5. Product information
5.1 Product description
The PushPull 60 K is a single-room
ventilation unit with heat recovery. The
ventilation unit is installed directly in the
room that is to be ventilated (no costly
installation of a duct system necessary).
The PushPull 60 K switches from exhaust
air mode to supply air mode every 70
seconds. Supply air is heated using heat
recovered from the exhaust air flow.
During this process, up to 90 % of the
exhaust air heat is recovered.
The RLS PP-K room air control can control
up to four PushPull 60 K. The room air
control is not included in the scope of
delivery.
5.2 Models
PP 60 KA: Comfort version with ●
stainless steel external cover.
PP 60 KL: Comfort version with stainless ●
steel / aluminium soffit element.
5.3 Equipment characteristics
PP 60 K ventilation unit with five ●
ventilation levels with heat recovery.
Ceramic heat exchanger providing up to ●
90 % of heat.
Simultaneous supply and exhaust air ●
operation possible. Unit switches from
exhaust air mode to supply air mode
every 70 seconds.
Cross-ventilation operating mode ●
without heat recovery: there are always
two ventilation units running in supply air
/ exhaust air mode.
Ventilation levels can be selected with ●
RLS PP-K room air control.
Low energy consumption.
●
Internal cover made from plastic, white ●
(similar to RAL 9016).
External cover made from stainless steel ●
(PP 60 KA) or with soffit element made
from stainless steel / aluminium
(PP 60 KL)
With air filter of filter class G3 for filtering ●
the outside and exhaust air. The M6 fine
dust filter can be ordered as an option.
The ventilation unit is practically ●
maintenance-free. The filter simply has
to be cleaned every 2-3 months and the
air filter replaced based on the filter
change display.
The ventilation system requires no ●
adjustment.
Simple installation of the complete fan ●
unit by insertion into the wall sleeve.
Fan with energy-saving, quiet EC motor, ●
suitable for continuous operation.
Electrically actuated shutter prevents ●
cold air from flowing in.
Pluggable terminal block for the power ●
connection.
Condensation is drained to the outside ●
via the drip edge of the external cover or
soffit duct by tilting the wall insulation
sleeve. This prevents condensation from
running down the building wall.
The use of multiple ventilation units per ●
room is recommended for larger living
units.
5.4 Technical data