Anybus X-gateway Modbus-TCP
INSTALLATION SHEET
Further informa on and documents about this product can be found at
the product pages on www.anybus.com.
UL Certifi cation
I
Supply voltage: The X-gateway requires a regulated 24 V (20.4 V to 28.8
V) DC power source.
Field wiring terminal markings (wire type (Cu only, 14-30AWG)
“Use 105oC copper (CU) wire only”
Terminal ghtening torque (5-7 lb-in)).
Use in Overvoltage Category I Pollu on Degree 2 Environment.
Install in an enclosure considered representa ve of the intended use.
To comply with ATEX direc ves, the equipment must be installed within
an IP54 enclosure and must be installed with a transient suppressor on
the supply that does not exceed 140% (33.6 V DC) of the nominal rated
supply voltage.
Opera ng temperature/Surrounding temperature:
-25 to +60 degrees C @ 300 mA @ 24 V DC.
In order to sustain high opera ng temperatures of up to 70 degrees C
@ 225 mA, the module must be mounted ver cally (power connector
facing upwards) to ensure op mal ver cal airfl ow. Addi onally, if the
module is mounted side-by-side with other modules, this will aff ect the
module’s ability to sustain high opera ng temperatures.
Maximum surface temperature: 135 degrees C.
Pressure: 850 - 1050 millibar.
This product is designed to safely operate in class I, division 2 Hazard-
ous loca on according to ANSI/ISA 12.12.01-2011 and category 3, zone
2 according to EN 60079-0 and EN 60079-15.
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D HAZ-
ARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.
Additional Installation and Operating
Instructions
This product is in accordance with the EMC direc ve 2004/108/EC through
conformance with the following standards:
• EN 61000-6-4 (2007)
Emission standard for industrial environment
EN 55016-2-3, Class A (2006)
• EN 61000-6-2 (2005)
Immunity for industrial environment
EN 61000-4-2 (2009)
EN 61000-4-3 (2006)
EN 61000-4-4 (2004)
EN 61000-4-5 (2005)
EN 61000-4-6 (2007)
EMC Compliance (CE)
Warnings
• WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF ANY COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2.
• WARNING - EXPLOSION HAZARD - WHEN IN HAZ-
ARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES.
• WARNING - EXPLOSION HAZARD - DO NOT DIS-
CONNECT EQUIPMENT WHILE THE CURCUIT IS
LIVE OR UNLESS THE AREA IS KNOWN TO BE
FREE OF IGNITABLE CONCENTRATIONS.
• WARNING - EXPLOSION HAZARD- THE USB CON-
NECTOR IS NOT FOR USE IN HAZARDOUS LOCA-
TIONS AND FOR TEMPORARY CONNECTION ONLY.
DO NOT USE, CONNECT OR DISCONNECT UNLESS
THE AREA IS KNOWN TO BE NONHAZARDOUS.
CONNECTION OR DISCONNECTION IN AN EXPLO-
SIVE ATMOSPHERE COULD RESULT IN AN EXPLO-
SION.
• WARNING - EXPLOSION HAZARD - DO NOT CON-
NECT OR DISCONNECT THE SD CARD UNLESS
THE AREA IS KNOWN TO BE NONHAZARDOUS.
CONNECTION OR DISCONNECTION IN AN EXPLO-
SIVE ATMOSPHERE COULD RESULT IN AN EXPLO-
SION.
• WARNING - INSTALL IN AN ENCLOSURE CON-
SIDERED REPRESENTATIVE OF THE INTENDED
USE. TO COMPLY WITH ATEX DIRECTIVES, THE
EQUIPMENT MUST BE INSTALLED WITHIN AN IP54
ENCLOSURE AND MUST BE INSTALLED WITH A
TRANSIENT SUPPRESSOR ON THE SUPPLY THAT
DOES NOT EXCEED 140% (33.6 V DC) OF THE
NOMINAL RATED SUPPLY VOLTAGE.
Atex Certifi cation
EX nA IIC T4 Gc
II 3 G
Demko 12 ATEX 1062524X
Y
DIN-rail Mounting
Make sure the DIN-rail fastening
mechanism on the back of the module
is in a fi xed and closed posi on, i. e.
pushed all the way up.
To mount the module, fi rst hook it on
to the DIN-rail (1), then push it against
the DIN-rail to make it snap on (2).
To unmount the module, a screwdriver
is needed. Use the screwdriver to push
the DIN-rail fastening mechanism on
the back of the module down un l it
locks in a fi xed and open posi on (1).
Then unhook the module from the
DIN-rail (2).
Note: Do not leave the module with the DIN-rail fastening mechanism in a fi xed
and open posi on. This may eventually wear the fastening mechanism out so it
cannot be used effi ciently. Be sure to push the DIN-rail fastening mechanism back
into the fi xed and closed posi on a er unmoun ng the module, according to the
picture below.
HMS Industrial Networks AB
^ƚĂƟŽŶƐŐĂƚĂŶϯϳ
ϯϬϮϰϱ,ĂůŵƐƚĂĚ͕^ǁĞĚĞŶ
Label Markings
Product name and
descrip on
Product number
Product
informa on bar
code
Surrounding air
temperature and
electrical ra ngs
Cer fi ca on markings
Warnings
HMS Industrial Networks AB
Sta onsgatan 37
302 45 Halmstad
Sweden