Rosemount 3051 Pressure Transmitter and 3051CF Series Flowmeter Quick start guide

Type
Quick start guide
Quick Start Guide
00825-0200-4774, Rev DA
March 2020
Rosemount
3051 Pressure Transmitter
and Rosemount 3051CF Series Flow
Meters
with FOUNDATION
Fieldbus Protocol
Contents
About this guide...........................................................................................................................3
System readiness......................................................................................................................... 5
Transmitter installation................................................................................................................ 7
Product certifications................................................................................................................. 31
Quick Start Guide March 2020
2 Emerson.com/Rosemount
1 About this guide
This guide provides basic guidelines for Rosemount 3051 Pressure
Transmitters. It does not provide instructions for configuration, diagnostics,
maintenance, service, troubleshooting, Explosion-proof, Flameproof, or
intrinsically safe (I.S.) installations. Refer to Rosemount 3051 Reference
Manual for more instructions. This guide is also available electronically at
Emerson.com/Rosemount.
1.1 Safety messages
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance
with appropriate local, national, and international standards, codes, and
practices. Review the approvals section of the Rosemount 3051
Reference Manual for any restrictions associated with a safe installation.
In an explosion-proof/flameproof installation, do not remove the
transmitter covers when power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
To avoid process leaks, only use the O-ring designed to seal with the
corresponding flange adapter.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing
enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or
conduit with a compatible thread form when closing these entries.
Entries marked M20 are M20 x 1.5 thread form. On devices with multiple
conduit entries, all entries will have the same thread form.
When installing in a hazardous location, use only appropriately listed or
Ex certified plugs, glands, or adapters in cable/conduit entries.
March 2020 Quick Start Guide
Quick Start Guide 3
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or
unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by
unauthorized personnel to protect end users’ assets. This is true for all
systems used within the facility.
Quick Start Guide March 2020
4 Emerson.com/Rosemount
2 System readiness
2.1 Confirm correct device driver
Verify the correct device driver (DD/DTM
) is loaded on your systems to
ensure proper communications.
Download the correct device driver at your host vendor download site,
Emerson.com/Rosemount or Fieldbus.org.
2.1.1 Rosemount 3051 device revisions and drivers
Table 2-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 2-1: Rosemount 3051 FOUNDATION Fieldbus Device Revisions and
Files
Device
Revision
(1)
Host Device driver (DD)
(2)
Device driver
(DTM)
Document
8 All DD4: DD Rev 1 Emerson.com Rosemount
3051 Pressure
Transmitter
with FOUNDATION
Fieldbus
Reference
Manual
All DD5: DD Rev 1
Emerson AMS Device Manager
V 10.5 or higher: DD
Rev 2
Emerson AMS Device Manager
V 8 to 10.5: DD Rev 1
Emerson Field Communicator:
DD Rev 2
7 All DD4: DD Rev 3
All DD5: NA
Emerson AMS Device Manager
V 10.5 or higher: DD
Rev 6
Emerson AMS Device Manager
V 8 to 10.5: DD Rev 4
Emerson Field Communicator:
DD Rev 6
(1) FOUNDATION Fieldbus device revision can be read using a FOUNDATION Fieldbus
capable configuration tool.
(2) Device driver file names use device and DD revision. To access functionality, the
correct device driver must be installed on your control and asset management
hosts, and on your configuration tools.
March 2020 Quick Start Guide
Quick Start Guide 5
Figure 2-1: Installation Flowchart
Start
1. Transmitter
installation
(Section 3)
2. Commissioning
tag
(Section 3.4)
Done
Locate device
7. Zero trim the
transmitter
(Section 5.4)
3. Housing
rotation
(Section 3.5.1)
5. Grounding,
wiring and
power up
(Section 4.6)
6. Configuration
(Section 2.7.1, 2.8)
4. Set switches
and software
write lock
(Section 4.4)
Quick Start Guide March 2020
6 Emerson.com/Rosemount
3 Transmitter installation
3.1 Mount the transmitter
Figure 3-1: Panel Mount Coplanar Flange
5/16 x 1½ panel bolts are customer supplied.
Figure 3-2: Pipe Mount Coplanar Flange
March 2020 Quick Start Guide
Quick Start Guide 7
Figure 3-3: Panel Mount Traditional Flange
Figure 3-4: Pipe Mount Traditional Flange
Figure 3-5: Panel Mount Rosemount 3051T
Quick Start Guide March 2020
8 Emerson.com/Rosemount
Figure 3-6: Pipe Mount Rosemount 3051T
March 2020 Quick Start Guide
Quick Start Guide 9
3.1.1 Mount the transmitter in liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 3-7: Mounting the Transmitter in Liquid Applications
In-line
3.1.2 Mount the transmitter in gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 3-8: Mounting the Transmitter in Gas Applications
In-line
Quick Start Guide March 2020
10 Emerson.com/Rosemount
3.1.3 Mount the transmitter in steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 3-9: Mounting the Transmitter in Steam Applications
In-line
3.1.4 Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow these assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 3-10 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
March 2020 Quick Start Guide
Quick Start Guide 11
Figure 3-10: Common Transmitter Assemblies
B
4 × 2.88-in. (73 mm)
A
4 × 1.75-in. (44 mm)
C
4 × 1.75-in.
(44 mm)
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in. (44 mm)
4 × 2.25-in. (57 mm)
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing . If
bolt material is not shown in Table 3-1, contact a local Emerson
representative for more information.
Procedure
1. Carbon steel bolts do not require lubrication and the stainless steel
bolts are coated with a lubricant to ease installation. However, no
additional lubricant should be applied when installing either type of
bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern.
See Table 3-1 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing
pattern. See Table 3-1 for final torque value.
5. Verify the flange bolts are protruding through the isolator plate
before applying pressure.
Quick Start Guide March 2020
12 Emerson.com/Rosemount
Table 3-1: Torque Values for the Coplanar Flange and Flange Adapter
Bolts
Bolt material Head markings Initial
torque
Final
torque
CS
B7M
300 in-lb 650 in-lb
SST
316
316
316
SW
316
STM
316
R
B8M
150 in-lb 300 in-lb
March 2020 Quick Start Guide
Quick Start Guide 13
3.1.5 O-rings with flange adapters
WARNING
Failure to install proper flange adapter O-rings may cause process leaks,
which can result in death or serious injury. The two flange adapters are
distinguished by unique O-ring grooves. Only use the O-ring that is designed
for its specific flange adapter, as shown below.
Figure 3-11: O-ring Location
A
B
C
D
Rosemount 3051S/3051/2051
A. Flange adapter
B. O-ring
C. PFTE-based profile (square)
D. Elastomer profile (round)
Whenever the flanges or adapters are removed, visually inspect the O-rings.
Replace them if there are any signs of damage, such as nicks or cuts. If you
replace the O-rings, re-torque the flange bolts and alignment screws after
installation to compensate for seating of the PTFE O-ring.
3.1.6 Environmental seal for housing
Thread sealing (PFTE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seals and meets requirements of NEMA
®
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings
are required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
Quick Start Guide March 2020
14 Emerson.com/Rosemount
3.1.7 In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is between the housing and sensor of the transmitter (see Figure
3-12).
Keep the vent path free of any obstruction, including but not limited to
paint, dust, and lubrication by mounting the transmitter so that the process
can drain away.
Figure 3-12: In-line Gage Low Side Pressure Port
A
A. Low side pressure port (atmospheric reference)
3.1.8 Installing high pressure coned and threaded connection
The transmitter comes with an autoclave connection designed for high
pressure applications. Follow the steps below to properly connect the
transmitter to your process:
Procedure
1. Apply a process-compatible lubricant to the gland nut threads.
2. Slip the gland nut onto the tube, then thread the collar onto the tube
end (the collar is reverse threaded).
3. Apply a small amount of process-compatible lubricant applied to the
tube cone to help prevent galling and facilitate sealing. Insert the
tubing into the connection and tighten finger tight.
4. Tighten the gland nut to a torque of 25 ft-lb.
Note
A weep hole has been designed into the transmitter for safety and
leak detection. If fluid begins to leak from the weep hole, isolate the
process pressure, disconnect the transmitter, and reseal until the
leak is resolved.
March 2020 Quick Start Guide
Quick Start Guide 15
3.2 Tagging
3.2.1 Commissioning (paper) tag
To identify which device is at a particular location, use the removable tag
provided with the transmitter. Ensure the physical device tag (PD tag field) is
properly entered in both places on the removable commissioning tag and
tear off the bottom portion for each transmitter.
Note
The device description loaded in the host system must be at the same
revision as this device.
Figure 3-13: Commissioning Tag
Commissioning Tag
DEVICE ID:
0011513051010001440-121698091725
DEVICE REVISION: 7.2
PHYSICAL DEVICE TAG
DEVICE ID:
0011513051010001440-121698091725
DEVICE REVISION: 7.2
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A
Commissioning Tag
DEVICE ID:
001151AC00010001440-121698091725
DEVICE REVISION: 8.1
PHYSICAL DEVICE TAG
DEVICE ID:
001151AC00010001440-121698091725
DEVICE REVISION: 8.1
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A. Device revision
Note
The device description loaded in the host system must be at the same
revision as this device. You can download the device description from the
host system website or Emerson.com/Rosemount by selecting Device
Drivers under Resources. You can also visit Fieldbus.org and select End User
Resources.
3.3
Consider housing rotation
To improve visibility of optional LCD display:
Procedure
1. Loosen the housing rotation screw.
Quick Start Guide March 2020
16 Emerson.com/Rosemount
2. First rotate the housing clockwise to the desired location. If the
desired location cannot be achieved due to thread limit, rotate the
housing counter clockwise to the desired location (up to 360° from
thread limit).
3. Re-tighten the housing rotation screw (see Figure 3-14).
Figure 3-14: Housing Rotation
A
A. Housing rotation screw (5/64-in. hex wrench required)
3.4 Set the switches
Set simulate and security switch configuration before installation as shown
in Figure 3-15.
The simulate switch enables or disables simulated alerts and simulated
AI Block status and values. The default simulate switch position is
enabled.
The security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.
Default security is off (unlocked symbol).
The security switch can be enabled or disabled in software.
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not
remove the instrument cover in explosive atmospheres when the
circuit is live.
3. Slide the security and simulate switches into the preferred position.
4. Replace the housing cover.
March 2020 Quick Start Guide
Quick Start Guide 17
Note
It is recommended the cover be tightened until there is no gap between the
cover and the housing.
Figure 3-15: Simulate and Security Switches
C
A
B
D
E
F
A. Simulate disabled position
B. Simulate switch
C. Simulate enabled position
D. Security locked position
E. Security switch
F. Security unlocked position
3.5 Connect wiring and power up
Use copper wire of sufficient size to ensure that the voltage across the
transmitter power terminals does not drop below 9 Vdc. Power supply
voltage can be variable, especially under abnormal conditions, such as when
operating on battery backup. Emerson recommends a minimum of 12 Vdc
under normal operating conditions and shielded twisted pair Type A cable.
Procedure
1. To power the transmitter, connect the power leads to the terminals
indicated on the terminal block label.
Quick Start Guide March 2020
18 Emerson.com/Rosemount
Figure 3-16: Wiring Terminals
A. Minimize distance
B. Trim shield and insulate
C. Protective grounding terminal (do not ground cable shield at the
transmitter)
D. Insulate shield
E. Connect shield back to the power supply ground
Note
The Rosemount 3051 power terminals are polarity insensitive, which
means the electrical polarity of the power leads does not matter
when connecting to the power terminals. If polarity sensitive devices
are connected to the segment, follow terminal polarity. When wiring
to the screw terminals, Emerson recommends using crimped legs.
2. Ensure full contact with terminal block screw and washer. When
using a direct wiring method, wrap wire clockwise to ensure it is in
place when tightening the terminal block screw.
Note
Emerson does not recommend using a pin or ferrule wire terminal, as
the connection may be more susceptible to loosening over time or
under vibration.
March 2020 Quick Start Guide
Quick Start Guide 19
3.5.1 Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
outside of the electronics housing and inside the terminal compartment.
These grounds are used when transient protect terminal blocks are installed
or to fulfill local regulations.
Procedure
1. Remove the field terminals housing cover.
a) Trim the cable shield as short as practical and insulate from
touching the transmitter housing.
Note
Do NOT ground the cable shield at the transmitter; if the
cable shield touches the transmitter housing, it can create
ground loops and interfere with communications.
b) Continuously connect the cable shields to the power supply
ground.
c) Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
Note
Improper grounding is the most frequent cause of poor
segment communications.
2. Connect the wiring pair and ground as indicated in Figure 3-16.
3. Replace the housing cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
3.5.2 Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic
safety and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide
complete functionality.
3.5.3 Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply
filter and decouple the segment from other segments attached to the same
power supply.
Quick Start Guide March 2020
20 Emerson.com/Rosemount
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56