because of some technological processes.
PROTON EX
Principle of operation
Model range
PROTON EX 30 heating power 10-30 kW
PROTON EX 50 heating power 25-50 kW
PROTON EX 70 heating power 40-70 kW
Applications
Chemicals production premises
Paint and varnish industry
Furniture production premises
Oil- and gas processing factories
Workshops with installed vessels and
containers of high pressure
Premises of production of highly explosive
substances
The air heater PROTON is an element of a
heating system. It is designed for heating air and
its even distribution in buildings. Its work is
based on axial fan functioning, which charges
the air and pass it through a copper-aluminum
heat exchanger in which the heat medium
(hot water) flows at certain temperature.
Heated air is supplied into a room and is directed
to the working area by directing louvers.
Explosion proof
design
3. GENERAL INFORMATION
Outlet pipe
Inlet pipe
Dimensions of the air heater PROTON EX
Fastening dimensions of the mounting console CM LX
6
4. DIMENSIONS
620
380
680
680
6,3
8,3
580
200
147
195
515
195
195
195
5. CONSTRUCTION
Major components of the air heater PROTON EX
Casing
Fan
Heat exchanger
Directing louvers
A heat exchanger consists of copper tubes and aluminum lamellas
pressed on them. It is equipped with copper pipes with threading
connection (external thread 3/4”). Copper-aluminum heat exchanger
is distinguished by high eciency, is not exposed to corrosion if you
don’t use substances and impurities in the heat medium causing
copper corrosion. Maximal parameters of heat medium supply are
130 °C/1,6 MPa.
Protection-proof axial fan of the air heater PROTON EX provides
even air distribution on heat exchanger’s surface. The construction
and material of the fan prevents sparks and local temperature
increase in motor windings. Overheat protection is provided by a
thermistor sensor, not a temperature sensor as for standard motors.
The motor meets European requirements on explosion safety.
Rated power supply of PROTON EX fans is 3~400 V/50 Hz. Motor
protection rating is IP44 (EN60529), isolation class THCL155,
protection class II2Gc ExeIIB T3. Operating temperature range is
-20 °C to +40 °C.
Взрывозащищенный вентилятор PROTON EX обеспечивает
равномерное распределение потока воздуха по всей поверхности
теплообменника. Конструкция и материал вентилятора не
допускают искрообразования и локального повышения
температуры на обмотках двигателя. Защита от перегрева
осуществляется за счет специального термисторного датчика, а
не термоконтакта, как в стандартных двигателях. Вентилятор
соответствует европейским нормам по взрывобезопасности.
Номинальное питание вентиляторов в серии EX осуществляется от
источника 3~400 В/50 Гц. Степень защиты двигателя IP44, класс
изоляции – THCL155, класс защиты II2Gc ExeIIB T3. Диапазон
температур во время работы составляет от -20 до +40 °C.
Metal casing is made of elements dyed by protection cover that
provides long-time protection against corrosion and conforms with
European quality and design standards.
7
Êîìïëåêò íàïðàâëÿþùèõ æàëþçè ñ èíäèâèäóàëüíîé ðåãóëèðîâêîé
îáåñïå÷èâàåò íàïðàâëåíèå ñòðóè òåïëîãî âîçäóõà. Íàïðàâëÿþùèå
æàëþçè èìåþò àýðîäèíàìè÷åñêèé ïðîôèëü, êîòîðûé ïîçâîëÿåò
ïîëó÷èòü íèçêèé êîýôôèöèåíò ñîïðîòèâëåíèÿ âîçäóøíîãî ïîòîêà è,
êàê ñëåäñòâèå, ìàêñèìàëüíóþ äàëüíîñòü ñòðóè òåïëîãî âîçäóõà.
They are made of steel and dyed by special paint, and provide minimal
air resistance at the outlet from the air heater. Aesthetic look and
high protection from corrosion guarantee durability and safety.
Parameters according to the heat medium
8
EX 30
Parameters according to the heat medium
EX 50
Parameters according to the heat medium
EX 70
Number of heat exchanger rows
Airflow
Heating power
Air temperature increase
Max. temperature of heat medium
Max. working pressure
Max. warm air throw
Volume of water in heat exchanger
Diameter of connection pipes
Weight without heat medium
Supply voltage
Motor power
Rated current of motor
Noise level
Motor protection rating
m³/h
kW
°С
°С
MPa
m
dm³
inch
kg
V/Hz
W
dB
А
IP
R
General parameters
6. TECHNICAL CHARACTERISTICS
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
(°С)
T /
z
T
p
(m³/h)
Qp
С)
P
p1
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
(°С)
T /
z
T
p
(m³/h)
Qp
С)
P
p1
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
(m³/h) (kW) (kPa)
P
g
Q
w
С)
P
p2 p
Water 90/70 Water 80/60 Water 70/50 Water 60/40Parameters
(°С)
T /
z
T
p
(m³/h)
Qp
С)
P
p1
29.7
27.7
25.7
23.8
21.8
19.8
51.5
48.1
44.7
41.3
37.9
34.5
66.5
62.2
58.0
53.8
49.5
45.2
53.3
54.8
56.4
57.8
59.3
60.7
57.2
52.9
48.7
44.4
40.1
35.7
38.3
34.0
29.5
25.0
20.4
15.5
30.8
32.2
33.6
35.0
36.2
37.2
45.9
47.4
48.9
50.4
51.8
53.2
47.8
43.6
39.2
34.9
30.5
26.0
38.4
39.9
41.4
42.8
44.2
45.6
14.2
12.3
10.6
8.9
7.4
6.0
18.5
16.4
14.4
12.5
10.7
9.1
3.0
2.8
2.6
2.4
2.2
2.0
2.6
2.4
2.2
2.0
1.8
1.6
2.1
1.9
1.8
1.6
1.4
1.2
1.7
1.5
1.3
1.1
0.9
0.7
7.1
5.7
4.4
3.3
2.2
1.4
10.4
8.8
7.2
5.8
4.6
3.4
37.3
39.8
42.3
44.7
47.2
49.6
44.0
40.6
37.2
33.8
30.4
26.9
36.5
33.1
29.7
26.2
22.7
19.2
26.5
28.9
31.4
33.9
36.3
38.7
28.9
25.4
21.9
18.4
14.8
10.9
20.9
23.4
25.8
28.2
30.6
32.8
11.4
9.9
8.4
7.0
5.8
4.6
31.9
34.4
36.9
39.3
41.8
44.2
15.0
13.2
11.6
10.0
8.5
7.2
2.3
2.2
2.0
1.9
1.7
1.6
1.6
1.5
1.3
1.2
1.1
0.9
1.3
1.4
1.0
0.8
0.7
0.5
5.5
4.4
3.4
2.4
1.6
1.0
8.3
6.9
5.7
4.5
3.5
2.6
2.0
1.8
1.7
1.5
1.4
1.2
19.2
22.9
26.6
30.2
33.9
37.6
25.3
23.3
21.3
19.3
17.2
15.2
20.8
18.8
16.7
14.7
12.6
10.5
16.3
20.0
23.7
27.4
31.0
34.7
13.4
17.1
20.8
24.4
28.1
31.7
16.2
14.2
12.1
10.0
7.8
5.3
10.5
14.1
17.8
21.4
25.0
28.4
1.3
1.2
1.2
1.1
1.0
0.9
1.2
1.1
1.0
0.9
0.8
0.7
0.9
0.9
0.8
0.7
0.6
0.5
0.8
0.7
0.6
0.5
0.4
0.3
3.0
2.4
1.8
1.3
0.8
0.4
4.6
3.9
3.1
2.5
1.9
1.4
6.5
5.6
4.7
3.9
3.2
2.6
8.5
7.5
6.6
5.7
4.8
4.0
46004 1003700
EX 30
4600
28
1.30
29.4
29.7
19.2
51.5
37.3
66.5
53.3
53
1
130
1.6
3/4
44
400/50
EX 50
4100
23
2.25
31.3
53
2
130
1.6
3/4
44
400/50
EX 70
3700
20
3.18
32.9
53
3
130
1.6
3/4
44
400/50
290
0.51
290
0.51
290
0.51
0
5
10
15
20
25
0
5
10
15
20
25
0
5
10
15
20
25
P
g
Q
w
P
p2
p
P
p1
– air temperature at the inlet of the unit
– air temperature at the outlet of the unit
– heat power of the unit
– air consumption
P
p
Q
p
P
z
– water temperature at the inlet of the unit
– water temperature at the outlet of the unit
– water pressure drop in heat exchanger– water consumption
Обращение
7. INSTALLATION
Installation of air heater PROTON EX
9
Ways of installation with mounting console
30
30
45
45
Distance from a wall, min.
Mounting height
Distance of air stream
Distance from a ceiling, min.
Mounting height
*
directing louvers are installed under angle of 45
**
directing louvers are installed vertically
***
directing louvers are installed symmetrically under
angle of 45
0,25 m
3-8 m
up to 28 m
0,25 m
4-12 m
28 m
3-8 m
*
4-12 m
*
*
15 m
*
*
*
Wall mounting Ceiling mounting
8. INSTALLATION
Installation of air heater PROTON E 15
On a wall vertically or
horizontally, and under angle
of 30° or 45°.
Under a ceiling horizontally,
or under angle of 30° or 45°.
Обращение
Монтаж аппарата PROTON E 15
10
Recommended distances from walls and ceiling Manifold of a heat exchanger
Монтаж аппарата PROTON E 15Installation of a few units Recommendations of placing units
Noncompliance with the minimal distance (0,25 m) from a
wall or ceiling will lead to wrong operation of the air heater
which, in turn, will influence the useful life of the equipment.
When connecting the heat medium
pay your attention that manifolds
of the air heater must be fixed.
For this use two keys: one – for
fixing heat exchanger manifolds,
the second for connecting it to
the system.
Examples of placing the equipment
which provide even distribution of
heat in a building are presented on
the illustrations.
When mounting a few air heaters PROTON it is
recommended to stick to the following distances between
units: installation in one line 5-9 m, installation opposite to
each other 27-35 m, installation one by one 12-15 m.
These distances are just recommendations. The installer
should also take into account dimensions and shape of a
building, its encumbering, and recommendations of
specialists on a project.
5-9 m
12-15 m
27-35 m
7. INSTALLATION
min
0,25 m
min
0,25 m
min 0,5 m
min 0,5 m
min 0,5 m
Обращение
8. CONNECTION OF HEAT MEDIUM
9. CONNECTION OF HEAT MEDIUM
Switch panel
or
Two-way valve with an actuator
PROTON ECO
Programmable controller
0,003
Piping unit heaters PROTON ЕСO
When connecting to the heating main pipes it is necessary to provide the following conditions:
Air heating units can be installed in closed heating systems with forced circulation with maximal
temperature of the heat medium 105 °C and maximal pressure 1,6 MPa.
Installation of the air heater should be carried out referring to the minimal distances from walls,
ceiling and floor.
The air heater has to be completed with intercepting cocks on the inlet and outlet pipes.
1.
2.
It is recommended to install a coarse filter on the inlet pipe.
3.
Provide at least one cock for heat medium drainage on the bottom point on the piping scheme of the
air heater.
4.
Provide at least one air outtake on the upper point on the piping scheme of the air heater.
5.
The diameter of pipes should be selected in accordance with hydraulic calculations of the heat supply
system.
6.
Heating tubes from the heating system pipe to the air heater must be installed with the pitch of
to the pipes the heat supply system.
7.
All cable trays for wiring a fan and two-way valve should be installed higher than pipes of the heating
system.
8.
Installation must be done by technician/company who has appropriate permissions for performing
such a type of work.
9.
11
PROTON EX
0,003
Piping unit heaters PROTON ЕX
Термодатчик
внешний
Inlet pipeline
Coarse filter
Drain
Ball cock
Ball cock
Air outtake
Outlet pipeline
Piping unit heaters PROTON ЕСO
When connecting to the heating main pipes it is necessary to provide the following conditions:
Air heating units can be installed in closed heating systems with forced circulation with maximal
temperature of the heat medium 130 °C and maximal pressure 1,6 MPa.
Installation of the air heater should be carried out referring to the minimal distances from walls,
ceiling and floor.
The air heater has to be completed with intercepting cocks on the inlet and outlet pipes.
1.
2.
It is recommended to install a coarse filter on the inlet pipe.
3.
Provide at least one cock for heat medium drainage on the bottom point on the piping scheme of the
air heater.
4.
Provide at least one air outtake on the upper point on the piping scheme of the air heater.
5.
The diameter of pipes should be selected in accordance with hydraulic calculations of the heat supply
system.
6.
Heating tubes from the heating system pipe to the air heater must be installed with the pitch of
to the pipes the heat supply system.
7.
All cable trays for wiring a fan should be installed higher than pipes of the heating system.
8.
Installation must be done by technician/company who has appropriate permissions for performing
such a type of work.
9.
12
DS 2M Сontrol device
The device regulates three-phase motor of a fan by turning on/o from an
external thermostat and regulating rotations through recommutation of
windings according to the scheme “delta” and “star” with help of a manual
switch.
Possibility of smooth star-up (start - basing on star”, operation - basing ondelta”).
Possibility to regulate a group of air heaters.
Simple and reliable construction.
Dustproof and moisture resistance.
Remote control of turn on/o of motor.
STD EX Control board
Control board ECOMATIC STD EX is a board in which automatic switch, a
thermistor relay of motor protection, and a “dry contact” of firefighting device
are mounted. The board protects a motor from alarms, controls temperature of
cable windings. It is a mandatory element for air heaters PROTON EX.
Three-phase construction.
Control over motor temperature.
Protection device against shunt fault.
Connection to «dry contacts» of fireproof main.
STD EX
Щит управления
Управление аппаратом сo
взрывозащищенным двигателем
на базе щита управления:
380 В/50 Гц
STD EX
RD
Термодатчик
внешний
NTC 65 External thermal sensor
RD Programmable thermostat
ECOMATIC PRO
ECOMATIC PRO is a control element with help of which
advantages of heating and ventilation systems become
more noticeable and perceivable as its use provide
comfortable inside temperature and significant energy
savings due to fast response of the system to changes
of climatic conditions in a room. Using PROTON PRO you increase equipment lifetime protecting it from
functioning under alarm mode.
Programmable chrono-thermostat with high accuracy controls set temperature
in a room, enables to program operation of air heaters PROTON in the modes
“day-night” and “7-day calendar”.
Programmability of working cycles of the air heating system.
Available and eective solution.
Convenient interface and soft light.
Ability to connect external temperature sensor.
High accuracy.
Ability to connect a group of large buildings.
Ability to use in explosive buildings.
The sensor is designed to fix temperature in a room and transfer data to a
controller. The sensors have IP65 construction, that allows to apply them in
industrial buildings (dusty, moist, explosive environments).
9. CONTROL ELEMENTS
13
DS 2M
PETP TP V
2
V
1
U
2
U
1
W
2
W
1
Трехфазный АС-двигатель
в взрывоопасном исполнении
RD
NTC65
11 10 9 8 7 6 5
3~400 В/50 Гц
N PE
B
4
B
4
B
4
1
L
2
L
3
L
PE PE
1
L
1
U
2
U
1
V
2
V
1
W
2
W
2
L
3
L
N PE2 4 6
N PE1 3 5
N 2 3 41
STD EX
ППС
X1:4
X1:3
X1:2
X1:1
Connect a «dry contact» of fireproof main.
Make the connection «dry contac of
fireproof main.
Обнспечьте подключение ППС — «сухой
контакт» противопожарной централи.
While wiring, control the direction of fan
rotation. It is necessary to swap two
supply phases in case of its reverse
direction of rotation.
It is necessary to remove jumpers between
fan terminals while installing control device
DS 2M.
It is necessary to provide motor protection
against overheat, so wire TP contacts to a
device, which controls power.
1 х RS 330
6 х E 15
2 х E 25, E 45, E 65
1 х E 35, E 55, E 75
3.1 Подключение однофазных трехскоростных АС-двигателей к
блоку управления POWER BOX с пультом механическим RTS 10
(подключение несколькиих вентиляторов к одному каналу)
10. WIRING CONTROL ELEMENTS
Provide installation of a device protecting
the motor from shunt fault (B on the
scheme).
4
«Dry contact» of
fire-proof main
DS 2M
PETP TP V
2
V
1
U
2
U
1
W
2
W
1
RD
NTC65
11 10 9 8 7 6 5
3~400 В/50 Гц
N PE
B
4
B
4
B
4
1
L
2
L
3
L
PE PE
1
L
1
U
2
U
1
V
2
V
1
W
2
W
2
L
3
L
N PE2 4 6
N PE1 3 5
N 2 3 41
STD EX
X1:4
X1:3
X1:2
X1:1
Three-phase AC-motor
Heated building
11. REFERENCE INFORMATION
11.1 Table of pressure calculation on a wire depending on its section
14
Data is presented as a reference. For calculations for actual projects address to specialists.
Section of current
conducting core, mm
Material of the conductor – copper
Voltage, 220 V
Voltage, 380 V
Current, A
Power, kW
Current, A
Power, kW
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
4.1
5.9
8.3
10.1
15.4
18.7
25.3
29.7
38.5
47.3
57.2
66.0
10.5
16.5
19.8
26.4
49.5
59.4
75.9
95.7
118.8
145.2
171.6
11.6
15.1
19.8
25.7
36.3
46.2
56.1
72.6
92.4
112.2
132.0
4.4
6.1
7.9
13.2
18.7
29.7
50.6
36.3
22.0
44.0
11.0
19.0
27.0
38.0
46.0
70.0
85.0
115.0
135.0
175.0
215.0
260.0
300.0
20.0
28.0
36.0
50.0
60.0
85.0
100.0
135.0
165.0
200.0
230.0
19.0
23.0
30.0
39.0
55.0
70.0
85.0
110.0
140.0
170.0
200.0
16.0
25.0
30.0
40.0
50.0
75.0
90.0
115.0
145.0
180.0
220.0
260.0
33.0
Material of the conductor – aluminum:
Material of the conductor – aluminum
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
2
Material of the conductor – copper:
Section of current
conducting core, mm
Voltage, 220 V
Voltage, 380 V
Current, A
Power, kW
Current, A
Power, kW
2
11.2 Recommended diameters of pipes depending on power of equipments
heat output
12. СПРАВВОЧНАЯ ИНФОРМАЦИЯ
12.1 Таблица расчета нагрузки на провод в зависимости от его сечения
15
12. СПРАВВОЧНАЯ ИНФОРМАЦИЯ
kW Water consumption Inside diameter Type
15 kW
23 kW
39 kW
61 kW
96 kW
180 kW
20 mm
25 mm
32 mm
40 mm
50 mm
70 mm
3/4
1
1
1
4
1
2
2
0.6 m³/h
1.0 m³/h
1.6 m³/h
2.5 m³/h
4.0 m³/h
8.0 m³/h
1
2
1
2
11. REFERENCE INFORMATION
Data is presented as a reference. For calculations for actual projects address to specialists.
PROTON GROUP LLC
03680, Ukraine, Kyiv,
3, Nesterova str.
Tel.: +380 (44) 537 0930
Fax: +380 (44) 537 0903
www.protongroup.org
www.protongroup.org
In case of any failures in operation of equipment address the authorized
support centers of the Manufacturer.
For information about support centers and procedure of claim submission
contact Manufacturer’s service department:
Service department
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Proton EX70 Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI