NORD Drivesystems SK 300P - NORDAC ON/ON+ - frequency inverter User manual

Type
User manual
BU 0800 – en
NORDAC ON (SK 300P series)
Manual with installation instructions
NORDAC ON (SK 300P series)Manual with installation instructions
2 BU 0800 en-3623
Read document and keep for future reference
Read this document carefully prior to performing any work on or putting the device into operation. It is
essential to read and observe the instructions in this document. They serve as the prerequisite for
smooth and safe operation and the fulfilment of any warranty claims.
Contact Getriebebau NORD GmbH & Co. KG if your questions regarding the handling of the device are
not answered in this document or if you require further information.
The German version of this document is the original. The German document is always decisive. If this
document is available in other languages, this will be a translation of the original document.
Keep this document in the vicinity of the device so that it is available if required.
Please also note the following documents:
Catalogue “NORDAC electronic drive technology” (E3000),
Documentation for optional accessories
Documentation for equipment which is attached or provided.
Please contact Getriebebau NORD GmbH & Co. KG if you require further information.
Documentation
Title:
BU 0800
Order no.:
6078002
Series:
SK 3xxP
Device series:
SK 300P, SK 301P, SK 310P, SK 311P, SK350P
Device types:
SK 3xxP-360-340-A … SK 31xP-371-340-A
0.37 kW … 3.70 kW, 3~ 400 V
Version list
BU 0800 en-3623 3
Version list
Title,
Date
Order number Software
version of
device
Remarks
BU 0800,
November 2021
6078002/ 4521
V 1.2 R5
First issue
BU 0800,
February 2022
6078002/ 0822
V 1.2 R5
“Maintenance information” chapter revised
BU 0800,
November 2022
6078002/ 4622
V 1.2 R6
General corrections
Supplementation of size 3
Revision of the scaling tables
Supplementation of disposal notes
BU 0800,
May 2023
6078002/ 2223
V 1.2 R9
General corrections
Supplement of type NORDAC ON PURE
Supplement of SK 30x-191-340
Supplement of SK 31x-371-340
Revision of the scaling tables
Revision of standards and approvals
Revision of UL and CSA conditions
BU 0800,
September
2023
6078002/ 3623
V 1.2 R9
Adjustment of information on maximum
operating / ambient temperature
Revision of UL and CSA conditions
Copyright notice
As an integral component of the device described here, this document must be provided to all
users in a suitable form.
Any editing or amendment or other utilisation of the document is prohibited.
Publisher
Getriebebau NORD GmbH & Co. KG
Getriebebau-Nord-Straße 1 22941 Bargteheide, Germany http://www.nord.com
Fon +49 (0) 45 32 / 289-0 Fax +49 (0) 45 32 / 289-2253
Member of the NORD DRIVESYSTEMS Group
NORDAC ON (SK 300P series)Manual with installation instructions
4 BU 0800 en-3623
Table of Contents
BU 0800 en-3623 5
Table of Contents
1 General ......................................................................................................................................................... 9
1.1 Overview .......................................................................................................................................... 10
1.2 Delivery ............................................................................................................................................ 12
1.3 Scope of delivery.............................................................................................................................. 12
1.4 Presentation conventions ................................................................................................................. 13
1.4.1 Warning information ........................................................................................................... 13
1.4.2 Other information ................................................................................................................ 13
1.4.3 Text markings ..................................................................................................................... 13
1.5 Safety, installation and application information ................................................................................ 14
1.6 Warning and hazard information ...................................................................................................... 18
1.6.1 Warning and hazard information on the product ................................................................. 18
1.6.2 Warning information on the upper shell .............................................................................. 18
1.7 Standards and approvals ................................................................................................................. 19
1.7.1 UL and CSA approval ......................................................................................................... 19
1.8 Type code / nomenclature ................................................................................................................ 21
1.8.1 Name plate ......................................................................................................................... 21
2 Assembly and installation ........................................................................................................................ 22
2.1 Installation ........................................................................................................................................ 22
2.2 Dimensions NORDAC ON, motor-mounted ..................................................................................... 23
2.3 Dimensions NORDAC ON+, motor-mounted ................................................................................... 24
2.4 Dimensions NORDAC ON PURE, motor-mounted .......................................................................... 25
2.5 Dimensions NORDAC ON and NORDAC ON+, wall-mounted ........................................................ 26
2.6 Dimensions NORDAC ON PURE, wall-mounted ............................................................................. 27
2.7 Connections ..................................................................................................................................... 28
2.7.1 NORDAC ON, motor-mounted, size 1 ................................................................................ 28
2.7.2 NORDAC ON, motor-mounted, sizes 2 and 3 .................................................................... 29
2.7.3 NORDAC ON+, motor-mounted, sizes 2 and 3 .................................................................. 30
2.7.4 NORDAC ON PURE, motor-mounted, sizes 2 and 3 ......................................................... 31
2.7.5 NORDAC ON, wall-mounted, size 1 ................................................................................... 32
2.7.6 NORDAC ON and NORDAC ON+, wall-mounted, sizes 2 and 3 ....................................... 33
2.7.7 NORDAC ON PURE, wall-mounted, sizes 2 and 3 ............................................................ 34
2.7.8 Hybrid cable........................................................................................................................ 34
2.8 Electrical Connection ....................................................................................................................... 35
2.8.1 NORDAC ON and NORDAC ON+ mains connection ......................................................... 35
2.8.2 NORDAC ON PURE mains connection .............................................................................. 36
2.8.3 Daisy chain connection ....................................................................................................... 37
2.8.4 Motor connection ................................................................................................................ 38
2.8.5 Wiring guidelines ................................................................................................................ 39
2.8.6 Electrical connection of power unit ..................................................................................... 39
2.8.6.1 Mains connection 40
2.8.6.2 Motor cable 40
2.8.6.3 Braking resistor (optionally with size 2 and above) 41
2.8.6.4 Electromechanical brake (optionally with size 2 and above) 41
2.8.7 Electrical connection Ethernet communication and digital input/outputs ............................ 42
2.8.7.1 Control connection details 44
2.9 Diagnostic connection ...................................................................................................................... 45
2.10 Encoder ............................................................................................................................................ 46
3 Display ....................................................................................................................................................... 49
3.1 LEDs ................................................................................................................................................ 49
3.1.1 Display of M1 and M2 when using EtherCAT ..................................................................... 49
3.1.2 Display of M1 and M2 when using EthernetIP .................................................................... 50
3.1.3 Display of M1 and M2 when using PROFINET ................................................................... 51
3.1.4 Display M3 .......................................................................................................................... 51
3.1.5 Display of M4 and M5 ......................................................................................................... 52
3.2 Diagnostic LED ................................................................................................................................ 52
4 Commissioning ......................................................................................................................................... 53
4.1 Starting up the device ...................................................................................................................... 53
NORDAC ON (SK 300P series)Manual with installation instructions
6 BU 0800 en-3623
4.2 Firmware update .............................................................................................................................. 54
4.3 Selecting the operating mode for motor control ............................................................................... 54
4.3.1 Explanation of the operating modes (P300) ....................................................................... 54
4.3.2 Overview of controller parameter settings .......................................................................... 56
4.3.3 Motor control commissioning steps .................................................................................... 57
5 Parameter ................................................................................................................................................... 58
5.1 Parameter overview ......................................................................................................................... 60
5.1.1 Operating displays .............................................................................................................. 63
5.1.2 Basic parameters ................................................................................................................ 65
5.1.3 Motor data .......................................................................................................................... 71
5.1.4 Speed control ..................................................................................................................... 80
5.1.5 Control terminals ................................................................................................................ 88
5.1.6 Additional parameters ......................................................................................................... 99
5.1.7 Information........................................................................................................................ 113
6 Operating status messages ................................................................................................................... 122
6.1 Display of messages ...................................................................................................................... 122
6.2 Messages ....................................................................................................................................... 122
6.3 FAQ operational problems ............................................................................................................. 134
7 Technical data ......................................................................................................................................... 136
7.1 General frequency inverter data ..................................................................................................... 136
7.2 Maximum operating / ambient temperature .................................................................................... 137
7.2.1 Wall-mounted frequency inverters .................................................................................... 138
7.2.2 Motor-mounted frequency inverters .................................................................................. 139
7.2.3 Reducing the maximum ambient temperature .................................................................. 140
7.2.3.1 When using daisy chain 140
7.2.3.2 With reduced 24 V DC supply voltage 140
7.3 Technical data for determining the energy efficiency level ............................................................. 141
7.3.1 Electrical data 3~400 V ..................................................................................................... 142
7.3.1.1 NORDAC ON, size 1 142
7.3.1.2 NORDAC ON, NORDAC ON+, NORDAC ON PURE, size 2 143
7.3.1.3 NORDAC ON, NORDAC ON+, NORDAC ON PURE, size 3 143
7.4 Electrical data for 24 V DC supply ................................................................................................. 143
7.5 Electrical data for daisy chain operation ......................................................................................... 144
7.5.1 Electrical data for braking resistor (optional) .................................................................... 144
8 Additional information ............................................................................................................................ 145
8.1 Electromagnetic compatibility (EMC) ............................................................................................. 145
8.1.1 General Provisions ........................................................................................................... 145
8.1.2 EMC evaluation ................................................................................................................ 146
8.1.3 EMC of device .................................................................................................................. 147
8.1.4 Declarations of Conformity ............................................................................................... 149
8.2 Reduced output power ................................................................................................................... 151
8.2.1 Derating depending on the pulse frequency ..................................................................... 151
8.2.2 Reduced overcurrent due to the time ............................................................................... 152
8.2.3 Reduced overcurrent due to output frequency.................................................................. 153
8.2.4 Reduced output current due to low voltage ...................................................................... 154
8.2.5 Reduced output current due to the heat sink temperature ................................................ 154
8.3 Operation on the RCD .................................................................................................................... 154
8.4 Motor data characteristic curves (asynchronous motors) ............................................................ 154
8.5 Motor data characteristic curves (synchronous motors) .............................................................. 155
8.6 Scaling of setpoint/actual values .................................................................................................... 155
8.6.1 Setpoints .......................................................................................................................... 155
8.6.2 Actual values .................................................................................................................... 157
8.7 Definition of set and actual value processing (frequencies) ........................................................... 158
8.8 Connection accessories ................................................................................................................. 159
8.8.1 Motor cable ....................................................................................................................... 159
8.8.2 Hybrid motor cable ........................................................................................................... 159
8.8.3 Mains cable ...................................................................................................................... 159
8.8.4 Hybrid mains cable ........................................................................................................... 160
8.8.5 Daisy chain cable ............................................................................................................. 160
8.8.6 Daisy chain hybrid cable ................................................................................................... 160
8.8.7 Sealing caps ..................................................................................................................... 160
8.8.8 Encoder cables ................................................................................................................. 160
Table of Contents
BU 0800 en-3623 7
9 Maintenance and servicing information ................................................................................................ 161
9.1 Maintenance information ................................................................................................................ 161
9.2 Service notes ................................................................................................................................. 162
9.3 Disposal ......................................................................................................................................... 163
9.3.1 Disposal according to German law ................................................................................... 163
9.3.2 Disposal outside of Germany............................................................................................ 163
9.4 Abbreviations ................................................................................................................................. 164
NORDAC ON (SK 300P series)Manual with installation instructions
8 BU 0800 en-3623
1 General
BU 0800 en-3623 9
1 General
The devices have sensorless current vector control with a wide range of settings. In combination with
suitable motor models, which always provide an optimised voltage/frequency ratio, all three-phase
asynchronous motors that are suitable for inverter operation and permanently excited synchronous
motors (IE4, IE5+) can be driven. For the drive unit, this means very high starting and overload torques
with constant speed.
The power range is from 0,37 kW to 3,7 kW.
The device series can be adapted to individual requirements by means of modular assemblies.
This manual is based on the device software as stated in the version list (see P707). If the frequency
inverter uses a different software version, this may cause differences. If necessary, the current manual
can be downloaded from the Internet (http://www.nord.com/).
Additional descriptions exist for optional functions and bus systems (http://www.nord.com/).
Accessories
The accessories that are mentioned in the manual are also subject to changes. Current details of these
are included in separate data sheets, which are listed under www.nord.com under th
e heading
Documentation Manuals Electronic drive technology Techn. info / Data sheet. The data sheets
available at the date of publication of this manual are listed by name in the relevant sections (TI ...).
The device is either mounted directly on a motor or in the vicinity of the motor (on the wall or on a
machine frame).
All electrical connections (power connections and control connections) are made with plug connectors.
This simplifies the installation of the device.
Parameters can be accessed as follows:
Via Ethernet connection
The three Ethernet dialects PROFINET IO, EtherNet/IP and EtherCAT are available for this.
Via the diagnostic port D1
The diagnostic port is designed as an RJ12 port and offers the possibility of using the following via
an internal RS232/RS485 interface
an optional SimpleBox or ParameterBox, or
the NORDAC ACCESS BT (SK TIE5 BT stick), or
a PC with the installed NORDCON software.
The parameter settings modified by the operator are backed up in the integrated, non-volatile memory
of the device.
The device is configured according to the customer’s individual requirements. The device equipment is
therefore realised ex works. Later retrofitting of options or device conversions are not planned.
NORDAC ON (SK 300P series)Manual with installation instructions
10 BU 0800 en-3623
The device does not need to be opened at any time during its service life. All mounting, installation and
commissioning works are only done on the closed device.
Assembly is done via freely accessible mounting holes.
Electrical connection is exclusively established via plug connectors.
Operational settings are made via parameter adjustments.
Blind plugs may only be removed for works in connection with commissioning and must be properly
replaced afterwards.
Diagnostic LEDs for displaying switching and operating states are externally visible.
The cover cap of the diagnostic port D1 only requires removal for the connection of parameterisation
tools such as a PC, ParameterBox or NORDAC ACCESS BT. After successful parameterisation,
the cover cap must be replaced.
1.1 Overview
Model NORDAC ON
SK 30xP
NORDAC ON
SK 30xP
NORDAC ON+
SK 31xP
NORDAC ON
PURE
SK 350P
Power 0.370.45 kW 0.373.0 kW 0.373.7 kW 0.371.5 kW
Size 1 2 - 3 2 - 3 2 - 3
Sensorless current vector control
(ISD control)
RS485/RS232 diagnostic interface
via RJ12
Four separate online switchable
parameter sets
LEDs for diagnosis
LEDs for the DIs/DOs signal statuses
Integrated PLC,
BU 0550
Integrated Industrial Ethernet
interface EtherCAT®, EtherNet/IP®,
PROFINET IO®, BU 0820
Stator resistance measurement
Load monitor
Functional safety connection facility
O
O
Internal braking resistor
O
O
O
External 24 V supply of the control
board
Operation of three-phase
as
ynchronous
m
otors (ASM)
Operation of IE5+ motors
Mountable on IE3 motor
Mountable on IE5+ motor
Brake management for mechanical
holding brake
POSICON
RS 485 encoder interface for speed
control (closed-loop, servo mode)
and positioning tasks
1 General
BU 0800 en-3623 11
Model NORDAC ON
SK 30xP
NORDAC ON
SK 30xP
NORDAC ON+
SK 31xP
NORDAC ON
PURE
SK 350P
Power 0.370.45 kW 0.373.0 kW 0.373.7 kW 0.371.5 kW
Size 1 2 - 3 2 - 3 2 - 3
Integrated EMC mains filter    
Hybrid circular connectors for mains
input / control voltage / Ethernet / and
data
Hybrid circular connectors for mains
output / daisy chain / control voltage /
Ethernet / and data
Mains input (3-phase 400 V) with
integrated 24 V DC via plug  
Mains output / daisy chain (3-phase
400 V) with integrated 24 V DC via
plug
  
Thermostats (PTC)    
DIN via M12 plug connector   
DOUT via M12 plug connector   
Not available
Optional properties
Depending on the device configuration, the meanings of the individual LEDs, the functions or
assignments of individual plugs or the function of control elements (e.g. switches) may differ. The
possible combinations are shown and explained in the course of this manual. The individual equipment
of the device is shown on the name plate and can be compared with the information in the manual.
Available as standard
O Optional
NORDAC ON (SK 300P series)Manual with installation instructions
12 BU 0800 en-3623
1.2 Delivery
Examine the device for transport damage or loose components immediately on delivery / unpacking.
In case of damage, contact the carrier immediately and arrange for a careful survey.
Important! This also applies if the packaging is undamaged.
1.3 Scope of delivery
Defect in the device
Use of impermissible accessories and options (e.g. also options for other inverter series) may result in
defects of interconnected components.
Only use accessories and options which are explicitly intended for use with this device and stated
in this manual.
Standard version: Device according to customer order, protection class see 7.1 "General
frequency inverter data"
Operating instructions as PDF file on CD ROM including NORDCON, (PC
parametrisation software)
Warning signs as addition for assembly near to the device according to
UL/cUL, 1x each in the languages English and French:
Warning sign as addition for assembly near to the device according to UL,
1x in English language:
1 General
BU 0800 en-3623 13
1.4 Presentation conventions
1.4.1 Warning information
Warning information for the safety of users are marked as follows:
DANGER
This warning information warns of danger to persons that results in severe injuries or death.
WARNING
This warning information warns of danger to persons that could result in severe injuries or death.
CAUTION
This warning information warns of danger to persons that could usually result in moderate injuries.
This warning information warns of material damage.
1.4.2 Other information
This information shows tips and important information.
1.4.3 Text markings
The following markings are used to differentiate between various types of information:
Text
Type of information Example Marking
Instructions
1.
2.
Instructions whose sequence must be complied with
are numbered sequentially.
Bullet points Bullet points are marked with a dot.
Parameter
P162
Parameters are indicated by a “P” prefix, a three-
digit number and bold lettering.
Arrays
[-01]
Arrays are indicated by square brackets.
Factory settings
{ 0.0 }
Factory settings are indicated by curly brackets.
Software descriptions
Cancel
Menus, fields, windows, buttons and tabs are
indicated by quotation marks and bold lettering.
NORDAC ON (SK 300P series)Manual with installation instructions
14 BU 0800 en-3623
Numbers
Type of information Example Marking
Binary numbers
100001b
Binary numbers are indicated by the suffix “b”.
Hexadecimal numbers
0000h
Hexadecimal numbers are indicated by the suffix “h”.
1.5 Safety, installation and application information
Before working on or with the device, please read the following safety instructions extremely carefully.
Please pay attention to all other information from the device manual.
Non-compliance can result in serious or fatal injuries and damage to the device or its surroundings.
These safety instructions must be kept in a safe place!
1. General
Do not use defective devices or devices with defective or damaged housings or missing covers (e.g.
blind plugs for cable glands). Otherwise, there is a risk of serious injury or death from electric shock or
rupture of electrical components, e.g. high power capacitors.
Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious
personal injury or material damage.
Depending on its protection class, the devices may have live, bare, moving or rotating parts or hot
surfaces during operation.
The device is operated with hazardous voltage. Dangerous voltage may be present at the supply lines,
contact strips and PCBs of all connecting terminals (e.g. mains input, motor connection), even if the
device is not working or the motor is not rotating (e.g. caused by electronic disabling, jamming of the
drive or a short circuit at the output terminals).
The device is not equipped with a master mains switch and is thus always live when connected to mains
voltage. Voltages may therefore be connected to a connected motor at standstill.
A connected motor may also rotate if the drive is disconnected from the mains and possibly generate
hazardous voltage.
If persons come into contact with dangerous voltage such as this, there is a risk of an electric shock,
which can lead to serious or fatal injuries.
The device and any power plug connectors must not be disconnected while a voltage is applied to the
device. Failure to comply with this may cause arcing, which in addition to the risk of injury, also may
result in a risk of damage or destruction of the device.
The fact that the status LED or other indicators are not illuminated does not safely indicate that the
device has been disconnected from the mains and is without voltage.
The heat sink and all other metal components may heat up to temperatures above 70 °C.
Touching these parts can result in local burns to the body parts concerned (cooling times and clearance
from neighbouring components must be complied with).
All work on the device, e.g. transportation, installation, commissioning and maintenance work must be
carried out by qualified personnel (observe IEC 364 or CENELEC HD 384 or DIN VDE 0100 and
IEC 664 or DIN VDE 0110 and national accident prevention regulations). In particular, the general and
regional installation and safety regulations for work on low-voltage systems (e.g. VDE) must be complied
with, as must the regulations concerning correct use of tools and the use of personal protection
equipment.
During all work on the device, take care that no foreign bodies, loose parts, moisture or dust enter or
remain in the device (risk of short circuit, fire and corrosion).
1 General
BU 0800 en-3623 15
With certain setting conditions, the device or the motor which is connected to it may start automatically
when the mains are switched on. The machinery which it drives (press / chain hoist / roller / fan etc.)
may then make an unexpected movement. This may cause various injuries, including to third parties.
Before switching on the mains, secure the danger area by warning and removing all persons from the
danger area.
Further information can be found in this documentation.
Triggering of a circuit breaker
If the device is secured by a circuit breaker and if this was triggered, this may indicate that a residual
current was interrupted. A component (e.g. device, cable or plug connector) in this circuit may have
caused an overload (e.g. short circuit or earth fault).
A direct reset of the circuit breaker may lead to the circuit breaker not being triggered afterwards
although the fault cause is still present. As a result, any current flowing into the fault location may cause
overheating and ignite the surrounding material.
After each triggering of a circuit breaker, all live components within this circuit must thus be visually
checked for defects and flashover tracks. Also check the connections at the device’s connection
terminals.
In case of no faults found or after the replacement of the defect components, switch on the power supply
by resetting the circuit breaker. Carefully observe the components keeping a safe physical distance. As
soon as you observe a malfunction (e.g. smoke, heat or unusual odours), the occurrence of a new fault
or if the status LED on the device does not light up, switch off the circuit breaker immediately and
disconnect the defect component from the mains. Replace the defect component.
2. Qualified specialist personnel
Within the meaning of this basic safety information, qualified specialist personnel are persons who are
familiar with the installation, assembly, commissioning and operation of the product and who have the
qualifications appropriate to their work.
In addition, the device and the accessories associated with it must only be installed and commissioned
by a qualified electrician. A qualified electrician is a person who, because of his/her technical training
and experience, has sufficient knowledge with regard to
switching on, switching off, disconnection, earthing and labelling of electric circuits and devices,
correct maintenance and use of protective devices according to specified safety standards.
3. Do not make any modifications.
Unauthorised changes and the use of spare parts and additional equipment tnot purchased from or
recommended by NORD may cause fire, electric shock and injury.
Do not change the original coating / paint or apply additional coatings / paints.
Do not make any structural modifications to the product.
4. Intended use general
Frequency inverters are devices for industrial and commercial systems that are used to operate three-
phase asynchronous motors with squirrel-cage rotors and Permanent Magnet Synchronous Motors
PMSM (IE4, IE5+). These motors must be suitable for operation with frequency inverters, other loads
must not be connected to the devices.
The devices are components intended for installation in electrical systems or machines.
Technical data and information for connection conditions can be found on the rating plate and in the
documentation, and must be complied with.
The devices may only be used for safety functions which are described and explicitly approved.
CE-labelled devices meet the requirements of the Low Voltage Directive 2014/35/EU. The stated
harmonized standards for the devices are used in the declaration of conformity.
NORDAC ON (SK 300P series)Manual with installation instructions
16 BU 0800 en-3623
a. Supplement: Intended use within the European Union
When installed in machines, commissioning of the devices (i.e. commencement of proper use) is
prohibited until it has been ensured that the machine fulfils the provisions of EC Directive
2006/42/EC (Machinery Directive); EN 60204-1 must also be complied with.
Commissioning (i.e. start of intended use) is only permitted if the EMC directive (2014/30/EU) is
complied with.
b. Supplement: Intended use outside the European Union
The local conditions of the operator for the installation and commissioning of the device must be
complied with at the usage location (see also “a. Supplement: Intended use within the European
Union”).
5. Phases of life
Transport, storage
The information in the manual regarding transport, storage and correct handling must be complied with.
The permissible mechanical and climatic ambient conditions (see technical data in the manual for the
device) must be complied with.
If necessary, suitable, adequately dimensioned means of transport (e.g. lifting gear, rope guides) must
be used.
Installation and assembly
The installation and cooling of the device must be implemented according to the regulations in the
corresponding documentation. The permissible mechanical and climatic ambient conditions (see
technical data in the manual for the device) must be complied with.
The device must be protected against impermissible loads. In particular, components must not be
deformed and/or insulation distances must not be changed. Touching of electronic components and
contacts must be avoided.
The device and its optional modules contain electrostatically sensitive components, which can be easily
damaged by incorrect handling. Electrical components must not be mechanically damaged or destroyed.
Electrical connection
Ensure that the device and the motor are specified for the correct supply voltage.
Installation, maintenance and repair work must not be carried out unless the device has been
disconnected from the voltage and at least 5 minutes have elapsed since the mains was switched off!
(Due to charged capacitors, hazardous voltages may be present on the device for up to 5 minutes after
being switched off from the mains). Before starting work it is essential to check by measurement that all
contacts of the power plug connections or the connection terminals are voltage-free.
The electrical installation must be implemented according to the applicable regulations (e.g. cable cross-
section, fuses, earth lead connections). Further instructions can be found in the documentation or
manual for the device.
Information regarding EMC-compliant installations such as shielding, earthing, location of filters and
routing of cables can be found in the documentation for the devices and in the technical information
manual TI 80-0011. This information must always be observed even with devices with a CE label.
Compliance with the limit values specified in the EMC regulations is the responsibility of the
manufacturer of the system or machine.
In case of a fault, inadequate earthing may result in electric shock, possibly with fatal consequences.
The device may only be operated with effective earth connections which comply with local regulations
for large leakage currents (> 3.5 mA). Detailed information regarding connections and operating
conditions can be obtained from the technical Information manual TI 80-0019.
1 General
BU 0800 en-3623 17
Connection of the supply voltage may directly or indirectly set the device into operation. Contact with
electrically live components may result in electric shock, possibly with fatal consequences.
All poles of cable connections (e.g. power supply) must always be disconnected.
Setup, troubleshooting and commissioning
When working on live devices, the applicable national accident prevention regulations must be complied
with.
Connection of the supply voltage may directly or indirectly set the device into operation. Contact with
electrically live components may result in electric shock, possibly with fatal consequences.
The parametrisation and configuration of the devices must be selected so that no hazards can occur.
Operation
Where necessary, systems in which the devices are installed must be equipped with additional
monitoring and protective equipment according to the applicable safety requirements (e.g. legislation
concerning technical equipment, accident prevention regulations, etc.).
All covers must be kept closed during operation.
Due to its operation, the device produces noises within the audible frequency range. These noises may
cause long-term stress, discomfort and fatigue, with negative effects on concentration. The frequency
range or the noise can be shifted to a less disturbing or almost inaudible range by adjustment of the
pulse frequency. However, this may possibly result in derating (lower power) of the device.
Maintenance, repair and decommissioning
Installation, maintenance and repair work must not be carried out unless the device has been
disconnected from the voltage and at least 5 minutes have elapsed since the mains was switched off!
(Due to charged capacitors, hazardous voltages may be present on the device for up to 5 minutes after
being switched off from the mains). Before starting the work, it is essential to check by measurement
that all contacts of the power plug connectors or the connection terminals are voltage-free.
Disposal
The product and its parts and accessories must not be disposed of as domestic waste. At the end of its
life, the product must be properly disposed of according to the local regulations for industrial waste. In
particular, this product contains integrated semiconductor circuits (PCBs and various electronic
components, including high power electrolytic capacitors). In case of incorrect disposal there is a risk of
formation of toxic gases, which may cause contamination of the environment and direct or indirect
injuries (e.g. chemical burns). In the case of high power electrolytic capacitors, there is also a risk of
explosion, with the associated risk of injury.
6. Potentially explosive environment (ATEX)
The device is not approved for operation or maintenance work in potentially explosive environments
(ATEX).
NORDAC ON (SK 300P series)Manual with installation instructions
18 BU 0800 en-3623
1.6 Warning and hazard information
Under certain circumstances, hazardous situations may occur in association with the frequency inverter.
In order to give explicit warning of possibly hazardous situations, clear warning and hazard information
can be found on the device and in the relevant documentation.
1.6.1 Warning and hazard information on the product
The following warning and hazard information is used on the product.
Symbol Supplement to
symbol 1) Meaning
DANGER
Device is live
>5min after
removing mains
voltage
Danger
Electric shock
The device contains powerful capacitors. Because of this, there may be a
hazardous voltage for more than 5 minutes after disconnection from the mains.
Before starting work, check that the device is free of voltage at all power
contacts by means of suitable measuring equipment.
It is essential to read the manual in order to prevent hazards!
CAUTION
Hot surfaces
The heat sink and all other metal components as well as the surfaces of plug
connectors may heat up to temperatures in excess of 70°C.
Danger of injury due to local burns on contact.
Heat damage to adjacent objects
Allow sufficient cooling time before starting work on the device. Check the
surface temperatures with suitable measuring equipment. Maintain an
adequate distance to adjacent components or provide protection against
contact.
NOTICE
EDS
The device contains electrostatically sensitive components, which can be
easily damaged by incorrect handling.
Avoid all contact (indirect contact by tools or similar, or direct contact) with
PCBs and their components.
1) Texts are written in English.
Table 1: Warning and hazard information on the product
1.6.2 Warning information on the upper shell
Important information regarding danger of electric shock and hot surfaces can be found at the side of
the upper shell of the device.
1 General
BU 0800 en-3623 19
1.7 Standards and approvals
All devices across the entire series comply with the standards and directives listed below.
Approval Directive Applied
standards Certificates Label
CE
(European
Union)
Low Voltage 2014/35/EU
EN 61800-5-1
EN 60529
EN 61800-3
EN 63000
EN 61800-9-1
EN 61800-9-2
C310001_0921
EMC 2014/30/EU
RoHS 2011/65/EU
Delegated directive
(EU) 2015/863
Ecodesign
2009/125/EC
Regulation (EU)
Ecodesign 2019/1781
UL
(USA) UL 61800-5-1 E171342
CSA
(Canada) C22.2 No.274-13 E171342
RCM
(Australia) F2018L00028 EN 61800-3 ------
UkrSEPRO
(Ukraine)
EN 61800-5-1
EN 60529
EN 61800-3
EN 63000
EN 60947-1
EN 60947-4
EN 61558-1
EN 50581
C311900
UKCA
(United
Kingdom)
EN 61800-5-1
EN 60529
EN 61800-3
EN 63000
EN 61800-9-1
EN 61800-9-2
C352000
Table 2: Standards and approvals
1.7.1 UL and CSA approval
File No. E171342
The categorisation of protective equipment approved by the UL according to United States standards
for the devices described in this manual is listed below, basically with the original wording. The
categorisation of the individually relevant fuses or circuit breakers can be found in the “Electrical Data”
section of this manual.
All devices include motor protection.
Additional adhesive labels with supplementary warning information
Attach the signs enclosed with the device and listed according to Section 1.3 "Scope of delivery"in a
clearly visible position in the immediate vicinity of the device.
NORDAC ON (SK 300P series)Manual with installation instructions
20 BU 0800 en-3623
Conditions UL/CSA according to report
Information
Listed as ENCLOSED POWER CONVERSION EQUIPMENT
These devices incorporate an adjustable internal solid-state motor overload protection (see P533, P535)
• “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the Manufacturer Instructions, National Electrical Code and
any additional local codes”.
CSA: For Canada: “Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Canadian Electrical Code, Part I”.
“Use min. 75°C rated Copper Conductors Only”.
“For use in Pollution Degree 3 and Overvoltage Category III environments only.”
“Maximum surrounding air Temperature 40°C (S1) - 50°C (S3-70%). ( see chapter 7 )
“The device has to be mounted according to the Manufacturer Instructions.”.
“For NFPA79 applications only”
“Control circuit is Limited Voltage / Limited Current maximum 30 V/ 3 A
“External protective means (e.g. thermal sensor or switch embedded in the motor or from an external
protective relay) may be additionally used”.
“The source shall be derived from a non-corner grounded type TN AC source not exceeding 277 V phase to
earth”.
• “They are suitable for operation on TN as well as for IT networks with the configuration of the integrated
mains filter.
Frame
Size
description
all
“Suitable for use on a circuit capable of delivering not more than 10 kA rms symmetrical amperes, 480
(3-phase) volts max., when protected by high-interrupting capacity, current limiting class RK5 fuses or
faster, rated min. 480 Volts”. 1)
This is not applicable for devices with QPD-W Connector.
all
Suitable for use on a circuit capable of delivering not more than 10 kA rms symmetrical amperes, 480
Volt maximum, when protected by circuit breaker (inverse time trip type) in accordance with UL 489,
min. 480 Volts”. 1)
This is not applicable for devices with QPD-W Connector.
all
“Suitable for motor group installation on a circuit capable of delivering not more than 10 kA rms
symmetrical amperes, 480 (3-phase) V max, when protected by high-interrupting capacity, current
limiting class RK5 fuses or faster, rated max. 30 Amperes”.
If provided with QPD-W Connector the SCCR is max. 5 kA with class J fuses or faster.
all
“Suitable for motor group installation on a circuit capable of delivering not more than 10 kA rms
symmetrical amperes, 480 (3-phase) V max, when protected by circuit breaker (inverse time trip type)
in accordance with UL 489, rated max. 30 Amperes and 480 Volts min.”
This is not applicable for devices with QPD-W Connector.
1)
(
see chapter 7)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168

NORD Drivesystems SK 300P - NORDAC ON/ON+ - frequency inverter User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI