Greenheck 483944 User manual

Type
User manual

This manual is also suitable for

STEP #6 HUB PLATE
INSTALLATION
STEP #1 STEEL TRUSS INSTALLATION
STEP #3 SAFETY CABLE
INSTALLATION
TOOL LIST
- IMPACT DRIVER
- 1/2 IN. AND 9/16 IN. SOCKETS
- 1/2 IN. WRENCH
- #2 PHILLIPS SCREWDRIVER
- #2 PHILLIPS IMPACT BIT
- MAGNETIC TORPEDO LEVEL
- TORQUE WRENCH (UP TO 50 FT-LBF)
- TORQUE WRENCH (UP TO 120 IN-LBF)
STEP #5 INSTALL WINGLET
STEP #2 MOTOR TO DOWNTUBE
BY OTHERS
HARDWARE KIT 916411
TORQUE U-BOLTS TO 54 IN-LBF
(MANUAL PAGE 12-13)
HARDWARE KIT 916400
(MANUAL PAGE 17)
HARDWARE KIT 916400
TORQUE SCREWS TO 60 IN-LBF
(MANUAL PAGE 16)
HARDWARE KIT 916399
TORQUE BOLTS TO 33 FT-LBF
(MANUAL PAGE 10)
HARDWARE KIT 916400
TORQUE BOLTS TO 20 FT-LBF
(MANUAL PAGE 16)
STEP #4 AIRFOIL
INSTALLATION
QUICK START GUIDE FOR COMMERCIAL FAN INSTALLATION
- REFER TO INSTALLATION MANUAL FOR COMPLETE INSTALLATION INFORMATION
- THIS QUICK START GUIDE DOES NOT REPLACE INSTALLATION MANUAL INSTRUCTIONS
ALTERNATE MOUNTING - MANUAL PAGES 7-9
GUY WIRE INSTALLATION (IF INCLUDED) - MANUAL PAGES 14-15
1/2 IN. BOLTS
BY OTHERS
HARDWARE KIT 916376
TORQUE BOLTS TO 35 FT-LBF
(MANUAL PAGE 6)
HARDWARE KIT 916399
TORQUE BOLTS TO 25 FT-LBF
(MANUAL PAGE 8, 10)
HARDWARE KIT 916376
TORQUE BOLTS TO 35 FT-LBF
(MANUAL PAGE 8)
5-1/2 IN.
MIN.
483944 Quick Start Guide, Rev. 1, August 2019
3
3
2
2
1
1
12
3
4
5
6
7
8
ON
12
3
ON
12
3
ON
12
3
ON
FAN 1
ALL OTHER FANS
IN SERIES
DIP SWITCH BANK 1 SETTINGS
DIP SWITCH BANK 1
DIP SWITCH BANK 2
FIRST FAN IN SERIES
ALL OTHER FANS IN SERIES
POST INSTALLATION CHECKLIST
ALL BOLTS TIGHTENED PROPERLY
ONLY USED SHIELDED NETWORKING COMPONENTS PROVIDED
MODBUS ADDRESSES SET
SAFETY CABLE INSTALLED PROPERLY
VERIFY POWER AND NETWORKING CABLES CONNECTED
- REMOVE BROWN/WHITE 24V WIRE AND CAP
- DO NOT REMOVE BROWN GROUND WIRE
- REMOVE SILVER SHIELD AND SECURE IN A WAY
THAT PREVENTS CONTACT WITH VFD BOARD
NOTE
HALL CABLE PLUG HAS BUILT-IN
ALIGNMENT TAB. DO NOT FORCE
THIS PLUG.
FIRE ALARM LANDING POINT
FIRE RELAY INSTALLATION AND WIRING
TO FAN WIRING
BLUE - COMMON
YELLOW - NORMALLY CLOSED
ORANGE - NORMALLY OPEN
(FAN DISABLED WHEN RELAY OPEN)
FIRE
RELAY
FIRE SUPPRESSION SYSTEM
LANDING POINT AT FAN
20 TO 32 VDC
RED (+)
WHITE (-)
NOTE
DO NOT CUT CABLE OR REMOVE CRIMP CAP IF NOT USING FIRE RELAY.
DIP SWITCH BANK 2 SETTINGS (MODBUS ADDRESSES)
MODBUS
ADDRESS
2
3
4
5
6
7
8
9
10
11
SWITCH
1
SWITCH
2
SWITCH
3
SWITCH
4
SWITCH
5
ON OFF OFF OFF OFF
ON
ON ON
ON
ON ON
ON ON
ON ON ON
ON
ON ON
ON ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SWITCH
6, 7, 8
DO
NOT
MODIFY
HELPFUL HINT
ALL NETWORKING MODIFICATIONS CAN BE COMPLETED PRIOR TO BLADE INSTALLATION.
FAN NETWORKING
FOR ALL WIRING AND NETWORKING - SEE MANUAL PAGES 11-12
MOTOR-TO-VFD WIRING AND DIP SWITCH BANK LOCATIONS
  • Page 1 1
  • Page 2 2

Greenheck 483944 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI