Brief Operating Instructions
FieldEdge HXF40
System Products
KA01534S/00/EN/02.23-00
71637678
2023-11-15
FieldEdge HXF40
2 Endress+Hauser
Order code:
Ext. ord. cd.:
Ser. no.:
www.endress.com/deviceviewer Endress+Hauser
Operations App
XXXXXXXXXXXX
XXXXX-XXXXXX
XXX.XXXX.XX
Serial number
1.
3.
2.
A0023555
FieldEdge HXF40 Table of contents
Endress+Hauser 3
Table of contents
1 Document information ............................................................ 3
1.1 Symbols ............................................................................. 3
2 Basic safety instructions .......................................................... 4
2.1 Requirements for the personnel ............................................................ 4
2.2 Intended use .......................................................................... 5
2.3 Workplace safety ...................................................................... 5
2.4 Operational safety ......................................................................5
2.5 Product safety ......................................................................... 5
2.6 IT security ............................................................................ 5
3 Incoming acceptance and product identification ................................... 6
3.1 Incoming acceptance .................................................................... 6
3.2 Product identification ................................................................... 6
3.3 Manufacturer address ................................................................... 7
3.4 Storage and transport ................................................................... 7
4 Mounting ......................................................................... 8
4.1 Mounting requirements ................................................................. 8
4.2 Mounting the device .................................................................... 8
4.3 Post-mounting check .................................................................. 11
5 Electrical connection ............................................................ 11
5.1 Connecting requirements ............................................................... 11
5.2 Connecting the device .................................................................. 11
5.3 RS485 serial interface .................................................................. 13
5.4 LAN interface ........................................................................ 13
5.5 Post-connection check ..................................................................15
6 Operation ....................................................................... 15
6.1 Local display ......................................................................... 15
6.2 Operating elements ....................................................................16
6.3 Card slot ............................................................................ 17
6.4 USB port ............................................................................ 18
1 Document information
1.1 Symbols
1.1.1 Safety symbols
DANGER
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
Basic safety instructions FieldEdge HXF40
4 Endress+Hauser
NOTICE
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.1.2 Electrical symbols
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding
system.
1.1.3 Symbols for certain types of information
 Tip
Indicates additional information
Reference to documentation
1.1.4 Symbols in graphics
1, 2, 3, ...
Item numbers
1.
,
2.
,
3.
Series of steps
Result of a step
Notice or individual step to be observed
-
 Hazardous area
Indicates the hazardous area
 Safe area (non-hazardous area)
Indicates the non-hazardous area
1.1.5 Communication symbols
 LED is off
 LED is on
 LED is flashing
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel must fulfill the following requirements to carry out the necessary tasks:
Are trained and qualified to perform specific functions and tasks.
FieldEdge HXF40 Basic safety instructions
Endress+Hauser 5
Are authorized by the plant owner or operator to perform specific tasks.
Are familiar with federal or national regulations.
Have read and understood the instructions in the manual and supplementary
documentation.
They follow instructions and comply with conditions.
2.2 Intended use
The device is suitable for collecting data in industrial applications like OT and IT.
The device is configurable regarding the client needs. It is the responsibility of the operator to
ensure safe operation of the device.
Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
With regard to special fluids and media used for cleaning, Endress+Hauser can assist in
choosing the detergent or cleaning materials. Endress+Hauser gives no guarantee or warranty
as to the suitability of the materials.
2.3 Workplace safety
For work on and with the device:
Wear the required protective equipment according to federal or national regulations.
2.4 Operational safety
When performing configuration, testing, and maintenance work on the device, alternative
supervisory measures must be taken to guarantee the operational safety and process safety.
2.5 Product safety
This device is designed following good engineering practice to meet state-of-the-art safety
requirements, has been tested, and left the factory in a condition in which it is safe to operate.
It meets general safety standards and legal requirements. It is compliant with the EC
directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms
this by affixing the CE mark to the device.
2.6 IT security
Our warranty is valid only if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any
inadvertent changes to the settings. IT security measures, which provide additional protection
for the device and associated data transfer, must be implemented by the operators themselves
in line with their security standards.
Incoming acceptance and product identification FieldEdge HXF40
6 Endress+Hauser
3 Incoming acceptance and product identification
3.1 Incoming acceptance
Check whether the packaging or content is damaged. Check that the goods delivered are
complete and compare the scope of delivery with the information in your order.
3.2 Product identification
For an overview of the scope of the associated Technical Documentation, refer to the
following:
Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the
nameplate
Endress+Hauser Operations app: Enter serial number from nameplate or scan matrix
code on nameplate.
FieldEdge HXF40 Incoming acceptance and product identification
Endress+Hauser 7
Baujahr
Y r of constrea .
LAN1/2:
MAC1:
MAC2:
Zertifikat-Nr.
Certification no.
Order code:
Ser no.:.
10/100/1000Mbps
1
2
3
4
5
6
78
9
10
11 12
A0046035
1 Manufacturer address
2 Device type
3 Order code and serial number
4 Power supply data
5 Output data
6 Temperature span
7 Certification number
8 Year of construction
9 MAC addresses
10 Certification signs
11 Code bar
12 QR code
3.3 Manufacturer address
Endress+Hauser SE+Co. KG
Hauptstraße 1
79689 Maulburg, Germany
Place of manufacture: See nameplate.
3.4 Storage and transport
EN 60068-2-1; Ab; 0.5 K/min
EN 60068-2-2; Bb; 0.5 K/min: –25 to +85 °C (–13 to +185 °F)
Mounting FieldEdge HXF40
8 Endress+Hauser
4 Mounting
4.1 Mounting requirements
4.1.1 Mounting location
In a cabinet or protective wall-mounted cabinet, outside the hazardous area.
LWARNING
Risk of electric shock!
The minimum protection class of the cabinet is IP67 for wet locations.
4.1.2 Orientation
Vertical or horizontal on DIN rail (HT 35 as per EN 60715).
4.2 Mounting the device
4.2.1 Mounting device on DIN rail
Install the device on DIN rail (HT 35 as per EN 60715) or in a stable cabinet.
1.
2.
A0046188
1. Hang the housing on DIN rail.
2. Push the housing to lock it on DIN rail.
FieldEdge HXF40 Mounting
Endress+Hauser 9
4.2.2 Removing device from DIN rail
2.
1.
A0046189
1. Unlock the latch.
2. Pull up the housing.
4.2.3 Mounting the device in a protective cabinet
It is possible to mount the device in a protective wall-mounted cabinet, close to the sensors.
The minimum protection class of the cabinet, according to IEC 60529 is IP67.
Mounting FieldEdge HXF40
10 Endress+Hauser
A0046048
Detailed information about the enviroment requirements, Operating Instructions
BA02147S.
FieldEdge HXF40 Electrical connection
Endress+Hauser 11
4.3 Post-mounting check
After mounting, make sure that:
The device is in the correct position and orientation
The device is protected from precipitation and direct sunlight
The device is securely seated on the DIN rail
The DIN rail-clip is clicked into place
The temperature limits are observed at the mounting location
The mechanical connections are tightened
5 Electrical connection
5.1 Connecting requirements
LWARNING
Danger! Electric voltage!
Risk of electric shock and injury from startle response.
De-energize all power sources before connecting.
In the building installation, specify an appropriate switch or power switch according to
IEC EN 61010. This switch must be easily accessible and installed close to the device and
marked as a disconnector.
Before commissioning the device, measure the supply voltage and compare it with the
voltage specifications on the nameplate. Only connect the device if the supply voltage
measured matches the specifications.
5.2 Connecting the device
5.2.1 Grounding terminal
The grounding terminal protects the HXF40 electronic circuits from short circuits and
dissipates static charges collected on the housing.
Minimum cable cross-section for the grounding terminal: 4 mm2 (11 AWG).
Electrical connection FieldEdge HXF40
12 Endress+Hauser
1
A0046042
1 Grounding terminal
5.2.2 Power supply
24V
GND S NC
A0046253
GND The functional grounding and negative potential of the power supply
24V The positive potential 24 VDC of the power supply
S Shield
NC Not connected
Supply voltage
The supply voltage is 24 VDC (±20 %). You may only use power units that ensure safe electrical
isolation according to DIN VDE 0570-2-6 and EN61558-2-6 (SELV / PELV or NEC Class 2)
and that are designed as limited-energy circuits.
FieldEdge HXF40 Electrical connection
Endress+Hauser 13
5.3 RS485 serial interface
The RS485 interface can perform as an input or output. The terminals are galvanically
isolated from each other and from grounding.
0201 03 04
A0046254
01 Ground
02 Shield
03 + (A)
04 - (B)
Internal resistance: 96 kΩ
5.3.1 RS485 serial interface cable specification
Twisted pair, shielded cable
Minimum cable cross-section: 0.5 mm2 (20 AWG)
Maximum total cable resistance: 250 Ω
Low capacitance
5.4 LAN interface
The LAN interface is compatible with IEEE 802.3. There are 2 shielded RJ45 sockets available
for connection. The LAN interface can be used to connect the device to other devices with a
hub or switch. The office equipment standard EN 60950 must be taken into consideration for
safe distances between equipment. The assignment corresponds to an
MDI-interface (AT&T258) conforming to standards so that a shielded 1:1 cable with a
maximum length of 100 m (328 ft) can be used. The Ethernet interface can operate with a
bandwidth of 1 Gbit/s, 100 Mbit/s and 10 Mbit/s. Direct connection to a PC is possible with a
crossover cable. Half-duplex and full-duplex data transmission are supported.
Electrical connection FieldEdge HXF40
14 Endress+Hauser
1
2
3
4
5
6
7
8
9 10
A0046134
1 Tx+
2 Tx-
3 Rx+
4 Not connected
5 Not connected
6 Rx-
7 Not connected
8 Not connected
10 Green LED: link indicator
11 Yellow LED: active transfer indicator
FieldEdge HXF40 Operation
Endress+Hauser 15
5.5 Post-connection check
After connection, make sure that:
The device is not damaged
The cables are not damaged
The mounted cables have adequate strain relief
The plug-in terminals are securely engaged
The supply voltage matches the specifications on the nameplate
The terminal assignment is correct
The protective ground connection is correct
6 Operation
6.1 Local display
5
7
6
8
1 2
3 4
A0046044
1 Red LED: indicates errors
2 Green LED: indicates power status
3 Red LED: recommended to use to indicate that the W&M switch is in the lock position
4 Green LED: recommended to use to indicate that the W&M switch is in the unlock position
5 Yellow LED: indicates the field communication status
6 Green LED: indicates the power status of the RS485
7 Yellow LED: indicates incoming packages
8 Yellow LED: indicates outgoing packages
Operation FieldEdge HXF40
16 Endress+Hauser
The LED indicators (1), (3), (4), (5) can be controlled and used by the installed
software 1) to indicate important statuses.
6.2 Operating elements
Reset button
The button is used to perform the factory reset of the device.
1
A0046191
1 Reset button
W&M switch
The W&M switch can be used by the installed software 2) to activate functionality.
Endress+Hauser recommends using the W&M switch for locking the device to prevent
changes on the software configuration.
1) The software is not a part of the delivery
2) The software is not a part of the delivery
FieldEdge HXF40 Operation
Endress+Hauser 17
1
A0046237
1 W&M switch
6.3 Card slot
The microSD card is not a part of the delivery of HXF40.
Endress+Hauser recommends using microSD cards with the following parameters:
Storage capacity: 8 to 64 GB
Quality: High endurance
Temperature range: –40 to +85 °C (–40 to +185 °F)
Operation FieldEdge HXF40
18 Endress+Hauser
1
A0046045
1 microSD card
6.4 USB port
The USB (Type A) data:
USB 2.0 Host
up to 480 Mbit/s
5 VDC up to 1.5 A
FieldEdge HXF40 Operation
Endress+Hauser 19
1
A0046046
1 USB slot
www.addresses.endress.com
*71637678*
71637678
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Endres+Hauser KA FieldEdge HXF40 Short Instruction

Type
Short Instruction

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI