CVD Electrical
50 amp
40 amp
#10 Solid Copper Conductor
#10 Solid Copper Conductor
40.0
30.0
50 amp
40 amp
208-230/1/60
208-230/3/60
CVD2075
40 amp
25 amp
30 amp
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
25.0
20.0
20.0
40 amp
25 amp
30 amp
208-230/1/60
208-230/3/60
230/1/50
CVD1885
20 amp
15 amp
20 amp
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#12 Solid Copper Conductor
20.0
15.0
20.0
20 amp
15 amp
20 amp
208-230/1/60
208-230/3/60
230/1/50
CVD1486
20 amp
15 amp
30 amp
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
20.0
15.0
20.0
20 amp
15 amp
30 amp
208-230/1/60
208-230/3/60
230/1/50
CVD1485
25 amp
20 amp
20 amp
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#12 Solid Copper Conductor
14.7
10.6
11.7
25 amp
20 amp
20 amp
208-230/1/60
208-230/3/60
230/1/50
CVD1285
25 amp
15 amp
20 amp
#12 Solid Copper Conductor
#14 Solid Copper Conductor
#12 Solid Copper Conductor
15.7
10.8
11.2
25 amp
15 amp
20 amp
208-230/1/60
208-230/3/60
230/1/50
CVD1185
20 amp
15 amp
20 amp
#12 Solid Copper Conductor
#14 Solid Copper Conductor
#12 Solid Copper Conductor
12.5
9.4
10.9
20 amp
15 amp
20 amp
208-230/1/60
208-230/3/60
230/1/50
CVD1085
20 amp
15 amp
20 amp
#12 Solid Copper Conductor
#14 Solid Copper Conductor
#12 Solid Copper Conductor
11.8
9.1
10.0
20 amp
15 amp
20 amp
208-230/1/60
208-230/3/60
230/1/50
CVD0885
15 amp
15 amp
15 amp
#14 Solid Copper Conductor
#14 Solid Copper Conductor
#14 Solid Copper Conductor
9.6
7.3
9.0
15 amp
15 amp
15 amp
208-230/1/60
208-230/3/60
230/1/50
CVD0675
Minimum Breaker
Size Required by
Manitowoc
**Minimum Wire Size Required by
Manitowoc
Minimum
Circuit
Amps
Maximum Fuse/
Circuit
Breaker
Voltage/Phase/Cycle
Condensing
Unit