Emerson 644 User manual

Category
Measuring, testing & control
Type
User manual
www.rosemount.com
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644 Temperature Transmitter
with FOUNDATION
fieldbus
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
TOC-1
SECTION 1
Introduction
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Product Recycling/Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
SECTION 2
Installation
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Typical European Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Typical North American Installation . . . . . . . . . . . . . . . . . . . . . . . . 2-5
LCD Display Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Sensor Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Ground the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
SECTION 3
Configuration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
General Block Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Device Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Node Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Link Active Scheduler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Block Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Capabilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Foundation fieldbus function blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
LCD Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Troubleshooting Guides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
LCD Transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
Table of Contents
Reference Manual
00809-0400-4728, Rev AA
June 2011
TOC-2
Rosemount 644
APPENDIX A
Specifications and
Reference Data
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Functional. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-2
Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-3
Foundation Fieldbus Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . .A-4
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-9
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-12
Tagging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-14
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-14
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-15
APPENDIX B
Product
Certifications
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1
European Union Directive Information. . . . . . . . . . . . . . . . . . . . . . . . .B-1
Hazardous Locations Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
Rosemount 644 with Foundation fieldbus. . . . . . . . . . . . . . . . . . . .B-2
North American Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
European Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-3
IECEx Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-4
Japanese Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Combination Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Russian GOST Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Kazakhstan GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Ukraine GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-7
APPENDIX C
Foundation
fieldbus Block
Information
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Sensor Transducer Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-5
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-5
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-8
AI Parameter Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-9
LCD Transducer Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-11
PID Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-12
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
www.rosemount.com
Rosemount 644
Temperature Transmitters
Rosemount 644 Hardware Revision
F
OUNDATION
Fieldbus Device Revision
Device Descriptor Revision
9
2
1
NOTICE
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-(952)-906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact a Emerson Process
Management Sales Representative.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
www.rosemount.com
Section 1 Introduction
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-2
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-4
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
Before connecting F
OUNDATION fieldbus in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or
non-intrinsic field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
1-2
OVERVIEW
Manual This manual is designed to assist in the installation, operation, and
maintenance of Rosemount 644 head mount and 644 rail mount.
Section 1: Introduction
Transmitter and Manual Overview
Considerations
Return of Material
Section 2: Installation
Mounting
Installation
Wiring
Power Supply
Commissioning
Section 3: Configuration
Calibration
Hardware Maintenance
Diagnostic Messaging
Appendix A: Specifications and Reference Data
Specifications
Dimensional Drawings
Ordering Information
Biotechnology, Pharmaceutical Industries, and Sanitary Applications
Appendix B: Product Certifications
Product Certifications
Installation Drawings
Appendix C: Foundation fieldbus Block Information
Information regarding the Function Blocks
Transmitter Features of the Rosemount 644 include:
Accepts inputs from a wide variety of sensors
Configuration using F
OUNDATION fieldbus
Electronics that are completely encapsulated in epoxy and enclosed in
a metal housing, making the transmitter extremely durable and
ensuring long-term reliability
A compact size and two housing options allowing mounting flexibility for
the control room or the field
Reference Manual
00809-0400-4728, Rev AA
June 2011
1-3
Rosemount 644
Refer to the following literature for a full range of compatible connection
heads, sensors, and thermowells provided by Emerson Process
Management.
Temperature Sensors and Assemblies Product Data Sheet, Volume 1
(document number 00813-0100-2654)
Temperature Sensors and Assemblies Product Data Sheet, Volume 2
(document number 00813-0200-2654)
CONSIDERATIONS
General Electrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to their sensed temperature. The 644 converts
the low-level sensor signal to a standard 4–20 mA dc, or digital F
OUNDATION
fieldbus signal that is relatively insensitive to lead length and electrical noise.
This signal is then transmitted to the control room via two wires.
Commissioning The transmitter can be commissioned before or after installation. It may be
useful to commission it on the bench, before installation, to ensure proper
operation and to become familiar with its functionality. Make sure the
instruments in the loop are installed in accordance with intrinsically safe,
FISCO, or non-incendive field wiring practices.
Mechanical Location
When choosing an installation location and position, take into account the
need for access to the transmitter.
Special Mounting
Special mounting hardware is available for mounting a 644 head mount
transmitter to a DIN rail or assembling a new 644 head mount to an existing
threaded sensor connection head (former option code L1).
Electrical Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. For best results, shielded cable should be
used in electrically noisy environments.
Make wiring connections through the cable entry in the side of the connection
head. Be sure to provide adequate clearance for cover removal.
Environmental The transmitter electronics module is permanently sealed within the housing,
resisting moisture and corrosive damage. Verify that the operating
atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures
between –40 and 185 °F (–40 and 85 °C). Heat from the process is
transferred from the thermowell to the transmitter housing. If the expected
process temperature is near or beyond specification limits, consider the use of
additional thermowell lagging, and extension nipple, or a remote mounting
configuration to isolate the transmitter from the process.
Figure 1-1 provides an example of the relationship between transmitter
housing temperature rise and extension length.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
1-4
Figure 1-1. 644 head mount
Transmitter Connection Head
Temperature Rise vs. Extension
Length
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C
and the process temperature to be measured is 800 °C, the maximum
permissible connection head temperature rise is the transmitter specification
limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 100 mm meets this requirement, but 125 mm
provides a margin of 8 °C, thereby reducing any temperature effects in the
transmitter.
RETURN OF MATERIALS To expedite the return process in North America, call the Emerson Process
Management National Response Center toll-free at 800-654-7768. This
center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for the following information:
Product model
Serial numbers
The last process material to which the product was exposed
The center will provide
A Return Material Authorization (RMA) number
Instructions and procedures that are necessary to return goods that
were exposed to hazardous substances
For other locations, please contact a Emerson Process Management sales
representative.
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS),
required by law to be available to people exposed to specific hazardous
substances, must be included with the returned materials.
PRODUCT
RECYCLING/DISPOSAL
Recycling of equipment and packaging should be taken into consideration
and disposed of in accordance with local and national legislation/regulations.
Housing Temperature Rise, Above
Ambient °C (°F)
3 4 5 6 7 8 9
0
60 (108)
50 (90)
40 (72)
30 (54)
20 (36)
10 (18)
3.6
22
Extension Length (in.)
815 °C (1500 °F) Oven Temperature
540 °C (1000 °F)
Oven Temperature
250 °C (482 °F) Oven Temperature
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
www.rosemount.com
Section 2 Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-4
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-7
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-11
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
Before connecting a Field Communicator in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
2-2
Figure 2-1. Installation Flowchart
START
HERE
Bench
Calibration?
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
Refer to Section 3: Configuration
FIELD INSTALL
Set Failure Mode
Switch
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED
Does not apply to the 644
with F
OUNDATION fieldbus
Reference Manual
00809-0400-4728, Rev AA
June 2011
2-3
Rosemount 644
MOUNTING Mount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
The 644 head mount installs:
In a connection head or universal head mounted directly on a sensor
assembly
Apart from a sensor assembly using a universal head
To a DIN rail using an optional mounting clip.
The 644 rail mount attaches directly to a wall or to a DIN rail.
Mounting a 644H to a DIN Rail
To attach a head mount transmitter to a DIN rail, assemble the appropriate rail
mounting kit (part number 00644-5301-0010) to the transmitter as shown in
Figure 2-2.
Figure 2-2. Assembling Rail Clip
Hardware to a 644H
Retrofitting a 644H for Use in an Existing Threaded Sensor Connection
Head
To mount a 644H in an existing threaded sensor connection head (former
option code L1), order the 644H retrofit kit (part number 00644-5321-0010).
The retrofit kit includes a new mounting bracket and all associated hardware
necessary to facilitate the installation of the 644H in the existing head. See
Figure 2-3.
Figure 2-3. Assembling 644H for
Use in an Existing L1
Connection Head
G-Rail (asymmetric) Top Hat Rail (symmetric)
Note: Kit includes Mounting Hardware and both types of Rail Kits.
Transmitter
Mounting
Hardware
Rail Clip
Transmitter
Mounting
Hardware
Rail Clip
Kit includes
replacement bracket
and screws.
Existing Threaded Sensor Connection Head
(Former option code L1)
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
2-4
INSTALLATION
Typical European
Installation
Head Mount Transmitter with DIN Plate Style Sensor
1. Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell before applying process pressure.
2. Assemble the transmitter to the sensor. Push the transmitter
mounting screws through the sensor mounting plate and insert the
snap rings (optional) into the transmitter mounting screw groove.
3. Wire the sensor to the transmitter (see Figure 2-7 on page 2-8).
4. Insert the transmitter-sensor assembly into the connection head.
Thread the transmitter mounting screw into the connection head
mounting holes. Assemble the extension to the connection head.
Insert the assembly into the thermowell.
5. Attach a cable gland into the shielded cable.
6. Insert the shielded cable leads into the connection head through the
cable entry. Connect and tighten the cable gland.
7. Connect the shielded power cable leads to the transmitter power
terminals. Avoid contact with sensor leads and sensor connections.
8. Install and tighten the connection head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = 644H Transmitter D = Transmitter Mounting Screws
B = Connection Head E = Integral Mount Sensor with Flying Leads
C = Thermowell F = Extension
A
D
B
C
E
F
Reference Manual
00809-0400-4728, Rev AA
June 2011
2-5
Rosemount 644
Typical North American
Installation
Head Mount Transmitter with Threaded Sensor
1. Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell.
Seal the nipple and adapter threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
4. Pull the sensor wiring leads through the universal head and
transmitter. Mount the transmitter in the universal head by threading
the transmitter mounting screws into the universal head mounting
holes.
5. Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
6. Install conduit for field wiring to the conduit entry of the universal
head. Seal conduit threads with silicone tape.
7. Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact
with other terminals.
8. Install and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = Threaded Thermowell D = Universal Head
B = Threaded Style Sensor E = Conduit Entry
C = Standard Extension
A
B
C
D
E
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
2-6
LCD Display Installation The LCD display provides local indication of the transmitter output and
abbreviated diagnostic messages governing transmitter operation.
Transmitters ordered with the LCD display are shipped with the meter
installed. After-market installation of the meter can be performed if the
transmitter has a meter connector (transmitter revision 5.5.2 or later).
After-market installation requires the meter kit (part number
00644-4430-0001), which includes:
LCD display assembly (includes LCD display, meter spacer,
and 2 screws)
Meter cover with O-ring in place
Figure 2-4. Installing the LCD
Display
Use the following procedure to install the meter.
1. If the transmitter is installed in a loop, secure the loop and disconnect
the power. If the transmitter is installed in an enclosure, remove the
cover from the enclosure.
2. Decide meter orientation (the meter can be rotated in 9
increments). To change meter orientation, remove the screws located
above and below the display screen. Lift the meter off the meter
spacer. Remove the 8-pin plug and re-insert it in the location that will
result in the desired viewing orientation.
3. Reattach the meter to the meter spacer using the screws. If the meter
was rotated 90° from its original position, it will be necessary to
remove the screws from their original holes and re-insert them in the
adjacent screw’s holes.
4. Line up the 10-pin connector with the 10-pin socket and push the
meter into the transmitter until it snaps into place.
5. Attach the meter cover; tighten at least one-third turn after the O-ring
contacts the transmitter housing. The cover must be fully engaged to
meet explosion-proof requirements.
6. Use a Field Communicator, AMS software, or a F
OUNDATION fieldbus
Communication tool to configure the meter to the desired display.
NOTE
Observe the following LCD display temperature limits:
Operating: –4 to 185 °F (–20 to 85 °C)
Storage: –50 to 185 °F (–45 to 85 °C)
644H
Captive Mounting Screws and Springs
Meter Spacer
LCD Display
10 pin Connector
Reference Manual
00809-0400-4728, Rev AA
June 2011
2-7
Rosemount 644
WIRING All power to the transmitter is supplied over the signal wiring. Use ordinary
copper wire of sufficient size to ensure that the voltage across the transmitter
power terminals does not drop below 9 Vdc.
If the sensor is installed in a high-voltage environment and a fault condition or
installation error occurs, the sensor leads and transmitter terminals could
carry lethal voltages. Use extreme caution when making contact with the
leads and terminals.
NOTE
Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals.
Abnormally high voltage can damage the unit. (Sensor and transmitter power
terminals are rated to 42.4 Vdc. A constant 42.4 volts across the sensor
terminals may damage the unit.)
The transmitters will accept inputs from a variety of RTD and thermocouple
types. Refer to Figure 2-5 on page 2-7 when making sensor connections.
Refer to Figure 2-6 on page 2-8 for F
OUNDATION fieldbus installations.
Use the following steps to wire the power and sensor to the transmitter:
1. Remove the terminal block cover (if applicable).
2. Connect the positive power lead to the “+” terminal. Connect the
negative power lead to the “” terminal (see Figure 2-7).
3. Tighten the terminal screws. When tightening the sensor and power
wires, the max torque is 6-in.-lbs (0.7 N-m).
4. Reattach and tighten the cover (if applicable).
5. Apply power (see “Power Supply”).
Figure 2-5. Transmitter Power,
Communication, and Sensor
Terminals
644H
Sensor
Terminals
Communication
Terminals
Power Terminals
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
2-8
Figure 2-6. Connecting a
F
OUNDATION fieldbus Host
System to a Transmitter Loop
Sensor Connections The 644 is compatible with a number of RTD and thermocouple sensor types.
Figure 2-7 shows the correct input connections to the sensor terminals on the
transmitter. To ensure a proper sensor connection, anchor the sensor lead
wires into the appropriate compression terminals and tighten the screws.
Figure 2-7. Sensor Wiring
Diagrams
Thermocouple or Millivolt Inputs
The thermocouple can be connected directly to the transmitter. Use
appropriate thermocouple extension wire if mounting the transmitter remotely
from the sensor. Make millivolt inputs connections with copper wire. Use
shielding for long runs of wire.
Power
Supply
6234 ft (1900 m) max
(depending upon cable characteristics)
Integrated Power
Conditioner and Filter
Terminators
(Spur)
(Spur)
(Trunk)
(The power supply,
filter, first
terminator, and
configuration
tool are typically
located in the
control room.)
Devices 1
through 16
F
OUNDATION
fieldbus
Configuration
Tool
Power/
Signal
Wiring
644 Sensor Connections Diagram
* Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these
RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical
tape.
2-wire
RTD and
3-wire RTD
and
4-wire RTD
and
T/C
and mV
*
1234
1234
1234
1234
Reference Manual
00809-0400-4728, Rev AA
June 2011
2-9
Rosemount 644
RTD or Ohm Inputs
The transmitters will accept a variety of RTD configurations, including 2-wire,
3-wire, or 4-wire. If the transmitter is mounted remotely from a 3-wire or 4-wire
RTD, it will operate within specifications, without recalibration, for lead wire
resistances of up to 60 ohms per lead (equivalent to 6,000 feet of 20 AWG
wire). In this case, the leads between the RTD and transmitter should be
shielded. If using only two leads, both RTD leads are in series with the sensor
element, so significant errors can occur if the lead lengths exceed three feet
of 20 AWG wire (approximately 0.05 °C/ft). For longer runs, attach a third or
fourth lead as described above.
Sensor Lead Wire Resistance Effect– RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and
has no impact on accuracy. However, a 3-wire sensor will not fully cancel
lead resistance error because it cannot compensate for imbalances in
resistance between the lead wires. Using the same type of wire on all
three lead wires will make a 3-wire RTD installation as accurate as
possible. A 2-wire sensor will produce the largest error because it directly
adds the lead wire resistance to the sensor resistance. For 2- and 3-wire
RTDs, an additional lead wire resistance error is induced with ambient
temperature variations. The table and the examples shown below help
quantify these errors.
Table 2-1. Examples of
Approximate Basic Error
Examples of Approximate Lead Wire Resistance Effect Calculations
Given:
Pt100 4-wire RTD: No lead wire resistance effect.
Pt100 3-wire RTD:
Sensor Input Approximate Basic Error
4-wire RTD None (independent of lead wire resistance)
3-wire RTD ± 1.0 in reading per ohm of unbalanced lead wire resistance
(Unbalanced lead wire resistance = maximum imbalance between
any two leads.)
2-wire RTD 1.0 in reading per ohm of lead wire resistance
Total cable length: 150 m
Imbalance of the lead wires at 20 °C: 1.5
Resistance/length (18 AWG Cu): 0.025 /m °C
Temperature coefficient of Cu (
Cu
): 0.039 / °C
Temperature coefficient of Pt(
Pt
): 0.00385 / °C
Change in Ambient Temperature (T
amb
): 25 °C
RTD Resistance at 0 °C (R
o
): 100 (for Pt 100 RTD)
Basic Error
Imbalance of Lead Wires
Pt
R
o

------------------------------------------------------------------=
Error due to amb. temp. variation
Cu
T
amb
 Imbalance of Lead Wires
Pt
R
o

-------------------------------------------------------------------------------------------------------------------------
=
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
2-10
Lead wire imbalance seen by the transmitter = 0.5
Pt100 2-wire RTD:
Lead wire resistance seen by the transmitter = 150 m × 2 wires ×
0.025
/m = 7.5
Basic error
0.5
0.00385 / C100 
--------------------------------------------------------------------------------- - 1.3 C==
Error due to amb. temp. var. of 25 °C
0.0039 / C25 C 0.5 
0.00385 / C100
-------------------------------------------------------------------------------------------------------
0.1266C==
Basic Error
Lead Wire Resistance
Pt
R
o

----------------------------------------------------------
=
Error due to amb. temp. variation
Cu
T
amb
 Lead Wire Resistance
Pt
R
o

-----------------------------------------------------------------------------------------------------------------=
Basic error
7.5
0.00385 / C100 
--------------------------------------------------------------------------------- -
19.5 C==
Error due to amb. temp. var. of 25 °C
0.0039 / C25 C 7.5 
0.00385 / C100
-------------------------------------------------------------------------------------------------------
1.9 C==
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98

Emerson 644 User manual

Category
Measuring, testing & control
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI